Eaton eLLK 92 LED 400A NE Operating Instructions Manual

Taper
Operating Instructions Manual
Explosionsgeschützte Notleuchten
Serie: eLLK(M)(S)92 LED 400A(800A) NE
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400A(800A) NE
Luminaires de sécurité pour atmosphères explosives
Série: eLLK(M)(S)92 LED 400A(800A) NE
Betriebsanleitung
Operating instructions
Mode d’emploi
C
R
OUS
E-HIND
S
S
ERIE
S
300 8000 1470 D/GB/F (-)
2
Explosionsgeschützte
Notleuchten Serie:
eLL. 92...A LED NE,
Explosion protected
emergency light fittings Series:
eLL. 92...A LED NE,
Luminaires de sécurité pour
atmosphères explosives Série:
eLL. 92...A LED NE,
Inhalt: Contents: Contenu:
1. Sicherheitshinweise .....................................6
2. Technische Daten ........................................6
3. Normenkonformität .....................................7
4. Funktionelle Besonderheiten .......................7
5. Installation eLLK 92..A LED NE;
eLLS 08...A LED NE .....................................7
6. Inbetriebnahme ...........................................8
7. Instandhaltung .............................................8
8 Reparatur / Instandsetzung ..........................8
9. Entsorgung / Wiederverwertung ..................9
1. Safety instructions .....................................10
2. Technical data ............................................10
3. Conformity with standards ........................ 11
4. Special functional features ......................... 11
5. Installation eLLK 92..A LED NE;
eLLS 08...A LED NE ................................... 11
6. Taking into operation ..................................12
7. Maintenance ..............................................12
8. Repair / Overhaul / Modifications...............12
9. Disposal / Recycling ...................................13
1. Consignes de sécurité ...............................14
2. Caractéristiques techniques ......................14
3. Conformité avec les normes ......................15
4. Particularités fonctionnelles .......................15
5. Installation eLLK 92..A LED NE;
eLLS 08...A LED NE ...................................15
6. Mise en service .........................................16
7. Entretien ....................................................16
8. Réparation / Remise en état ......................16
9. Évacuation des déchets /Recyclage ..........17
Konformitätsaussage
separat beigelegt.
Declaration of conformity,
enclosed separately.
Déclaration de conformité,
jointe séparément.
33 33 150
150
20
1205
188
44
76
130
880
Maßangaben in mm Dimensions en mm Dimensions in mm
Sechskant SW 13
M8, 14 tief
M25 x 1,5
LED 400 = 400
LED 800 = 700
LED 400 = 900
LED 800 = 1500
21
130
65
188
46
M8,
14 tief/deep/
profond
LED 400A = 400
LED 800A = 700
LED 400A = 900
LED 800A = 1500
3
Lampe / lamp 1


schwarz / black / noir
blau / blue / bleu
grün / gelb / green / yellow / vert / jaune
schwarz / black / noir
Lampe / lamp 2
L1
L2
L3 N
PE
N
L3
L2 L1
PE
L
L
L1
L2
L3 N
PE
N
L3
L2 L1
PE
L
L
L1 NL
L
L1
N
+UB
1-wire
-UB
1/3h
LL
LL1
LL2
LED
gr
1
2
3
5
6
7
8
4
remote
LED
rt
VE 12
schwarz / black / noir
schwarz / black / noir
LE
PE
N
L
L2
L1
L3
S2
S1
Schaltpläne / Wiring diagrams / Schémas de connexions
eLLK(M)(S) 92 400A(800A) LED NE
Fernschalter
Remote switch
Interrupteur à
distance
max 20 Notleuchten / max. 20 emergency light fittings / 20 luminaires de sécurité au maxi
A Lichtschalter
Light Switch
Interrupteur d’éclairage
B Brücke für Fernschalter, muss beim
Anschluss eines Schalters entfernt werden.
Link for remote switch, has to be
removed while connecting a switch.
Pont pour l'interrupteur à distance.
C Wahlweise für 3-h Betrieb entfernen.
To be removed for 3 h duration.
Charger des connexions pour autonomie
de 3 h.
eBK 12 /
NE 2710-12
eLLK 92 NE
eLLK 92 NE
eLLK 92 NE
eLLK 92 NE
Netzlampe/mains lamp/lampe-secteur
B
Notlampe/emerg. lamp/lampe de. sec
.
Nur bei Durchgangsverdrahtung
Only in case of through-wiring
Seulement en cas d’interconnexion
A
A
B
C
C
3 3 3 3
4
444
eLLM
eLLK ; eLLS
– Klemme L dient zur Dauerstromversorgung von Notleuchten.
Terminal L serves for permanent current supply of emergency luminaires.
– La borne L sert à l’alimentation en courant permanent des luminaires de sécurité.
VE 12 400 /
VE 12 800
D
D
eLLK - 2 - / eLLK - 4 -
4
Montagebilder/ Illustrations for mounting / Illustrations du montage
1
2
1
2
ca. 90°
ca. 90°
klick
ca. 90°
SW 13
Anschlussraum
für ein Kabel
Connection
compartment
for 1 cable
Compartiment
de raccordement
pour 1 câble
Anschlussraum
für 2 Kabel
Connection
compartment
for 2 cables
Compartiment
de raccordement
pour 2 câbles
4a
2
4
2
4
3
5
6
7
8
1
9
8a
5
t 2 mm
O=8,5 - 9,5 mm
10
Montagebilder / Illustrations for mounting / Illustrations du montage
Ausbau LED-Modul / LED-module replacement / Remplacement de module-LED
11
12
PRESS
PRESS
PRESS
6
Explosionsgeschützte Notleuchten
Serie: eLLK(M)(S)92 LED 400A(800A) NE
D
2. Technische Daten
1. Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und geeignet
qualifizierte, unterwiesene
Personen gemäß den nationalen Rechts-
vorschriften, einschließlich der einschlägi-
gen Normen für elektrische Geräte in
explosionsgefährdeten Bereichen
(EN/IEC 60079-14).
Die Leuchte darf nicht in den Zonen 0
und 20 eingesetzt werden!
Die Anforderungen der EN/IEC 60079-31
u.a. in Bezug auf übermäßige Staubab-
lagerungen und Temperatur, sind vom
Anwender zu beachten.
Die auf der Leuchte angegebenen
technischen Daten sind zu beachten!
Umbauten oder Veränderungen an der
Leuchte sind nicht zulässig!
Die Leuchte ist bestimmungsgemäß in
unbeschädigtem und einwandfreiem
Zustand zu betreiben!
Als Ersatz dürfen nur Originalteile von
Cooper Crouse-Hinds (CCH) / EATON
verwendet werden!
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CCH / EATON
oder einer qualifizierten „Elektrofach-
kraft“ durchgeführt werden!
Diese Betriebsanleitung während des
Betriebes nicht in der Leuchte lassen!
Beachten Sie die nationalen Unfall-
verhütungs- und Sicherheitsvorschriften
und die nachfolgenden Sicherheitshinwei-
se, die in dieser Betriebsanleitung mit
einem (
) gekennzeichnet sind!
EU-Baumusterprüfbescheinigung: BVS 09 ATEX E 034
Gerätekennzeichnung nach 2014/34/EU und der Normenreihe EN 60079:
Gas
II 2 G Ex db eb mb ib op is IIC T4 Gb
Staub
II 2 D Ex tb IIIC T80 °C Db
IECEx Konformitätsbescheinigung: IEC Ex BVS 09.0033
Gerätekennzeichnung der Normenreihe IEC 60079:
Gas Ex db eb mb ib op is IIC T4 Gb
Staub Ex tb IIIC T80 °C Db
Bemessungsspannung AC ± 10 % 120 V bis 254 V
Bemessungsfrequenzbereich: 50 bis 60 Hz
cos p > 0,95
Ausführung
LED 400A LED 800A
Bemessungsstrom 120 V AC/DC 0,40 A 0,60 A
230 V AC/DC 0,20 A 0,35 A
254 V AC/DC 0,18 A 0,30 A
Bemessungsleistung: 45 VA 70 VA
Notlicht Betriebsdauer
1,5 h
3,0 h (siehe Schaltplan)
Lichtstromfaktor (Notlicht) bezogen
auf 1 LED Reihe bei Nennbetrieb
bei 1,5 h
bei 3,0 h
LED 400A
ca. 95 %
ca. 65 %
LED 800A
ca. 65 %
ca. 45 %
Störfestigkeit nach EN 61000-6-2: erfüllt
Störaussendung nach EN 61000-6-4: erfüllt
Schutzklasse nach EN/IEC 61140 I
Schutzart nach EN/IEC 60529 IP66 / IP67
zulässige Umgebungstemperatur
(1)
eLL. 92 ...LED NE -25 °C bis +55 °C
Batterie datenhaltig -5 °C bis +35 °C
Lagertemperatur in der Originalverpackung -25 °C bis +45 °C
Klemmvermögen Anschlussklemme
2 x je Klemme
einadrig
mehradrig
min. 1,5 mm² 1,5 mm²
max. 6,0 mm² 6,0 mm²
Leiterquerschnitt bei Durchgangsverdrahtung 2,5 mm² für max. 16 A
Ex e-Kabel- und Leitungseinführung
Standardausführung M25 x 1,5
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
ØNm
Dichtung 1+2+3
1 2
3
min.
max.
(2)
8,0
10,0
1,5
2,0
Dichtung 1+2
1 2
min.
max.
(2)
10,0
13,0
2,3
2,6
Dichtung 1
1
min.
max.
(2)
13,5
17,5
1,3
2,3
Metall M20 x 1,5 Gewinde
Prüfdrehmomente Einschraubgewinde: 3,0 Nm
Prüfdrehmoment für Entlüftungsstutzen M25 x 1,5: 3,0 Nm
(1)
Intensive Sonneneinstrahlung in Regionen mit hohen Umgebungstemperaturen kann im Leuchten inneren zu
unzulässig hohen Erwärmungen führen. Eine Reduzierung der Lebensdauer des EVGs kann eine Folge hiervon
sein. Zur Vermeidung sollten in diesen Regionen tagsüber die Leuchten über einen Lichtsensor geschaltet
werden.
(2) Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften
kann der Klemmbereich variieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus
Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
7
5. Installation eLLK 92...A LED NE;
eLLS 08...A LED NE
Die für das Errichten und Betreiben von explosionsgeschützten
elektrischen Betriebs mitteln geltenden Sicherheitsvorschriften
gemäß des Gerätesicherheitsgesetzes sowie die allgemein anerkann-
ten Regeln der Technik sind einzuhalten! Transport und Lagerung der
Leuchte ist nur in Originalverpackung und der ange gebenen Lage
gestattet!
Achtung! Zeigt der Lichtaustritt nach oben sind zusätzliche
Schutzmaßnahmen gegen dauerhafte Wasseransammlungen im
Bereich der Wannendichtung zu treffen.
Hinweis:
Bei Montage der Leuchte mit Neigung um die Längsachse
(z.B.: Geländer-Montage), wird empfohlen, die Abdeckung des Zentral-
verschlusses gegen die Version mit der Ident-Nr. 22216904000 zu
tauschen.
5.1 Öffnen und Schließen der Leuchte
Den Zentralverschluss mit Steckschlüssel (Schlüsselweite SW 13) um
90° bis zur Raststellung drehen und Schutzwanne abklappen (Bild 2).
Achtung: Bei Verwendung von ungeeignetem Werkzeug ist ein
kraftschlüssiges Drehen des Zentralverschlusses nicht gewährleistet.
Dieser wird dadurch beschädigt.
Schutzwanne ein- und ausbauen (Bild 5 und 6).
Die Schutzwanne ist wahlweise beidseitig scharnierbar.
– Die Schutzwanne beim Zuschwenken etwas nach außen ziehen.
Dadurch streifen die Rastnocken nicht am Reflektor des
LED-Moduls (Bild 8a).
Schutzwanne zum Verschließen der Leuchte fest an das Leuchtenge-
häuse andrücken und den Zentralverschluss um 90° drehen.
Achten sie auf die plane Anbringung der Leuchte zur Sicherstel-
lung der Schutzart, siehe Bild 9-10! Beachten Sie beim Befestigen
des Montagezubehörs an der Leuchte die max. Gewindetiefe der
Montagebohrung von 14 mm!
Verwenden Sie keine zu langen Schrauben!
Montagezubehör: siehe CCH / EATON Katalog.
5.2 Netzanschluss
Zum Öffnen des Anschlussraumes grünen Drehgriff in Pfei l richtung bis
zum Anschlag drehen, dann ziehen und die Klappe abklappen
(Bild 3 und 4).
Für den Netzanschluss Leitungen mit Kupfer adern verwenden.
Die Leitung durch die Ex-Kabel- und Leitungseinführung einführen (Bild 4).
Für Leitungen von Ø 8 bis 10 mm Dichtungsein sätze 1,2 und 3,
von Ø 10 bis 13mm Dichtungsein sätze 1 und 2 und von
Ø 13,5 bis 17,5mm Dichtungseinsatz 1 verwenden. Auf korrekten Sitz
des verbleibenden Dichtungseinsatzes in der Verschraubung achten.
Die Leitungen an den Anschlussklemmen PE, N, L1, L, (L2, L3) gemäß
Klemmenbezeichnung anklemmen (Schaltpläne, Seite 3). Auch nicht
benutzte Klemmen anziehen!
Achtung: Ladeleitung L und Netzanschluss der Leuchte müssen
stets auf demselben Außen leiter des Netzes liegen!
Achtung: Bei nicht benutzten Kabel- und Leitungseinfüh rungen
ist die Schutz scheibe zu entfernen und die Einführung durch einen
Verschlussstopfen zu verschließen. Beim Verschließen mit einem
Verschlussstopfen stets beide Dichtungs einsätze verwenden! Bei
Metall-Kabeleinführungen sind die Schutzkappen der nicht benutz-
ten Ein führungen zu ent fernen und diese durch bescheinigte
Ex-Verschlussstopfen zu verschließen!
3. Normenkonformität
Diese Leuchte ist zum Einsatz in explosionsgefährdeten Be rei chen der
Zone 1, 2, 21 und 22 gemäß EN/IEC 60079-10-1 und EN/IEC 60079-10-2
geeignet.
Die Leuchte entspricht den aufgeführten Normen in der separat
beigelegten Konformitätserklärung.
Verweise auf Normen und Richtlinien in dieser Betriebsanleitung beziehen
sich immer auf die aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4. Funktionelle Besonderheiten
Ladung der Batterie
Bei Netzbetrieb wird die Batterie der Leuchte durch ein Konstantstrom-
Ladeteil geladen.
Die Ladung erfolgt über den ungeschalteten Außenleiter L, damit sie auch
bei ausgeschalteter Leuchte nicht unterbrochen wird. Der Ladestrom ist
bei ordnungsgemäßem Betrieb der Leuchte so bemessen, dass bei
entladener Batterie innerhalb von 14 h ca. 90% der Nennkapazität erreicht
werden. Er ist für eine Dauerladung der Batterie geeignet.
Der Tiefentladeschutz mit Wiedereinschaltsperre überwacht im Notbetrieb
die Batteriespannung und verhindert die Tiefentladung der Zellen.
Betriebsarten
Bei anliegender Netzspannung kann das LED-Modul in der Leuchte mit
dem Leuchten schalter ein- und ausgeschaltet werden.
Für Notlicht gibt es zwei Betriebsarten:
1. Unabhängige Betriebsart
Ist zwischen den Klemmen 3-4 (Schaltplan) eine Brücke eingesetzt, so
erfolgt bei Netz ausfall automatisch eine Umschaltung
auf Notlichtbetrieb (Werkseinstellung).
Bei der Mastleuchte eLLM 92 ist diese Brücke an den Klemmen S1 und
S2 (Schaltplan 2).
2. Abhängige Betriebsart
Durch Entfernen der Brücke (B) Klemmen 3-4 (eLLK /S) oder Brücke (D)
Klemmen S1-S2(eLLM 92) kann bei Netzausfall die Notlichtfunktion über
einen extern installierten Fernschalter separat ein- und ausgeschaltet
werden.
Ist der externe Fernschalter geöffnet, sind die Notlichtfunktionen sowie
die Zyklentests der Leuchte außer Funktion.
Der externe Fernschalter ist an den Klemmen 3-4 (eLLK /S) bzw. S1 und
S2 (eLLM 92) zu installieren.
Es sind max. 20 Leuchten an einen Fernschalter an schließbar (Schaltplan).
Einstellung der Notlicht-Betriebsdauer:
siehe Schaltplan
1,5 Stunden: Brücke C zwischen Klemme 5 und 6 anschließen
3,0 Stunden: Brücke C zwischen Klemme 5 und 6 entfernt.
Explosionsgeschützte Notleuchten
Serie: eLLK(M)(S)92 LED 400A(800A) NE
D
8
5.3 Installation eLLM 92 ...A LED NE
Die Montage und Installation der Mastleuchte erfolgt in folgender
Reihenfolge:
Die drei Kreuzschlitzschrauben im Deckel des Mastanschlussraumes
lösen (Bild 1, Pos. 1).
Anschlussraum durch Aufklappen des Deckels öffnen (Bild 1, Pos. 2).
Verriegelungsbügel des Kabel- und Leitungseinführungsstutzens bis zum
Anschlag hochziehen und Abdeckplatte abnehmen
(Bild 1, Pos. 3).
Kabel- und Leitungseinführungsstutzen aus den Führungsnuten im
Anschlussraum entnehmen.
Mastrohr oder das Rohr des Wandarmes von jeweils Ø 42 mm (Bild 1,
Pos. 4) bis zum Anschlag in die Öffnung der Mastleuchte einführen (Bild
1, Pos. 4a).
Leuchte ausrichten und die vormontierten Spezialschrauben M6
anziehen (Drehmoment 3,0 Nm, Bild 1, Pos. 5).
Leitung durch das Rohr einführen und auf die ent sprechende Länge
abisolieren.
Leitung durch die Ex-Kabel- und Leitungseinführung (KLE) einführen und
mit der Druckschraube der KLE die Leitung anziehen).
Kompletten Träger (mit eingeführter Leitung) in die Führungsnuten der
Mastleuchte einsetzen (Bild 1, Pos. 6).
Träger mit Verriegelungsbügel verschließen (Bild 1, Pos. 3).
Leitung in die Zugentlastung legen und anziehen (Bild 1, Pos. 7).
Leitung entsprechend der Klemmenbezeichnung anschließen.
Bei Verwendung von mehr- oder feindrähtigen Anschlussleitungen sind
die Aderenden entsprechend den geltenden nationalen und internationa-
len Vorschriften zu behandeln (z.B. Verwenden von Aderendhülsen).
5.4 LED Modul einsetzen
Im Auslieferungszustand ist das LED Modul (CML 17ATEX3243U /
IECEx CML 17.0137U) der Leuchte beigelegt.
Verwenden Sie nur zugelassene (CCH / EATON) Original teile!
Reflektor des LED Moduls nicht beschädigen.
Das LED Modul nur in der Originalverpackung transportieren.
Beim Herausnehmen aus der Verpackung und beim Einsetzen in die
Leuchte, nur an den seitlichen Kunststoffhalterungen anfassen
(Bild 6a).
Das LED Modul in die G13-Fassungen der Langfeldleuchte einsetzen Bild 7.
Hierzu das LED Modul an beiden Enden festhalten und gleichzeitig in
die G13-Fassungen einrasten. Ein deutliches "Klick" muss hörbar sein
(Bild 8).
6. Inbetriebnahme
Vor der Inbetriebnahme die korrekte Funktion und Installation der
Leuchte in Übereinstimmung mit dieser Betriebs anlei tung und
anderen zutreffenden Bestimmungen überprüfen!
Isolationsmessungen nur zwischen PE und Außenleiter L1 (L, L2, L3)
sowie zwischen PE und N durchführen!
– Messspannung: max. 1kV DC
– Messstrom: max. 10 mA
Achtung: Eine Isolationsmessung zwischen L und N darf nicht
durchgeführt werden, da sonst die Elektronik oder die Netzein gangs-
sicherung im VE-Gerät zerstört wird.
Leuchte verschließen.
Die Schutzwanne beim Zuschwenken etwas nach außen ziehen.
Dadurch streifen die Rastnocken nicht am Reflektor des LED-Moduls (Bild 8a).
Bei der Mastleuchte (eLLM 92...) ist der Anschlussraum durch die
vorher entfernte Ab deckplatte wieder abzudecken. Hierzu Verriegelungs-
bügel des Kabel- und Leitungsein führungsstutzens hochziehen (Bild 1,
Pos.3) und die Abdeckplatte sowie den Kabel- und Leitungsein führungs-
stutzen mit dem Verriegelungsbügel festklemmen. Mit den drei
Kreuzschlitzschrauben den Deckel des Anschlussraumes wieder
verschließen.
Die Netzspannung zu- und die Leuchte einschalten.
Die Leuchte mindestens 14 h eingeschaltet lassen, damit die Batterie
aufgeladen wird.
Danach einen Funktionstest der Notlicht schaltung durchführen, (siehe 7.
Instand haltung, Funktionstest).
- Die Notlichtfunktionsdauer beträgt mind. 1 min.
7. Instandhaltung
Die für die Instandhaltung, Wartung und Prüfung von explosions-
geschützten Betriebs mitteln geltenden Bestimmungen sind
einzuhalten (EN/IEC 60079-17 und EN/IEC 60079-19)!
7.1 Wartung
Im Rahmen der Wartung sind vor allem die Teile, von denen die Zünd-
schutzart abhängt, zu prüfen z. B.:
Gehäuse und Schutzwannen auf Risse und Beschädigungen.
Dichtungen auf Beschädigungen.
Klemmen und Verschlussstopfen auf festen Sitz.
Wegen der Gefahr elektrostatischer Aufladung darf die Leuchte nur mit
einem feuchten, nicht fasernden Tuch oder Schwamm gereinigt werden!
Dazu nur übliche Haushaltsspülmittel in Verdünnung mit Wasser
benutzen! Die Wassertemperatur darf maximal 50 °C betragen.
Anschließend mit klarem Wasser nachspülen, da sonst Spannungsrisse
in der Schutzwanne entstehen können!
Die Lampenwechselintervalle der Lampen hersteller sind zu beachten!
7.2 Funktionstest Notlicht
Netzspannung der Leuchte ausschalten.
Die LED-Reihe Notlichtbetrieb (Seite mit grünem Punkt) muss leuchten.
Die Notlichtfunktionsdauer beträgt mind. 1 min.
Folgende Prüfzeiten sollten bei einem Funktions test nicht überschritten
werden, das sonst keine Notlichtreserve zur Verfügung steht:
Batteriesatz mit 1,5 h Notlicht: 60 min.
Batteriesatz mit 3,0 h Notlicht: 120 min.
Hinweis: Weitere Informationen zum automatischen Funktions- und
Betriebsdauertest siehe beiliegende Betriebsanleitung des
eBK12 Nr. 3 2211 000 172
8. Reparatur / Instandsetzung
Das Betriebsmittel vor dem Öffnen oder vor Instandhaltungsarbei-
ten erst spannungsfrei schalten!
Die Batterie ist auszubauen.
I
nstandsetzungsarbeiten / Reparaturen dürfen nur mit CCH / EATON
Originalersatzteilen vorgenommen werden.
Bei Schäden an dem LED Modul ist nur ein Austausch zulässig.
Im Zweifelsfalle ist das betroffene LED Modul an Cooper Crouse-
Hinds / EATON zur Reparatur zurückzugeben.
Umbauten oder Änderungen am LED Modul sind nicht gestattet.
Reparaturen, die den Explosionsschutz betreffen, dürfen nur von
CCH / EATON oder einer qualifizierten Elektrofachkraft in Überein-
stimmung mit national geltenden Regeln durchgeführt werden
(EN/IEC 60079-19).
Verwenden Sie nur zugelassene CCH / EATON Original ersatzteile
(siehe (CCH / EATON) Ersatzteilliste)!
Explosionsgeschützte Notleuchten
Serie: eLLK(M)(S)92 LED 400A(800A) NE
D
9
9. Entsorgung / Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die jeweils geltenden
nationalen Abfallbeseitigungsvorschriften zu beachten.
Die Kunststoffmaterialien sind mit Materialkennzeichnungen versehen.
Zusätzliche Informationen zur Entsorgung des Produktes können Sie bei
Ihrer zuständigen Cooper Crouse-Hinds / EATON Niederlassung erfragen.
Programmänderungen und -ergänzungen sind vorbehalten.
8.1 LED Modul auswechseln
Das Auswechseln des LED Moduls kann ohne Freischalten vom Netz
durchgeführt werden, da die Fassungen beim Öffnen der Schutzwanne
durch einen allpoligen Trennschalter spannungsfrei geschaltet werden.
Beachten Sie jedoch, dass nationale Vorschriften oder lokale Anwen-
dungsrichtlinien hiervon abweichend sein können!
Das LED Modul, wie in Bild 11 und Bild 12 gezeigt, herausnehmen.
Betriebsart
LED Modul 400/800
Netz
LED Modul 400/800
Netz / Not
Achtung! Chemische Beständigkeit beachten.
Nur mit feuchtem Tuch säubern.
Warning! Do not use chemical cleaner.
Clean with a damp cloth only.
Important! Attention à la resistance chimique.
Nettoyer uniquement avec un
chiffon humide.
Batterie
Netz
oder
ok
oder
ok
VE 12 defekt
VE 12 defekt
Not
ok
Batterie entladen
Lampenfehler
Batterie Fehler
Netzschalter AUS
LED
rot,
-
grün AN
Netzschalter EIN
LED
rot,
-
grün BLINKT
LED Reihe vom Modul AUS
○ ○
LED
rot,
-
grün AUS
LED Reihe vom Modul AN
LED
Modul
400/800
Fehleranalyse: eLL. .. NE;
(Test bei Dauerschaltung der Leuchte - Kombinationen von mehren Fehlern sind nicht erfasst)
Weitere Infos zur Betriebs- und Störungsanzeige des eBK12 siehe beiligende Betriebsanleitung des eBK12 Nr. 3 2211 000 172.
Explosionsgeschützte Notleuchten
Serie: eLLK(M)(S)92 LED 400A(800A) NE
D
10
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400A(800A) NE
GB
2. Technical data
1. Safety instructions
Target group:
For skilled electricians and
suitable qualified, instructed
personnel in accordance with national
legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
The light fitting must not be operated in
zone 0 or zone 20 hazardous areas!
The light fitting must not be use while
excessive deposit of dust
(accd. IEC/EN 60079-31) exist.
The technical data indicated on the light
fitting are to be observed!
Changes of the design and modifica-
tions to the light fitting are not
permitted!
The light fitting shall be operated as
intended and only in an undamaged and
perfect condition!
Only genuine Cooper Crouse-Hinds
(CCH) / EATON spare parts may be used
for replacement!
Repairs that affect the explosion
protection, may only be carried out by
CCH / EATON or a qualified "electrician”!
These operating instructions shall not
be kept inside the light fitting during
operation!
The national safety rules and regulations
for prevention of accidents and the
following safety instructions which are
marked with an (
) in these operating
instructions shall be observed!
EU-Type Examination Certificate:
BVS 09 ATEX E 034
Marking acc. to 2014/34/EU and standard series EN 60079:
gas
II 2 G Ex db eb mb ib op is IIC T4 Gb
dust
II 2 D Ex tb IIIC T80 °C Db
IECEx Certificate of Conformity:
IEC Ex BVS 09.0033
Category of application standard series IEC 60079:
gas
Ex db eb mb ib op is IIC T4 Gb
dust Ex tb IIIC T80 °C Db
Rated voltage AC ± 10 % 120 V to 254 V
Rated frequency range: 50 to 60 Hz
cos p > 0,95
Version
LED 400A LED 800A
Rated current: 120 V AC/DC 0.40 A 0.60 A
230 V AC/DC 0.20 A 0.35 A
254 V AC/DC 0.18 A 0.30 A
Rated power: 45 VA 70 VA
Emergency operation time
1.5 h
3.0 h (see wiring diagram)
Luminous flux factor (emerg. light)
related to 1 LED row in rated
operation:
at 1.5 h
at 3.0 h
LED 400A
approx. 95 %
approx. 65 %
LED 800A
approx. 65 %
approx. 45 %
Immunity from interference to IEC/EN 61000-6-2: fulfilled
Emission of interferences to EN 61000-6-4: fulfilled
Insulation class to IEC/EN 61140 I
Degree of protection IEC/EN 60529 IP66 / IP67
Perm. ambient temperature
(1)
eLL. 92 ..LED NE -25 °C to +55 °C
Battery apecitied -5 °C to +35 °C
Storage temperature in original packing -25 °C to +45 °C
Supply terminal clamping capacity
2 x per terminal
single-wire
multi-wire
min. 1.5 mm² 1.5 mm²
max. 6.0 mm² 6.0 mm²
Conductor cross-section with through-wiring 2.5 mm² for max. 16 A
Ex-e cable entry
Standard version M25 x 1.5
suitable cables and test torques of the pressure
screw
ØNm
Seal 1+2+3
1 2
3
min.
max.
(2)
8.0
10.0
1. 5
2.0
Seal 1+2
1 2
min.
max.
(2)
10.0
13.0
2.3
2.6
Seal 1
1
min.
max.
(2)
13.5
17.5
1. 3
2.3
Metal M20 x 1.5 thread
Test torque for screw in thread cable entry: 3.0 Nm
Test torque for breathing plug M25 x 1,5: 3.0 Nm
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside of
the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those luminaires
should be switched off during daytime by a photocell control.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
11
5. Installation eLLK 92..A LED NE;
eLLS 08...A LED NE
The respective national regulations as well as the general rules of
engineering which apply to the installation and operation of
explosion protected apparatus, will have to be observed!
Transport and storage of the luminaire is permitted in original
packing and specified position only!
Installing the light output upwards additional protection has to
be assembled to avoid permanent water accumulations at the
protective bowl gasket area.
Mind:
For handrail mounting (e.g. mounted at 45°) we recommend replacing the
existing cover of the locking bolt with the version part no 22216904000.
5.1 Opening and closing the light fitting
Turn the central locking device with a box spanner (opening of the
spanner SW 13) through 90° to its lock-in position and fold down the
protective bowl, see fig. 3.
Caution: If an unsuitable tool is used, frictional turning of the
central locking device can not be guaranteed and the device may be
damaged.
Fit in and remove the protective bowl acc. to fig. 5 and 6.
The protective bowl can, at option, be hinged on either side.
When closing the protective bowl, pull out slightly to avoid the catch
mechanism touching the LED module reflector (Photo 8a)
To close the light fitting, press the protective bowl tightly onto the
luminaire housing and turn the central locking device through 90°.
The integrity of the fitting may be compromised if the fixing
centres are not correctly aligned, see fig. 9 - 10. When fixing the
mounting accessories onto the light fitting, observe the max. depth
of thread of 14 mm!
Do not use too long screws!
Accessories for mounting: See CCH / EATON catalogue.
5.2 Mains connection
To open the connection box, turn the green handle to its stop in the
direction of arrow, then pull it and fold down the flap (fig. 3 and 4).
For power connection, use cables with copper conductor.
Introduce the cable through the Ex cable entry (fig. 4). Use sealing
inserts 1,2 and 3 for cables from 8 to 10 mm Ø, sealing inserts 1 and 2
for cables from 10 to 13 mm Ø and sealing insert 1 for cables from 13,5
to 17,5 mm Ø. Pay attention to the proper fit of the sealing insert
remaining in the cable gland.
Connect the conductors to the terminals
PE, N, L1, L, (L2, L3) in accordance with the terminal marking (wiring
diagrams, page 3). Also tighten vacant terminals!
Mind: The charging conductor L and
the luminaire’s mains connection must always be connected to the
same external conductor of the mains supply!
Attention: In case of unused cable entries, remove their protective
cover and close the entries with a blanking plug. When closing the
gland with a blanking plug, always use both sealing inserts! When
metal cable entries are used, the protective caps of the unused
entries are to be removed and the entries to be closed with certified
Ex blanking plugs!
3. Conformity with standards
The light fitting is suitable for use in zone 1, 21, 2 and 22 hazardous areas
acc. to IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The light fitting is conform to the standards specified in the EU-Declara-
tion of conformity, enclosed separately.
References to standards and directives in these operating instructions
always relate to the latest version. Other additions (e.g. details relating to
the year) shall be observed.
4. Special functional features
Charging the battery
In mains operation the light fitting is charged by means of a constant
current charger. Charging takes place via the unswitched external phase L
to prevent an interruption, even when the luminaire is switched off. With
regular operation of the light fitting the charging current is measured so
that a flat battery will have obtained approx. 90% of its rated capacity
within 14 h. It is suitable for a continuous charge of the battery.
In emergency operation a deep discharge protection with reclosure
preventing device monitors the battery voltage and prevents the
accumulators deep discharge.
System modes
When a voltage is applied, the LED module in the light fitting can be
switched on and off with the light switch.
There are two system modes for emergency operation:
1. Independent system mode:
If the terminals on the terminal block 3-4 (wiring diagrams) are bridged,
there will be an automatic changeover to emergency operation in the
event of a mains failure.
On the eLLM92 pole mounted light fitting this bridge is established on the
terminals S1 and S2 (wiring diagram).
2. Dependent system mode
When removing the bridge (B), terminal 3-4 (eLLK/S) or bridge (D) terminal
S1 - S2 (eLLM 92) the emergency light function can be separately
switched on and off via a remote switch installed outside in the event of a
mains failure. Connect the remote switch to terminal 3-4 (eLLK/S) or to S1
and S2 (eLLM 92). Max.
20 luminaires can be connected to one remote switch (wiring diagram).
Setting the emergency duration:
1.5 hours: connect Bridge "C" between terminals 5 and 6
3.0 hours: remove Bridge "C" between terminals 5 and 6.
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400A(800A) NE
GB
12
5.3 Installation eLLM 92...A LED NE
The pole mounted light fitting is mounted and installed in the following
order:
Unscrew the three recessed head screws in
the cover of the pole connecting compartment (fig. 1, item 1).
Open the connecting compartment by folding down the cover
(fig. 1, item 2).
Pull the stay shackle of the cable entry socket up to its stop and take off
the cover plate (fig. 1, item 3).
Remove the cable entry sockets from the guiding grooves in the
connecting compartment.
Then the pole mounting tube or the tube of the wall socket of 42 mm [
each (fig. 1, item 4) is pushed home into the opening of the light fitting
(fig. 1, item 4a).
Adjust the light fitting and screw down the pre assembled M 6 special
screws (torque of 3.0 Nm, fig. 1, item 5).
Introduce the cable through the tube and strip the insulation to the
required length.
Introduce the cable through the Ex cable entry (KLE) and tighten it with
the pressure screw of the cable entry.
The complete support (with the cable being introduced) is put into the
guiding grooves of the pole mounted light fitting (fig. 1, item 6).
Lock the support with the stay shackle
(fig. 1, item 3).
Insert the cable into the pull-relief and tighten it (fig. 1, item 7).
Then connect the cable in accordance with the terminal marking.
If multi- or fine-wire connecting cables are used, the wire ends will have
to be handled in acc. with the applicable national and international rules.
(e.g. use of sleeves for strands).
5.4 LED module inserting
As delivered, the LED module (CML 17ATEX3243U /
IECEx CML 17.0137U) is attached to the light fitting.
Use only approved CCH / EATON stock items in stock!
Do not damage the LED module reflector.
Only transport the LED module in its original packing.
When removing from the packaging and fitting in to the light fitting,
only handle the unit by the plastic parts at the ends (Fig 6a).
Insert the LED module in the G13 versions of linear luminaire fig. 7.
Snap the module into the G13-sockets of the light fitting, whereby a
distinct clicking sound can be heard (Fig. 2.8).
6. Taking into operation
Prior to operation, check the light fitting for its proper functioning
and installation in compliance with these operating instructions and
other applicable regulations!
Only carry out insulation measurements between PE and the external
conductor L1 (L, L2, L3) as well as between PE and N.
– measuring voltage: max. 1 kV DC
– measuring current: max. 10 mA
Mind: There must no insulation measurement be carried out
between L and N, since that would destroy the electronics (mains
input fuse in the VE unit).
Then the luminaire will have to be closed. The terminal compartment of
the pole mounted light fitting (eLLM 92..) is again to be covered with the
cover plate that was previously removed.
To that effect, pull up the stay shackle of the cable entry socket (fig. 1,
item 3) and clamp down the cover plate and the cable entry socket with
the stay shackle. Again screw down the cover of the terminal compart-
ment with the three recessed head screws.
Switch on the mains voltage and then the light fitting.
Leave the light fitting switched on for at least
14 hours so that the battery will be recharged.
After that, release a function test of the emergency light connection,
see 7. Maintenance, function test.
7. Maintenance
The national regulations applicable to the maintenance, servicing
and test of apparatus for explosive atmospheres as well as the
general rules of engineering will have to be observed
(IEC/EN 60079-17 and IEC/EN 60079-19)!
7.1 Servicing
When servicing, in particular those components that affect the explosion
protection, will have to be checked, e. g.:
Housing and protective bowl for any cracks or damages.
Gaskets for their perfect condition.
Terminals and blanking plugs for their firm fit.
Because of the risk of an electrostatic charge, the light fitting shall only
be cleaned with a damp, non-fibrous cloth or sponge!
Only use customary household washing-up liquid diluted in water! The
water temperature may be max. 50 °C.
After that, rinse with clear water to prevent the risk of tension cracks in
the protective bowl!
Lamp replacement: Keep replacement intervals as specified by the lamp
manufacturer!
7.2 Test of the emergency light function
Switch the luminaire off the mains voltage.
The emergency operation LED row (row with green spot) must light up
The emergency function lasts at least 1 min..
A function test should not exceed the following test periods:
Battery set for 1.5 h emergency light: 60 min.
Battery set for 3.0 h emergency light: 120 min.
Note: See the enclosed operating instructions for eBK12, No. 3 2211 000 172
for further information on the automatic function and operation duration
test
8. Repair / Overhaul / Modifications
Prior to replacing or removing any components, observe the
following:
Cut the apparatus off the voltage before opening or servicing it!
The battery have to be removed.
Repairs and overhaul may only be carried out with genuine Cooper
Crouse-Hinds / EATON spare parts.
In the event of damage, replacement of these components is
mandatory. In case of doubt, the respective apparatus shall be sent
to CCH / EATON for repair.
Reconstruction or modifications to LED module are not permitted.
Repairs that affect the explosion protection, may only be carried
out by CCH / EATON or a qualified electrician in compliance with the
applicable national rules (IEC/EN 60079-19).
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400A(800A) NE
GB
13
9. Disposal / Recycling
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
In order to facilitate the recycling of individual components, plastic parts
are provided with the identification mark of the plastic material used.
In case of disposal you can obtain additional information from your Cooper
Crouse-Hinds / EATON branch.
Subject to modifications or supplement of the product range.
8.1 LED-module replacement
LED-module replacement can be done without cut off the luminaire
from mains supply, because an all pole switch will isolate the
lampholders while opening the protective bowl.
Notice: Observe national standards or directions for use which can be
divergent to this!
The LED-module have to be replaced as shown in fig. 11 and 12.
Operation
LED Modul 400/800
Mains
LED Modul 400/800
Mains / Emergency
Achtung! Chemische Beständigkeit beachten.
Nur mit feuchtem Tuch säubern.
Warning! Do not use chemical cleaner.
Clean with a damp cloth only.
Important! Attention à la resistance chimique.
Nettoyer uniquement avec un
chiffon humide.
Battery
Mains
or
ok
or
ok
VE 12 faulty
VE 12 faulty
Emergency
ok
V
Battery low
,
Lamp fault
v
Battery fault
Mains OFF
v
LED
red
-
green ON
Mains ON
,
LED
red,
-
green flashing
LED row of module OFF
V V
LED
red,
-
green OFF
LED row of module ON
Fault indicator: eLL. .. NE;
(Test during continuous switching of light fitting - combinations with several faults are not registered)
See the enclosed operating instructions for eBK12, No. 3 2211 00 172, for further information on the function and fault indication.
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400A(800A) NE
GB
14
Luminaires de sécurité pour atmosphères explosives
Série: eLLK(M)(S)92 LED 400A(800A) NE
F
2. Caractéristiques techniques
1. Consignes de sécurité
Groupe cible:
Pour les électriciens qualifiés et
les personnels ayant reçu les
formations adéquates, conformément à la
législation nationale en vigueur et, si
applicable, à la norme CEI/EN 60079-14
sur les installations électriques pour les
atmosphères explosives.
Il n’est pas permis d’utiliser le luminaire
dans la zone 0 et zone 20 !
L’appareil ne doit pas être mis en
marche lorsque l’épaisseur du dépôt de
poussière est trop importante
(selon CEI/EN 60079-31).
Les caractéristiques techniques
indiquées sur le luminaire doivent être
respectées !
Il n’est pas permis de transformer ou de
modifier le luminaire !
Le luminaire ne doit être exploité que
pour la fonction qui lui est dévolue et
qu’en état intact et parfait !
Seules des pièces de rechange d’origine
Cooper Crouse-Hinds (CCH) / EATON
doivent être employées pour le
remplacement !
Des réparations qui portent sur la
protection contre l’explosion, ne
doivent être exécutées que par CCH /
EATON ou par un «électricien» qualifié !
Ce mode d’emploi ne doit pas être
laissé dans le luminaire pendant son
exploitation !
Veuillez respecter les prescriptions
nationales de sécurité et de prévoyance
contre les accidents ainsi que les
consignes de sécurité qui sont marquées
d’un (
) dans ce mode d’emploi!
EU-Type Examination Certificate: BVS 09 ATEX E 034
Marking acc. to 2014/34/EU and standard series EN 60079:
gaz
II 2 G Ex db eb mb ib op is IIC T4 Gb
poussière
II 2 D Ex tb IIIC T80 °C Db
IECEx Certificate of Conformity: IEC Ex BVS 09.0033
Category of application standard series IEC 60079:
gaz Ex db eb mb ib op is IIC T4 Gb
poussière Ex tb IIIC T80 °C Db
Gamme des tensions CA ± 10 % 120 V à 254 V
Gamme des fréquences: 50 à 60 Hz
cos p > 0,95
Version
LED 400A LED 800A
Courant nom. en A avec: 120 V AC/DC 0,40 0,60
230 V AC/DC 0,20 0,35
254 V AC/DC 0,18 0,30
Puissance nominale: 45 VA 70
Temps de fonctionnement d'urgence
1,5 h
3,0 h (voir schémas de connexions)
Facteur de flux lumineux (éclairage
des secours) par rapport à 1 lampe
en service nominal
à 1,5 h
à 3,0 h
LED 400A
env. 95 %
env. 65 %
LED 800A
env. 65 %
env. 45 %
Antiparasitage selon EN 61000-6-2: remplie
Emission de parasites selon CEI/EN 61000-6-4: remplie
Classe d’isolation selon CEI/EN 61140 I
Mode de protection CEI/EN 60529 IP66 / IP 67
Température ambiante
(1)
eLL. 92 ...LED NE -25 °C à +55 °C
données spécifié batterie -5 °C à +35 °C
Température de stockage (emballage d'origine) -25 °C à +45 °C
Capacité de serrage des bornes, 2 x par borne unifilaire multifilaire
min. 1,5 mm² 1,5 mm²
max. 6,0 mm² 6,0 mm²
Section transversale du conducteur en
cas d’interconnexion
2,5 mm
2
pour 16 A au maxi
Entrée de câble Ex-e
modèle standard M25 x 1,5
câbles appropriés et couples d’essai de la vis
de pression
ØNm
Garniture 1+2+3
1 2
3
min.
max.
(2)
8,0
10,0
1,5
2,0
Garniture 1+2
1 2
min.
max.
(2)
10,0
13,0
2,3
2,6
Garniture 1
1
min.
max.
(2)
13,5
17,5
1,3
2,3
métall M20 x 1,5 fil
Couple d' essai pour l’entrée de câble: 3,0 Nm
Couple d'essai pour bouchon de vidange reniflard
M25 x 1,5:
3,0 Nm
(1)
Le rayonnement solaire intensive dans des régions à température ambiante élevée peut provoquer à l’intérieur
du luminaire un échauffement extensif. Ceci peut impliquer une réduction de durée de vie considérable. Pour
pallier à cela, il est préconiser d’utiliser un interrupteur photoélectrique.
(2)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
15
5. Installation eLLK 92..A LED NE; eLLS 08...A LED NE
Lors de l’installation et de l’exploitation des appareils électriques
pour atmosphère explosive, les règlements nationaux ainsi que les
règles de la technique généralement reconnues doivent être
respectés ! Le transport et le stockage ne sont permis que dans
l’emballage original et dans la position spécifiée !
Si le luminaire est installé avec la vasque vers le haut, des
précautions devront être prises pour éviter l’accumulation d’eau au
niveau du joint de la vasque.
Remarque:
Si le luminaire est monté incliné par rapport à l’axe longitudinal (par ex.:
montage sur une rampe), il est recommandé de remplacer le couvercle du
verrou central par la version portant la référence 22216904000.
5.1 Ouverture et fermeture du luminaire
Tourner le verrou central avec la clé à douille (ouverture de clé SW 13) de
90°dans sa position de crantage et rabattre la vasque de protection, voir
fig. 2.
Attention: En cas d’utilisation d’outillage inapproprié, la liaison
par adhérence lors du serrage du verrou central n’est pas garantie.
Ceci provoque I’endommagement du verrou.
Monter et démonter la vasque de protection suivant fig. 5 et 6.
La vasque de protection est pourvue d’une charnière des deux côtés ce
qui permet de la suspendre de chaque côté.
Pour fermer le luminaire, presser la vasque de protection contre le
boîtier du luminaire et tourner le verrou central de 90°.
Dimensions de fixation : voir fig. 1.
L'intégrité de l'ajustage de précision peut être compromise si les
centres de réparation ne sont pas correctement alignés, voir fig.
10-12. Respecter lors de la fixation des accessoires de montage au
luminaire que les trous de fixation doivent avoir une profondeur du
pas de 14 mm au maxi.
Ne pas utiliser de vis trop longues !
Accessoires pour le montage : voir le catalogue CCH /EATON.
5.2 Branchement sur secteur
Afin d’ouvrir la boîte de connexion, tourner la poignée vert jusqu’à sa
butée, puis la tirer et rabattre la trappe (fig. 3 et 4).
Utiliser câbles avec conducteur en cuivre pour connexion au réseau.
Introduire le câble par l’entrée de câble Ex-e (fig. 4). Utiliser des inserts
d'étanchéité 1,2 et 3 pour les câbles de 8 à 10 mm Ø, inserts 1 et 2
d'étanchéité pour les câbles 10-13 mm Ø et étanchéité insert 1 pour
câbles de 13,5 à 17,5 mm Ø. Veiller au propre logement du joint
d’étanchéité resté dans la presse-étoupe.
Connecter les câbles aux bornes PE, N, L1, L, (L2, L3) suivant le
repérage des bornes (schéma des connexions sur page 3). Serrer aussi
les bornes non utilisées !
Attention: Le raccordement du fil de charge L et le branchement
sur secteur du luminaire doivent toujours être établis sur le même
conducteur extérieur du secteur !
Attention: En cas d’entrées de câble non utilisées, leur disque
protecteur doit être enlevé, et l’entrée doit être fermée avec un
bouchon de fermeture. Lorsqu’ un bouchon de fermeture est mis,
toujours utiliser les deux joints d’étanchéité !
En cas d’entrées de câble métalliques, enlever les obturateurs
protecteurs des entrées non utilisées et les fermer avec des bou-
chons de fermeture Ex certifiés !
3. Conformité avec les normes
Ce luminaire convient à l’utilisation dans les zones 1, 2 , 21 et 22 d’une
atmosphère explosive selon CEI/EN 60079-10-1 et CEI/EN 60079-10-2.
Les Appareils sont conformes aux normes reprises dans la déclaration de
conformité, jointe séparément.
Les références aux normes et directives dans cette notice se réfèrent
toujours à la dernière version. Les suppléments éventuels doivent
également être respectés.
4. Particularités fonctionnelles
Charge de la batterie
En cas de fonctionnement sur secteur, la batterie du luminaire est
chargée par un chargeur à courant continu. La charge se fait par la phase
L non commutée afin de ne pas l’interrompre, lorsque le luminaire a été
mis hors service. Lors d’une exploitation régulière du luminaire, le courant
de charge est mesuré tel qu’environ 90% de la capacité nominale d’une
batterie déchargée soient obtenus en 14 heures. Il convient à une charge
continue de la batterie.
En service d’éclairage de sécurité, la protection de fin de décharge avec
barrage de réenclenchement surveille la tension de batterie et prévient la
décharge profonde des accumulateurs.
Modes de couplage
Le secteur présent, les lampes dans le luminaire peuvent être allumées et
éteintes avec l’interrupteur d’éclairage.
Il y a deux modes de couplage pour l’éclairage de secours:
1. Mode indépendant
Si les bornes du bornier 3-4 (schémas des connexions) sont pontées, une
commutation automatique en éclairage de secours se fera automatique-
ment en cas d’une panne de secteur. Au luminaire eLLM 92 ce pont est
installé aux bornes S1 et S2 (schéma des connexions).
2. Mode dépendant
Si le pont (B) bornes 3-4 (schémas des connexions) ou pont (D) bornes
S1-S2 est enlevé, la fonction d’éclairage de secours peut être enclenchée
ou déclenchée séparément à l’aide d’un interrupteur à distance installé à
l’extérieur.
L’interrupteur à distance doit être connecté à la borne 3-4 (eLLK /S) ou aux
bornes S1 et S2 (eLLM 92). 20 luminaires au maxi peuvent être connectés
à un interrupteur à distance (schéma des connexions 4).
Réglage de l’autonomie de l’éclairage de secours:
1,5 heures : Raccorder les deux conducteurs sous la borne 1.
3,0 heures : Raccorder un conducteur sous la borne 1 et 1 conducteur sous
la borne 0 (schémas des connexions 1 et 2).
Luminaires de sécurité pour atmosphères explosives
Série: eLLK(M)(S)92 LED 400A(800A) NE
F
16
5.3 Installation eLLM 92 ... LED NE
Le montage et l’installation du luminaire pour fixation sur mât se fait dans
l’ordre suivant :
Dévisser les trois vis à fentes en croix dans le couvercle du comparti-
ment de raccordement du poteau (fig. 1, pos. 1).
Ouvrir le compartiment de raccordement en rabattant le couvercle (fig.
1, pos. 2).
Lever l’étrier de verrouillage de la tubulure d’entrée de câble jusqu’à sa
butée et enlever la plaque de recouvrement (fig. 1, pos. 3).
Sortir la tubulure d’entrée de câble des rainures de guidage dans le
compartiment de raccordement.
Introduire le tube du poteau ou de la console d’un diamètre de 42 mm
chacun (fig. 1, pos. 4) jusqu’à la butée dans l’orifice du luminaire
(fig.1, pos. 4a).
Ajuster le luminaire et serrer à fond les vis spéciales M6 montées au
préalable avec un couple de 3,0 Nm (fig. 1, pos. 5).
Puis introduire le câble par le tube et le dénuder de la longueur requise.
Introduire le câble par l’entrée de câble Ex (KLE) et le serrer à fond au
moyen de la vis de pression de l’entrée de câble.
Puis le support complet (avec le câble mis en place) est posé dans les
rainures de guidage du luminaire pour fixation sur mât (fig. 1, pos. 6).
Verrouiller le support au moyen de l’étrier de verrouillage (fig. 1, pos. 3).
Poser le câble dans la décharge de traction et le serrer à fond
(fig. 1, pos. 7).
Puis raccorder à vis le câble suivant le repérage des bornes.
En cas d’utiliser des câbles de connexion multifilaires ou à fils de faible
diamètre, les bouts de fil doivent être traités selon la règlementation
nationale et internationale y applicable (par ex. emploi des embouts).
5.4 Mise en place de module LED
A la livraison, le module LED est fixé à la lampe (CML 17ATEX3243U /
IECEx CML 17.0137U).
N'utiliser que des pièces d'origine (CCH / EATON) agréés!
Insérez le module LED dans les versions G13 de luminaire linéaire Fig. 7.
Pour cela, le maintien du module LED et à ses deux extrémités en même
temps s'engager dans le G13. un "clic" doit être entendu (Fig. 8).
6. Mise en service
Avant la mise en service du luminaire, il faut vérifier s’il est
branché et fonctionne en conformité avec ce mode d’emploi et avec
d’autres règlements y applicables !
Des mesurages d’isolation ne doivent être effectués qu’entre PE et le
conducteur extérieur L1 (L, L2, L3) ainsi qu’entre PE et N !
– tension de mesurage: 1 kV CC au maxi
– courant de mesurage: 10 mA au maxi
Il n’est pas permis d’effectuer un mesurage d’isolation entre L et
N puisque cela détruirait l’électronique (fusible d’entrée secteur dans
le bloc VE).
Puis fermer le luminaire. Le compartiment de raccordement du
luminaire pour fixation sur mât (eLLM 92..) doit être recouvert de la
plaque de recouvrement qui était enlevé auparavant. Pour cela, lever
l’étrier de verrouillage de la tubulure d’entrée de câble (fig. 1, pos. 3) et
verrouiller la plaque de recouvrement ainsi que la tubulure d’entrée de
câble avec l’étrier de verrouillage. Puis refermer le couvercle du
compartiment de raccordement avec les trois vis à fentes en croix.
Enclencher le secteur et puis le luminaire.
Le luminaire doit rester mis en circuit pour au moins 14 heures afin que
la batterie soit rechargée.
Effectuer ensuite un test de fonctionnement de la commutation en
éclairage de secours (voir 7. Entretien, test de fonctionnement).
7. Entretien
En ce qui concerne l’entretien, le test et la réparation des
appareils électriques pour atmosphère explosive, les règlements
nationaux y applicables ainsi que les règles de la technique
généralement reconnues devront être respectés (CEI/EN 60079-17
et CEI/EN 60079-19) !
7.1 Entretien
Lors de l’entretien surtout les composants dont lesquels dépend le
mode de protection contre l’explosion, doivent être vérifié, par ex. :
Le boîtier et la vasque de protection présentent-ils des fissures ou des
signes d’avarie ?
Les joints d’étanchéité sont-ils efficaces ?
Les bouchons d’obturation et les bornes sont-ils bien serrés ?
Vu le risque d’une charge électrostatique, le luminaire ne doit être
nettoyé qu’avec un chiffon humide et non fibreux ou qu’avec une
éponge ! Utiliser uniquement un détergent ménager dilué avec de
l’eau comme prescrit! La température de l’eau ne doit pas dépasser
50 °C au maxi. Rincer ensuite à l’eau claire afin d’éviter que n’appa-
raissent des fissures dues à la contreinte exercée sur la vasque de
protection !
Respectez les intervalles de remplacement prescrits par le fabricant
de lampes.
Test de fonctionnement en éclairage de secours
Couper le luminaire du secteur. La lampe de sécurité (douille rouge) doit
s’allumer.
Les durées de test suivantes ne devraient pas
être surpassées lors d’un
test de fonctionnement :
Jeu d’accus pour 1,5 h d’éclairage
de secours : 60 min.
Jeu d’accus pour 3,0 h d’éclairage
de secours : 120 min.
Si la lampe de secours s’éteint en cette période de test, quoique la
batterie soit complètement chargée, il faudra remplacer le jeu d’accus.
Note : La capacité de batterie sera procurable après approxima-
tivement. 3 cycles de charging/discharging de dû au comportement
physique.
8. Réparation / Remise en état
Avant de remplacer ou d’enlever des composants, il faut
observer le suivant : Mettre l’appareil hors tension avant de l’ouvrir
ou de le réparer!
La batterie doit être enlevée.
N’utiliser que des pièces de rechange approuvées d’origine CCH /
EATON! (Voir liste des pièces de rechange CCH / EATON)w
Des réparations ne doivent être exécutées qu’à l’aide de pièces de
rechange d’origine
Cooper Crouse-Hinds / EATON
.
Quand les dommages au module LED seulement un échange
est autorisé. En cas de doute, le affecté module LED doit être
renvoyé à CCH / EATON pour réparation.
Ajouts ou des modifications sur le module LED ne sont pas autorisés.
Des réparations qui portent sur la protection contre l’explosion,
ne devront être exécutées que par CCH / EATON ou par un
électricien qualifié en conformité avec la règlementation nationale
en vigueur (CEI/EN 60079-19).
Luminaires de sécurité pour atmosphères explosives
Série: eLLK(M)(S)92 LED 400A(800A) NE
F
17
9. Évacuation des déchets /Recyclage
Lors de l’évacuation de ce matériel électrique, la règlementation nationale
respective en vigueur devra être respectée.
Pour faciliter la réutilisation des composants individuels, des pièces en
matière plastique sont repérées de la marque distinctive de la matière
plastique employée.
En cas d'élimination, vous pouvez obtenir des informations supplémen-
taires auprès de votre branche Cooper Crouse-Hinds / EATON.
Sous réserve de modification ou de supplément de cette série de
produits.
8.1 Remplacement de module-LED
Module-LED de remplacement peut se faire sans couper l'alimentation
électrique du luminaire, car un interrupteur omnipolaire va isoler les
douilles lors de l'ouverture de la vasque de protection.
Indication : Respecter les normes nationales ou des directives pour
l'utilisation qui peut être divergente par rapport à ça !
Le module-LED doivent être remplacés comme indiqué dans la
Fig.11 et Fig. 12.
Fonctionnement
LED Modul 400/800
normal
LED Modul 400/800
normal / secouru
Achtung! Chemische Beständigkeit beachten.
Nur mit feuchtem Tuch säubern.
Warning! Do not use chemical cleaner.
Clean with a damp cloth only.
Important! Attention à la resistance chimique.
Nettoyer uniquement avec un
chiffon humide.
Batterie
normal
ou
bien
our
bien
VE 12 défaut
VE 12 défaut
secouru
bien
batterie déchargée
Défaut lumiére
Défaut batterie
interrupteur ARRET
LED
rouge,
-
verte
MARCHE
interrupteur MARCHE
LED
rouge,
-
verte CLIGNOTANTE
LED série du module ARRET
LED série du module MARCHE
○ ○
LED
rouge,
-
verte
ARRET
m
a
l
nor
m
Analyse de défaut: eLL. .. NE;
(Test pendant le fonctionnement du luminaire - Les combinaisons de plusieurs défauts ne sont pas enregistrées)
Luminaires de sécurité pour atmosphères explosives
Série: eLLK(M)(S)92 LED 400A(800A) NE
F
Pour en savoir plus sur l'indicateur de fonctionnement et de défaut de EBK 12 voir Mode d'emploi de eBK12 Nr. 3 2211 000 172.
18
Notizen / Notes / Remarques
19
Notizen / Notes / Remarques
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Publication No.
300 8000 1470 D/GB/F (-) /
Auflage / 42.2017 / MS
C
ooper
C
rouse-Hinds
G
mbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2017 Eaton
All Rights Reserved
Printed in Germany
CZ: "Tento návod k pouåití si m åHWH vyåiGDt
ve
svém PDWe
ském MD]yce u p íslušného
]DVWRXSHQt spole
nosti Cooper Crouse-
Hinds/CEAG ve YDãt ]HPL"
'.0RQWDJHYHMOHGQLQJHQNDQRYersættes til
DQGUH(UVSURJoJUHNYLUHUHVKRV'eres
Cooper Crouse-Hinds/CEAG leverDndør"
E: "EQFDVo necesDrio podrá soliciWDUGHVX
representDnte Cooper Crouse-Hinds/CEAG
HVWDV instrucciones de servicio en otro idiomD
GHOD8QLRQ(XURSeD
EST: "SedDNDVXWXVjuhendit omD riiJikeeles
võite NVLGD RPD ULLJLV DsXYDVW DVMDRPDVHVt
Cooper Crouse+LQGVL&($*HVLQGXVHVW
FIN: "TDUYLWWDHVVDWlPlQNlytW|RKMHHQNllQnös
RQVDDWDYLVVDWRLVHOOD(8QNLHOHOOl7HLGlQ
Cooper
Crouse-Hinds/CEAG HGXVWDMDOWDQQH
GR:
Cooper Crouse-
Hinds/CEAG"
+$NH]HOpVL~WPXWDWyWD]DGRWWRUV]iJ
nyHOYpQD&Roper Crouse-HinGV&($*FpJ
helyi képviseletén LJpQyelheti PHJ"
,6HGHVLGHUDWHODtrDGX]LRQHGHOPDQXDOH
RSHUDWLYRLQXQDOWUDOLQJXDdHOOD&RPXQLWj
(XURSHDSRtHWHULFKLHGHUODDOYRVWUR
UDSSUHVHQtDQWH&ooper Crouse-Hinds/CEAG"
LT: Šios QDXGRMLPR instrukcijos, išverstos
J su
JLPt
j NDOb , JDOLWH SDUHLNDODXWL DWVDNLQJRMe
"Cooper Crouse-Hinds/CEA*DWVWRvyb
je VDYo
ãDOyje
/9âRHNVSOXDW
FLMDV instrukciju vDlsts vDlod
YDUDWSLHSUDV t j su YDOVWV DWELOd JDM Cooper
Crouse-Hinds/CEAG p
rst vniec b 
M: JistJ
u jitolbu dDn il-mDQwDO fil-linJwD
QD]]MRQDOL WDJ
KRPPLQJ DQGLUUDppre entDQW
WD&RRper Crouse Hinds/CEA*ISDMML
KRP
NL: "Indien QRRG]DNHOLMN NDQ de YHUWDOLQJ YDn
GH]HJHEUXLNVLQVWUXFWLHLQHHQDQGHUH(UWDDO
worden oSJHYUDDJd bij Uw Cooper Crouse-
+LQGV&($*YHUWHJHnZRRUGLJLQJ
36HIRUQHFHVViULDDtrDGXomRGHVWDV
LQVWUXo}HVGHRSHUDomRSDUDRXtURLGLRPDGD
8QLmR(XURSHLDSoGHVROLFLWDODMXQWRGRVHX
representDnte Cooper Crouse-Hinds/CEAG"
PL: Niniejs]
instrukcj obs XJLw odpowiedniej
wersji j
]ykowej mo nD]Dmywi
w
pU]edstDwicielstwie firmy Cooper-Crouse-
Hinds/CEAG QD dDQy NUDM
6(Q|YHUVlWWQLQJDYGHQQDmRQWDJHRch
skötselinstruktion till DQQDW EU - språk NDQ vid
EHKRYEHVWlOODVIUnQ(U&RRper Crouse-
Hinds/CEAG- representDQW
SK: "Tento niYRGQDREVOXKX9iPYR9DãRP
URGQRPMD]yku poskytQH]DVW~SHQLHVSROR
nosti
Cooper Crouse-Hinds/CEAG vo 9DãHM NUDMLQH
SLO: "NDYRGLOD ]D XSRUDER v 9DãHP MH]LNu
ODKNR ]DKWHYDWH pri pristojnem ]DVWRSQLãWYu
SRGMHWMD&RRSHUCrouse+LQGV&($*Y9DãL
GUåDYL"
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Eaton eLLK 92 LED 400A NE Operating Instructions Manual

Taper
Operating Instructions Manual

dans d''autres langues