Eaton PowerXL DH1 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Effective February 2018
Supersedes September 2016
PowerXL Series VFD
Installation manual
ii POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions, and safety notations in this document are based on manufacturers
experience and judgment and may not cover all contingencies. If further information is required, a sales representative
shouldbe consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate manufacturer selling policies or other contractual agreement between manufacturer and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN
ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF THE
MANUFACTURER. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT
BETWEEN THE PARTIES.
In no event will the manufacturer be responsible to the purchaser or user in contract, in tort (including negligence), strict
liability, orotherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not
limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses
in the use ofexisting power facilities, or claims against the purchaser or user by its customers resulting from the use of the
information, recommendations, and descriptions contained herein. The information contained in this manual is subject to
change withoutnotice.
Cover Photo: Eaton PowerXL Series Drive
iii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Support services
Support services
The goal of Eaton is to ensure your greatest possible
satisfaction with the operation of our products.
We are dedicated to providing fast, friendly, and accurate
assistance. That is why we offer you so many ways to get
the support you need. Whether it is by phone, fax, or email,
you can access Eatons support information 24 hours a day,
seven days a week.
Our wide range of services is listed below.
You should contact your local distributor for product pricing,
availability, ordering, expediting, and repairs.
Website
Use the Eaton Website to find product information.
You can also find information on local distributors or
Eatons sales offices.
Website address
www.eaton.com/drives
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance
with placing an order, stock availability or proof of shipment,
expediting an existing order, emergency shipments, product
price information, returns other than warranty returns, and
information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–6:00 p.m. EST)
After-Hours Emergency: 800-543-7038 (6:00 p.m.–8:00 a.m. EST)
Drives Technical Resource Center
Voice: 877-ETN-CARE (386-2273) option 2, option 6
(8:00 a.m.–5:00 p.m. Central Time U.S. [UTC –6])
email: TRCDriv[email protected]
For customers in Europe, contact
Phone: +49 (0) 228 6 02-3640
Hotline: +49 (0) 180 5 223822
www.eaton.com/moeller/aftersales
iv
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Table of contents
SAFETY
Before commencing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .x
Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .x
Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .x
Motor and equipment safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
CHAPTER 1—POWERXL SERIES OVERVIEW
How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Real time clock battery activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Rating label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Carton labels (U.S. and Europe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Catalog number system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Power ratings and product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DG1 replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
DH1 replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
CHAPTER 2—ENGINEERING CONSIDERATIONS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Electrical power network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Input voltage and frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Input voltage balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Total harmonic distortion (THD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Reactive power compensation devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
CHAPTER 3—PRODUCT OVERVIEW
Component identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Selection criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Maintenance and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Service and warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
CHAPTER 4—SAFETY AND SWITCHING
Fuses and cable cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Cables and fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Residual-current device (RCD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Leakage current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Input contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
EMC Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
CHAPTER 5—MOTOR AND APPLICATION
Motor selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Connecting motors in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Parallel connection of several motors to one frequency inverter . . . . . . . . . . . . . . . .26
Bypass operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Connecting EX motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
CHAPTER 6—INSTALLATION REQUIREMENTS
Electrical installation warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Standard mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Standard drive mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FR6 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
v
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Table of contents, continued
CHAPTER 6—INSTALLATION REQUIREMENTS, continued
Power wiring selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Cable selection: Power and motor leads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Line (Mains) and motor cable installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Connection tightening torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Cable routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Wiring the VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Rubber grommet installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Safe torque off (STO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Connection to power section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Three-phase input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Terminal designations in the power section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Product modified sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Checking the cable and motor insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
CHAPTER 7—EMC INSTALLATION
EMC Measures in the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Screen earth kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Installation requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
International EMC protection cable requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Installation in corner-grounded network and ITsystem . . . . . . . . . . . . . . . . . . . . . . .54
APPENDIX A—TECHNICAL DATA AND SPECIFICATIONS
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
APPENDIX B—INSTALLATION GUIDELINES
Cable and fuse sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Temperature deratings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Heat loss data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Brake resistor sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Efficiency ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
APPENDIX C—DIMENSION DRAWINGS
Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
APPENDIX D—SAFETY INSTRUCTIONS FOR UL AND CUL
UL Standards compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
Field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
APPENDIX E—STO FUNCTION
Description of safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Requirement for installation, commission, maintenance . . . . . . . . . . . . . . . . . . . . .103
Requirements of proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
APPENDIX F—UL CERTIFICATE OF COMPLIANCE
UL certificate of compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
CE declaration of conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
vi
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
List of  gures
Figure 1. RTC battery connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Figure 2. Rating label—DG1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 3. Rating label—DH1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 4. Carton label—DG1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 5. Carton label—DH1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 6. Catalog numbering system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 7. Drive system (PDS = power drive system) . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 8. AC power networks with grounded neutral point (TN-/TT networks) . . . . .16
Figure 10. Block diagram, elements of PowerXL frequency inverters . . . . . . . . . . . .19
Figure 11. Selection criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 12. Identification on the FI circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 13. EMC Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 14. Parallel connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 15. Example of a motor ratings plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 16. Star and delta circuit types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 17. V/Hz characteristic curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 18. Bypass motor control (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Figure 19. Mounting space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Figure 20. Open Drives FR0–FR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Figure 21. FR6 wiring layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Figure 22. Brake resistor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Figure 23. Input power and motor cable stripping lengths . . . . . . . . . . . . . . . . . . . .40
Figure 24. Ground wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Figure 25. Terminal block layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Figure 26. Basic internal control wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Figure 27. PowerXL variable frequency drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Figure 28. Thermistor/STO wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Figure 29. Example of wiring a STO with the internal 24V supply . . . . . . . . . . . . . .48
Figure 30. Example of wiring a STO with the internal 24V supply
to multiple drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Figure 31. Connection to power section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Figure 32. Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Figure 33. Product modified sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Figure 34. EMC-Compliant Setup—230 Vac, 460/480 Vac, 600 Vac . . . . . . . . . . . . .52
Figure 35. Cable description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 36. Location of the EMC Screw in Frame 0 . . . . . . . . . . . . . . . . . . . . . . . . . .54
Figure 37. Locations of the EMC Screw in Frame 1 and Frame 3 . . . . . . . . . . . . . . .54
Figure 38. Locations of EMC and MOV Screws for Frame 2 and Frame 4 . . . . . . . .55
Figure 39. Locations of the EMC Screws in Frame 5 and Frame 6 . . . . . . . . . . . . .55
Figure 40. FR0 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Figure 41. FR1 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Figure 42. FR1 Dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Figure 43. FR2 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Figure 44. FR2 Dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Figure 45. FR3 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Figure 46. FR3 Dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .84
Figure 47. FR4 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Figure 48. FR4 Dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .86
vii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
List of  gures, continued
Figure 49. FR5 Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Figure 50. FR5 Dimension drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Figure 51. FR6 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Figure 52. FR6 Dimensional drawing flange mount . . . . . . . . . . . . . . . . . . . . . . . . . .90
Figure 53. Functional block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 54. Reliability block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 55. STO terminal block in PowerXL control board . . . . . . . . . . . . . . . . . . . . .103
Figure 56. Thermistor STO wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
List of tables
Table 1. Common abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Table 2. Open Type IP20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 3. Type 1/IP21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 4. Type 12/IP54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Table 5. Open Type IP20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Table 6. Type 1/IP21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Table 7. Type 12/IP54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Table 8. Type 1/IP21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Table 9. Type 12/IP54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Table 10. Frame 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Table 11. Frame 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Table 12. Frame 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Table 13. Frame 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Table 14. Frame 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 15. Frame 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Table 16. Frame 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Table 17. Frame 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Table 18. Frame 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Table 19. Frame 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Table 20. Frame 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 21. Frame 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 22. Frame 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 23. Drive system components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Table 24. Elements of PowerXL frequency inverters . . . . . . . . . . . . . . . . . . . . . . . .19
Table 25. Maintenance measures and intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Table 26. Motor power cable EMC guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Table 27. Assignment of frequency inverters to example motor circuit . . . . . . . . . . .27
Table 28. Bypass motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Table 29. Space requirements for mounting the
PowerXL Series VFD and airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Table 30. Mounting drive dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Table 31. Tightening torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Table 32. Spacing between parallel motor cables . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Table 33. Maximum motor power cable length 230/480 V . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 34. Maximum motor power cable lengths 575 V . . . . . . . . . . . . . . . . . . . . . . .39
Table 35. Motor power cable EMC guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Table 36. Input power and motor cable stripping and wire lengths . . . . . . . . . . . . .40
Table 37. I/O connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Table 38. I/O specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
viii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
List of tables, continued
Table 39. 1st Environment 2nd environment EMC levels
according to EN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Table 40. Motor power cable EMC guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Table 41. Cable categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Table 42. PowerXL Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Table 43. North America cable and fuse sizes—208 Vac to 240 Vac ratings . . . . . . .59
Table 44. International cable and fuse sizes—208 Vac to 240 Vac ratings . . . . . . . . .60
Table 45. North America cable and fuse sizes—440 Vac to 500 Vac ratings . . . . . . .61
Table 46. International cable and fuse sizes—380 Vac to 440 Vac ratings . . . . . . . . .62
Table 47. North America cable and fuse sizes—525 Vac to 600 Vac ratings . . . . . . . .63
Table 48. 230 V temperature deratings (VT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Table 49. 230 V temperature deratings (CT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Table 50. 480 V temperature deratings (VT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Table 51. 480 V temperature deratings (CT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Table 52. 600 V temperature deratings (VT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Table 53. 600 V temperature deratings (CT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Table 54. 230 V heat loss data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Table 55. 400 V heat loss data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Table 56. 600 V heat loss data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 57. 230 V idle heat loss FR0~FR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 58. 480 V idle heat loss FR0~FR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 59. 575 V idle heat loss FR1~FR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 60. Brake resistor sizing data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 61. 230 V FR0-Xhp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Table 62. 230 V FR1-4hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Table 63. 230 V FR2-10hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Table 64. 230 V FR3-20hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Table 65. 230 V FR4-40hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Table 66. 230 V FR5-75hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Table 67. 400 V FR0-Xhp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Table 68. 400 V FR1-7.5hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Table 69. 400 V FR2-20hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Table 70. 400 V FR3-40hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Table 71. 400 V FR4-75hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Table 72. 400 V FR5-150hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Table 73. 575 V FR1-7.5hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Table 74. 575 V FR2-20hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Table 75. 575 V FR3-40hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Table 76. 575 V FR4-75hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Table 77. 575 V FR5-150hp efficiency rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Table 78. Protection ratings—480 V drive series . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
Table 79. Protection ratings—230 V drive series . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
Table 80. Protection ratings—575 V drive series . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Table 81. Required line and motor wire torque (480 V) . . . . . . . . . . . . . . . . . . . . . . .95
Table 82. Required line and motor wire torque (230 V) . . . . . . . . . . . . . . . . . . . . . . .96
Table 83. Required line and motor wire torque (575 V) . . . . . . . . . . . . . . . . . . . . . . .97
Table 84. Required grounding wire torque (480 V) . . . . . . . . . . . . . . . . . . . . . . . . . .98
Table 85. Required grounding wire torque (230 V) . . . . . . . . . . . . . . . . . . . . . . . . . .99
Table 86. Required grounding wire torque (575 V) . . . . . . . . . . . . . . . . . . . . . . . . . .10
0
ix
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Safety
WARNING!
DANGEROUS ELECTRICAL VOLTAGE!
Before commencing the installation
Disconnect the power supply of the device
Ensure that devices cannot be accidentally restarted
Verify isolation from the supply
Earth and short circuit the device
Cover or enclose any adjacent live components
Only suitably qualified personnel in accordance with
EN50110-1/-2 (VDE 0105 Part 100) may work on this
device/system
Before installation and before touching the device ensure
that you are free of electrostatic charge
The functional earth (FE, PES) must be connected to
the protective earth (PE) or the potential equalization.
The system installer is responsible for implementing
thisconnection
Connecting cables and signal lines should be installed so
that inductive or capacitive interference does not impair
the automation functions
Install automation devices and related operating elements
in such a way that they are well protected against
unintentional operation
Suitable safety hardware and software measures should
be implemented for the I/O interface so that an open
circuit on the signal side does not result in undefined
states in the automation devices
Ensure a reliable electrical isolation of the extra-low
voltage of the 24 V supply. Only use power supply units
complying with IEC 60364-4-41 (VDE 0100 Part 410) or
HD384.4.41 S2
Deviations of the input voltage from the rated value
must not exceed the tolerance limits given in the
specifications, otherwise this may cause malfunction and
dangerous operation
Emergency stop devices complying with IEC/EN
60204-1 must be effective in all operating modes of the
automation devices. Unlatching the emergency-stop
devices must not cause a restart
Devices that are designed for mounting in housings or
control cabinets must only be operated and controlled
after they have been installed and with the housing
closed. Desktop or portable units must only be operated
and controlled in enclosed housings
Measures should be taken to ensure the proper restart
of programs interrupted after a voltage dip or failure. This
should not cause dangerous operating states even for a
short time. If necessary, emergency-stop devices should
be implemented
Wherever faults in the automation system may cause
injury or material damage, external measures must be
implemented to ensure a safe operating state in the
event of a fault or malfunction (for example, by means of
separate limit switches, mechanical interlocks, and so on)
Depending on their degree of protection, adjustable
frequency drives may contain live bright metal parts,
moving or rotating components, or hot surfaces during
and immediately after operation
Removal of the required covers, improper installation,
or incorrect operation of motor or adjustable frequency
drive may cause the failure of the device and may lead to
serious injury or damage
The applicable national accident prevention and safety
regulations apply to all work carried out on live adjustable
frequency drives
The electrical installation must be carried out in
accordance with the relevant regulations (for example,
with regard to cable cross sections, fuses, PE)
Transport, installation, commissioning, and maintenance
work must be carried out only by qualified personnel
(IEC 60364, HD 384 and national occupational
safetyregulations)
Installations containing adjustable frequency drives must
be provided with additional monitoring and protective
devices in accordance with the applicable safety
regulations. Modifications to the adjustable frequency
drives using the operating software are permitted
All covers and doors must be kept closed
duringoperation
To reduce hazards for people or equipment, the user
must include in the machine design measures that
restrict the consequences of a malfunction or failure of
the drive (increased motor speed or sudden standstill of
motor). These measures include:
Other independent devices for monitoring safety-related
variables (speed, travel, end positions, and so on)
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks)
Never touch live parts or cable connections of
the adjustable frequency drive after it has been
disconnected from the power supply. Due to the charge
in the capacitors, these parts may still be live after
disconnection. Fit appropriate warning signs
x
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Read this manual thoroughly and make sure you
understand the procedures before you attempt to install,
set up,operate or carry out any maintenance work on this
PowerXLAdjustable Frequency Drive.
De nitions and symbols
WARNING
This symbol indicates high voltage. It calls your
attention to items or operations that could be
dangerous to you and other persons operating
this equipment. Read the message and follow the
instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with
either of two signal words: CAUTION or WARNING, as
described below.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION
(aswell as WARNING).
Hazardous high voltage
WARNING
Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing
drives and electronic controllers, there may be exposed
components with housings or protrusions at or above
line potential. Extreme care should be taken to protect
against shock.
Stand on an insulating pad and make it a habit to use
only one hand when checking components
Always work with another person in case an
emergency occurs
Disconnect power before checking controllers or
performing maintenance
Be sure equipment is properly earthed
Wear safety glasses whenever working on electronic
controllers or rotating machinery
WARNING
The components in the drive’s power section remain
energized after the supply voltage has been switched
off. After disconnecting the supply, wait at least five
minutes before removing the cover to allow the
intermediate circuit capacitors to discharge.
Pay attention to hazard warnings!
DANGER
5 MIN
WARNING
Electric shock hazard—risk of injuries! Carry out wiring
work only if the unit is de-energized.
WARNING
Do not perform any modifications on the AC drive when
it is connected to mains.
Warnings and cautions
WARNING
Be sure to ground the unit following the instructions in
this manual. Ungrounded units may cause electric shock
and/or fire.
WARNING
This equipment should only be installed, adjusted, and
serviced by qualified electrical maintenance personnel
familiar with the construction and operation of this
type of equipment and the hazards involved. Failure
to observe this precaution could result in death or
severeinjury.
WARNING
Components within the drive are live when it is
connected to power. Contact with this voltage
is extremely dangerous and may cause death or
severeinjury.
WARNING
Line terminals (L1, L2, L3), motor terminals (U, V, W) and
the DC link/brake resistor terminals (DC–, DC+/R+, R–)
are live when the drive is connected to power, even
if the motor is not running. Contact with this voltage
is extremely dangerous and may cause death or
severeinjury.
xi
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
WARNING
Even though the control I/O-terminals are isolated from
line voltage, the relay outputs and other I/O-terminals
may have dangerous voltage present even when the
drive is disconnected from power. Contact with this
voltage is extremely dangerous and may cause death or
severe injury.
WARNING
This equipment has a large capacitive leakage current
during operation, which can cause enclosure parts to be
above ground potential. Proper grounding, as described
in this manual, is required. Failure to observe this
precaution could result in death or severe injury.
WARNING
Before applying power to this drive, make sure that
the front and cable covers are closed and fastened to
prevent exposure to potential electrical fault conditions.
Failure to observe this precaution could result in death
or severe injury.
WARNING
An upstream disconnect/protective device must be
provided as required by the National Electric Code
®
(NEC
®
). Failure to follow this precaution may result in
death or severe injury.
WARNING
This drive can cause a DC current in the protective
earthing conductor. Where a residual current-operated
protective (RCD) or monitoring (RCM) device is used for
protection in case of direct or indirect contact, only an
RCD or RCM of Type B is allowed on the supply side of
this product.
WARNING
Carry out wiring work only after the drive has been
correctly mounted and secured.
WARNING
Before opening the drive covers:
Disconnect all power to the drive, including external
control power that may be present
Wait a minimum of five minutes after all the lights
on the keypad are off. This allows time for the DC bus
capacitors to discharge
A hazard voltage may still remain in the DC bus
capacitors even if the power has been turned off.
Confirm that the capacitors have fully discharged by
measuring their voltage using a multimeter set to
measure the DC voltage
Failure to follow these precautions may cause death or
severe injury.
WARNING
The opening of the branch-circuit protective device
may be an indication that a fault current has been
interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the
controller should be examined and replaced if damaged.
If burnout of the current element of an overload relay
occurs, the complete overload relay must be replaced.
WARNING
Operation of this equipment requires detailed
installation and operation instructions provided in the
Installation/Operation manual intended for use with
this product. It should be retained with this device
at alltimes. A hard copy of this information may be
ordered from literature fulfillment.
WARNING
Before servicing the drive:
Disconnect all power to the drive, including external
control power that may be present
Place a “DO NOT TURN ON” label on the disconnect
device
Lock the disconnect device in the open position
Failure to follow these instructions will result in death
or serious injury.
WARNING
The drive outputs (U, V, W) must not be connected to
the input voltage or the utility line power as severe
damage to the device may occur and there may be a
risk of fire.
WARNING
The heat sink and/or outer enclosure may reach a
hightemperature.
Pay attention to hazard warnings!
Hot Surface—Risk of Burn. DO NOT TOUCH!
WARNING
In a domestic environment, this product may cause
radio interference, in which case supplementary
mitigation measures may be required.
xii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
CAUTION
Any electrical or mechanical modification to this drive
without prior written consent of manufacturer will void all
warranties and may result in a safety hazard in addition and
voiding of the UL
®
listing.
CAUTION
Install this drive on flame-resistant material such as a steel
plate to reduce the risk of fire.
CAUTION
Install this drive on a perpendicular surface that is able
to support the weight of the drive and is not subject to
vibration, to lessen the risk of the drive falling and being
damaged and/or causing personal injury.
CAUTION
Prevent foreign material such as wire clippings or metal
shavings from entering the drive enclosure, as this may
cause arcing damage and fire.
CAUTION
Install this drive in a well-ventilated room that is not subject
to temperature extremes, high humidity, or condensation,
and avoid locations that are directly exposed to sunlight, or
have high concentrations of dust, corrosive gas, explosive
gas, inflammable gas, grinding fluid mist, etc. Improper
installation may result in a fire hazard.
CAUTION
When selecting the cable cross-section, take the voltage
drop under load conditions into account. The consideration
of other standards is the responsibility of the user.
The user is responsible for compliance with all international
and national electrical standards in force concerning
protective grounding of all equipment.
CAUTION
The specified minimum PE conductor cross-sections in this
manual must be maintained.
Touch current in this equipment exceeds 3.5 mA (AC). The
minimum size of the protective earthing conductor shall
comply with the requirements of EN 61800-5-1 and/or the
local safety regulations.
CAUTION
Touch currents in this frequency inverter are greater than
3.5mA (AC). According to product standard IEC/EN 61800-5-1,
an additional equipment grounding conductor of the same
cross-sectional area as the original protective earthing
conductor must be connected, or the cross-section of the
equipment grounding conductor must be at least 10 mm
2
Cu.
Drive requires that only copper conductor should be used.
CAUTION
Debounced inputs may not be used in the safety circuit
diagram. Residual current circuit breakers (RCD) are only
to be installed between the AC power supply network and
thedrive.
CAUTION
Debounced inputs may not be used in the safety circuit
diagram. If you are connecting multiple motors on one drive,
you must design the contactors for the individual motors
according to utilization category AC-3.
Selecting the motor contactor is done according to the rated
operational current of the motor to be connected.
CAUTION
Debounced inputs may not be used in the safety circuit
diagram. A changeover between the drive and the input
supply must take place in a voltage-free state.
CAUTION
Debounced inputs may not be used in the safety circuit
diagram. Fire hazard!
Only use cables, protective switches, and contactors that
feature the indicated permissible nominal current value.
CAUTION
Before connecting the drive to AC mains make sure that the
EMC protection class settings of the drive are appropriately
made according to instructions in this manual.
If the drive is to be used in a floating distribution network,
remove screws at MOV and EMC. See “Installation in
Corner-Grounded Network” on Page 47 and “Installation
in IT System” on Page 47 respectively
Disconnect the internal EMC filter when installing the
drive on an IT system (an ungrounded power system or a
high-resistance-grounded [over 30 ohm] power system),
otherwise the system will be connected to ground
potential through the EMC filter capacitors. This may
cause danger, or damage the drive
Disconnect the internal EMC filter when installing the
drive on a corner grounded TN system, otherwise the
drive will be damaged
NOTE
When the internal EMC filter is disconnected, the drive
might be not EMC compatible.
Do not attempt to install or remove the MOV or
EMCscrews while power is applied to the drives
inputterminals
xiii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Motor and equipment safety
CAUTION
Do not perform any meggar or voltage withstand tests on
any part of the drive or its components. Improper testing
may result in damage.
CAUTION
Prior to any tests or measurements of the motor or the
motor cable, disconnect the motor cable at the drive output
terminals (U, V, W) to avoid damaging the drive during motor
or cable testing.
CAUTION
Do not touch any components on the circuit boards. Static
voltage discharge may damage the components.
CAUTION
Before starting the motor, check that the motor is mounted
properly and aligned with the driven equipment. Ensure that
starting the motor will not cause personal injury or damage
equipment connected to the motor.
CAUTION
Set the maximum motor speed (frequency) in the drive
according to the requirements of the motor and the
equipment connected to it. Incorrect maximum frequency
settings can cause motor or equipment damage and
personal injury.
CAUTION
Before reversing the motor rotation direction, ensure that
this will not cause personal injury or equipment damage.
CAUTION
Make sure that no power correction capacitors are
connected to the drive output or the motor terminals to
prevent drive malfunction and potential damage.
CAUTION
Make sure that the drive output terminals (U, V, W) are not
connected to the utility line power as severe damage to the
drive may occur.
CAUTION
When the control terminals of two or more drive units are
connected in parallel, the auxiliary voltage for these control
connections must be taken from a single source which can
either be one of the units or an external supply.
CAUTION
The drive will start up automatically after an input voltage
interruption if the external run command is on.
CAUTION
Do not control the motor with the disconnecting device
(disconnecting means); instead, use the control panel start
and stop keys and, or commands via the I/O board of the
drive. The maximum allowed number of charging cycles
of the DC capacitors (i.e. power-ups by applying power) is
fivein ten minutes.
CAUTION
Improper drive operation:
If the drive is not turned on for a long period, the
performance of its electrolytic capacitors will be reduced
If it is stopped for a prolonged period, turn the drive on
at least every six months for at least 5 hours to restore
the performance of the capacitors, and then check
its operation. It is recommended that the drive is not
connected directly to the line voltage. The voltage should
be increased gradually using an adjustable AC source
Failure to follow these instructions can result in injury
and/or equipment damage.
For more technical information, contact the factory or your
local sales representative.
xiv
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Sécurité
AVERTISSEMENT !
TENSION ÉLECTRIQUE DANGEREUSE !
Avant de commencer l’installation
Débrancher l’alimentation de l’appareil
S’assurer que les dispositifs ne peuvent pas être
accidentellement redémarrés
Vérifier l’isolement de l’alimentation
Mettre l’appareil à la terre et le protéger contre les
courts-circuits
Couvrir ou enfermer tout composant sous
tensionadjacent
Seul le personnel qualifié conformément à la norme EN
50110-1/-2 (VDE 0105 Partie 100) peut travailler sur cet
appareil/ce système
Avant l’installation et avant de toucher l’appareil, s’assurer
de ne porter aucune charge électrostatique
La terre fonctionnelle (FE, PSE) doit être raccordée à la
terre de protection (PE) ou la compensation de potentiel.
L’installateur du système a la responsabilité d’assurer
cette connexion
Les câbles de connexion et les lignes de signal doivent
être installés de façon à ce que les interférences
capacitives ou inductives ne compromettent pas les
fonctions d’automatisation
Installer les appareils d’automatisation et les éléments de
fonctionnement associés de manière à ce qu’ils soient
bien protégés contre tout fonctionnement accidentel
Des dispositifs de sécurité matériels et logiciels
appropriés doivent être utilisés en rapport avec l’interface
des E/S afin qu’un circuit ouvert sur le côté signal
ne résulte pas en états indéfinis dans les dispositifs
d’automatisation
Assurer une isolation électrique fiable sur le côté tension
extra basse de l’alimentation 24 V. Utiliser uniquement
des blocs d’alimentation conformes à la norme CEI
60364-4-41 (VDE 0100, partie 410) ou HD384.4.41 S2
Les écarts entre la tension d’entrée et la tension
nominale ne doivent pas dépasser les limites de
tolérance indiquées dans les spécifications, au risque de
provoquer un mauvais fonctionnement et une utilisation
dangereuse du système
Les dispositifs d’arrêt d’urgence conformes à la
norme CEI/EN 60204-1 doivent être efficace dans
tous les modes de fonctionnement des dispositifs
d’automatisation. Le déverrouillage des dispositifs d’arrêt
d’urgence ne doit pas entraîner un redémarrage
Les dispositifs conçus pour un montage dans des boîtiers
ou armoires de commande ne doivent être utilisés et
contrôlés qu’après avoir été installés et avec le boîtier
fermé. Les unités de bureau ou portatives ne doivent être
utilisées et contrôlées que dans leurs boîtiers fermés
Des mesures doivent être prises pour assurer un bon
redémarrage des programmes interrompus après une
chute ou une panne de tension. Ceci ne doit pas causer
des états de fonctionnement dangereux, même pour un
court laps de temps. Si nécessaire, des dispositifs d’arrêt
d’urgence doivent être utilisés
Quand des défaillances du système d’automatisation
peuvent entraîner des blessures ou des dommages
matériels, des mesures externes doivent être appliquées
pour assurer un état de fonctionnement sans danger
en cas de panne ou de mauvais fonctionnement
(par exemple au moyen de disjoncteurs séparés, de
verrouillages mécaniques, etc.)
En fonction de leur degré de protection, les
entraînements à fréquence variable peuvent contenir des
pièces métalliques sous tension, des composants rotatifs
ou en mouvement et des surfaces brûlantes, pendant le
fonctionnement et immédiatement après l’arrêt
Le retrait des protections requises, une installation
incorrecte ou un mauvais fonctionnement du moteur ou
de l’entraînement à fréquence variable peuvent causer la
défaillance de l’appareil et entraîner des blessures graves
et des dommages importants
La réglementation nationale applicable en matière de
sécurité et de prévention des accidents s’applique à tous
les travaux effectués sur les entraînements à fréquence
variable sous tension
L’installation électrique doit être effectuée conformément
aux réglementations applicables (par exemple, en ce
qui concerne les sections transversales des câbles, les
fusibles, la mise à la terre de protection)
Le transport, l’installation, la mise en service et
les travaux de maintenance doivent être effectués
uniquement par un personnel qualifié (IEC 60364, HD 384
et règles de sécurité du travail)
Les installations contenant des entraînements à
fréquence variable doivent être équipées de dispositifs
de surveillance et de protection, conformément aux
réglementations applicables en matière de sécurité. Les
modifications des entraînements à fréquence variable
réalisées à l’aide du logiciel d’exploitation sont autorisées
xv
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Toutes les protections et les portes doivent être
maintenues fermées pendant le fonctionnement
Pour réduire les risques d’accidents et de dommages
matériels, l’utilisateur doit inclure dans la conception de
la machine des mesures limitant les conséquences de
panne ou de mauvais fonctionnement de l’entraînement
(augmentation de la vitesse ou arrêt soudain du moteur).
Ces mesures comprennent:
Autres dispositifs indépendants de surveillance des
variables en rapport avec la sécurité (vitesse, voyages,
positions d’extrémité, etc.)
Mesures électriques ou non électriques appliquées
à l’ensemble du système (verrouillages électriques
oumécaniques)
Ne jamais toucher les pièces sous tension ni les
connexions des câbles de l’entraînement à fréquence
variable après leur déconnexion de l’alimentation.
En raison de la charge dans les condensateurs,
ces pièces peuvent être encore sous tension
après la déconnexion. Installer les panneaux
d’avertissementappropriés.
Lire ce manuel en entier et s’assurer de bien comprendre
les procédures avant de tenter d’installer, de configurer,
d’utiliser et d’effectuer tout travail d’entretien sur cet
entraînement à fréquence variable PowerXL.
Dé nitions et symboles
AVERTISSEMENT
Ce symbole indique une haute tension. Il attire
l’attention sur les éléments ou les opérations qui
pourraient être dangereux pour les personnes utilisant
cet équipement. Lire attentivement le message et suivre
attentivement les instructions.
Ce symbole est le « symbole d’alerte de sécurité ». Il
accompagne les deux termes d’avertissement suivants:
MISE EN GARDE ou AVERTISSEMENT, comme décrit
ci-dessous.
AVERTISSEMENT
Indique une situation potentiellement dangereuse qui, si
elle n’est pas évitée, peut entraîner des blessures graves
ou la mort.
MISE EN GARDE
Indique une situation potentiellement dangereuse qui, si
elle n’est pas évitée, peut entraîner des blessures légères
à modérées et d’importants dégâts matériels. La situation
décrite dans la MISE EN GARDE peut, si elle n’est pas
évitée, entraîner des conséquences graves. Des mesures
de sécurité importantes sont décrites dans les MISES EN
GARDE (ainsi que dans les AVERTISSEMENTS).
Haute tension dangereuse
AVERTISSEMENT
L’équipement de contrôle du moteur et les contrôleurs
électroniques sont branchés sur des tensions secteur
dangereuses. Lors de l’entretien des entraînements
et des contrôleurs électroniques, il peut y avoir
des composants exposés avec des boîtiers ou des
protubérances au niveau du potentiel du réseau ou
au-dessus. Toutes les précautions doivent être prises
pour se protéger contre les chocs électriques.
Se tenir sur un tapis isolant et prendre l’habitude
de n’utiliser qu’une seule main pour vérifier
lescomposants
Toujours travailler avec une autre personne lorsqu’une
situation d’urgence se produit
Débrancher l’alimentation avant de vérifier les
contrôleurs ou d’effectuer des travaux d’entretien
S’assurer que l’équipement est correctement relié à
la terre
Porter des lunettes de sécurité lors des travaux sur les
contrôleurs électroniques ou les machines rotatives
AVERTISSEMENT
Les composants de la section d’alimentation de
l’entraînement restent sous tension après la coupure
de la tension d’alimentation. Après la déconnexion de
l’alimentation, attendre au moins cinq minutes avant
de retirer le couvercle pour permettre la décharge des
condensateurs du circuit intermédiaire.
Prêter attention aux avertissements signalant
desdangers !
DANGER
5 MIN
AVERTISSEMENT
Risque de choc électrique - risque de blessures !
Effectuer le câblage uniquement si l’unité n’est plus
sous tension.
AVERTISSEMENT
Ne pas effectuer de modifications sur l’entraînement CA
lorsqu’il est connecté à l’alimentation secteur.
xvi
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Avertissements et mises en garde
AVERTISSEMENT
S’assurer de mettre l’appareil à la terre en suivant
les instructions de ce manuel. Les unités non mises
à la terre peuvent causer des chocs électriques et
desincendies.
AVERTISSEMENT
Cet équipement ne doit être installé, réglé et entretenu
que par un personnel d’entretien électrique qualifié
connaissant la construction et le fonctionnement de ce
type d’équipement, ainsi que les risques encourus. Le
non-respect de cette précaution peut entraîner la mort
ou des blessures graves.
AVERTISSEMENT
Les composants à l’intérieur de l’entraînement sont
sous tension lorsque l’entraînement est branché
à l’alimentation. Le contact avec cette tension est
extrêmement dangereux et peut causer la mort ou des
blessures graves.
AVERTISSEMENT
Les bornes de phase (L1, L2, L3), les bornes du
moteur (U, V, W) et les bornes de résistance de liaison
CC/frein (DC-, DC+ /R+, R-) sont sous tension lorsque
l’entraînement est branché à l’alimentation, même si le
moteur ne tourne pas. Le contact avec cette tension est
extrêmement dangereux et peut causer la mort ou des
blessures graves.
AVERTISSEMENT
Même si les bornes E/S de commande sont isolées
de la tension secteur, les sorties de relais et les autres
bornes E/S peuvent présenter une tension dangereuse
même lorsque l’entraînement est débranché. Le contact
avec cette tension est extrêmement dangereux et peut
causer la mort ou des blessures graves.
AVERTISSEMENT
Cet équipement a un grand courant de fuite capacitif
pendant le fonctionnement, ce qui peut mettre les
pièces du boîtier à un niveau supérieur au potentiel
de terre. Une mise à la terre appropriée, telle que
décrite dans ce manuel, est nécessaire. Le non-respect
de cette précaution peut entraîner la mort ou des
blessuresgraves.
AVERTISSEMENT
Avant de mettre l’entraînement sous tension,
s’assurer que les protections avant et des câbles sont
fermées et attachées pour empêcher l’exposition à
d’éventuelles défaillances électriques. Le non-respect
de cette précaution peut entraîner la mort ou des
blessuresgraves.
AVERTISSEMENT
Un dispositif de protection/déconnexion en amont
doit être fourni, tel que requis par le code électrique
national (NEC
®
). Le non-respect de cette précaution peut
entraîner la mort ou des blessures graves.
AVERTISSEMENT
Cet entraînement peut causer un courant CC dans le
conducteur de mise à la terre de protection. Lorsqu’un
dispositif de protection ou de surveillance à courant
résiduel est utilisé pour la protection en cas de contact
direct ou indirect, seul un dispositif de type B est
autorisé sur le côté alimentation de ce produit.
AVERTISSEMENT
Ne travailler sur le câblage qu’après que l’entraînement
a été correctement monté et attaché.
AVERTISSEMENT
Avant d’ouvrir les couvercles de l’entraînement :
Débrancher toute l’alimentation allant à
l’entraînement, y compris l’alimentation de
commande externe pouvant être présente
Attendre un minimum de cinq minutes après
l’extinction de tous les voyants du clavier. Cela
permet aux condensateurs de bus CC de se décharger
Une tension dangereuse peut rester dans les
condensateurs de bus CC même si l’alimentation a
été coupée. Confirmer que les condensateurs sont
entièrement déchargés en mesurant la tension à l’aide
d’un multimètre réglé pour mesurer la tension CC
Le non-respect de cette précaution peut entraîner la
mort ou des blessures graves.
AVERTISSEMENT
L’ouverture du dispositif de protection du circuit de
dérivation peut indiquer que le courant de défaut a
été interrompu. Pour réduire le risque d’incendie ou de
choc électrique, les pièces porteuses de courant et les
autres composants du contrôleur doivent être examinés
et remplacés s’ils sont endommagés. Si l’élément de
courant d’un relais de surcharge a grillé, le relais de
surcharge doit être intégralement remplacé.
xvii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
AVERTISSEMENT
Le fonctionnement de cet équipement nécessite
le respect des instructions d’installation et de
fonctionnement détaillées fournies dans le manuel
d’installation/de fonctionnement destiné à être utilisé
avec ce produit. Ce support doit être conservé avec cet
appareil à tout moment.
AVERTISSEMENT
Avant de procéder à l’entretien de l’entraînement :
Débrancher toute l’alimentation allant à
l’entraînement, y compris l’alimentation de
commande externe pouvant être présente
Placer une étiquette « NE PAS UTILISER » sur le
dispositif de déconnexion
Verrouiller le dispositif de déconnexion en
positionouverte
Le non-respect de ces instructions peut entraîner la
mort ou des blessures graves.
AVERTISSEMENT
Les sorties de l’entraînement (U, V, W) ne doivent pas
être connectées à la tension d’entrée ni à l’alimentation
secteur, car ceci pourrait gravement endommager
l’appareil et causer un incendie.
AVERTISSEMENT
Le dissipateur de chaleur et/ou le boîtier externe
peuvent atteindre une température élevée.
Prêter attention aux avertissements signalant
desdangers !
Surface brûlante - Risque de brûlure. NE PAS TOUCHER !
MISE EN GARDE
Toute modification électrique ou mécanique de cet
entraînement sans consentement écrit préalable annule
toutes les garanties, peut entraîner un danger pour la
sécurité et annuler l’homologation UL
®
.
MISE EN GARDE
Installer cet entraînement sur une matière résistante aux
flammes, telle qu’une plaque d’acier, pour réduire les
risques d’incendie.
MISE EN GARDE
Installer cet entraînement sur une surface perpendiculaire
capable de supporter le poids de l’entraînement et non
soumise à des vibrations afin de diminuer les risques de
chute et de dommage de l’entraînement, ainsi que les
risques de blessures.
MISE EN GARDE
Empêcher la pénétration de corps étrangers, tels que
morceaux de fils et copeaux métalliques, dans le boîtier de
l’entraînement, car ceci pourrait provoquer la formation d’un
arc électrique et un incendie.
MISE EN GARDE
Installer cet entraînement dans une pièce bien aérée non
soumise à des températures extrêmes, à une forte humidité
ou à la condensation. Éviter les endroits directement
exposés au soleil ou présentant de fortes concentrations
de poussières, des gaz corrosifs, des gaz explosifs, des
gaz inflammables, ou des vapeurs de liquide de meulage,
etc. Une installation inadéquate peut entraîner un
risqued’incendie.
MISE EN GARDE
Lors de la sélection de la section transversale des câbles,
prendre en compte la chute de tension dans des conditions
de charge. La prise en compte d’autres paramètres relève
de la responsabilité de l’utilisateur.
Il relève de la responsabilité de l’utilisateur de respecter
toutes les normes électriques nationales et internationales
en vigueur concernant la mise à la terre de protection de
l’ensemble de l’équipement.
MISE EN GARDE
Les spécifications minimum relatives aux sections
transversales des conducteurs de terre de protection
indiquées dans ce manuel doivent être respectées.
Le courant de fuite de cet équipement dépasse 3,5mA(CA).
La taille minimum du conducteur de la mise à la terre de
protection doit être conforme aux exigences de la norme
EN61800-5-1 et/ou aux réglementations de sécurité locales.
MISE EN GARDE
Les courants de fuite de ce convertisseur de fréquence
sont supérieures à 3,5 mA (CA). Conformément à la
norme CEI/EN 61800-5-1, un conducteur de mise à la
terre de l’équipement supplémentaire possédant la même
superficie de coupe transversale que le conducteur de
mise à la terre de protection d’origine doit être branché,
ou la section transversale du conducteur de mise à la terre
de l’équipement doit être d’au moins 10 mm
2
Cu. Seul un
conducteur en cuivre doit être utilisé avec cet entraînement.
xviii
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le
schéma du circuit de sécurité. Des disjoncteurs de courant
résiduel (RCD) ne peuvent être installés qu’entre le réseau
de courant alternatif et l’entraînement.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le
schéma du circuit de sécurité. Si plusieurs moteurs sont
connectés à un entraînement, des contacteurs doivent être
conçus pour les moteurs individuels conformément à la
catégorie d’utilisation AC-3.
Sélectionner du contacteur du moteur en fonction du
courant de fonctionnement nominal du moteur à connecter.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le
schéma du circuit de sécurité. Une commutation entre
l’entraînement et l’alimentation d’entrée doit avoir lieu dans
un état sans tension.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le
schéma du circuit de sécurité. Risque d’incendie !
Utiliser uniquement des câbles, des interrupteurs de
protection et des contacteurs indiquant le courant
nominalpermis.
MISE EN GARDE
Avant de connecter l’entraînement à l’alimentation secteur
CA, s’assurer que les réglages de la classe de protection
CEM sont correctement effectués selon les instructions de
ce manuel.
Si l’entraînement doit être utilisé dans un réseau de
distribution flottant, retirer les vis au niveau des VOM
et CEM. Voir « Installation dans un réseau à une phase
connectée à la terre (corner-grounded) » à la Page47
et « Installation dans un réseau IT » à la Page 47
respectivement
Débrancher le filtre CEM interne lors de l’installation de
l’entraînement sur un réseau IT (système d’alimentation
non mis à la terre ou système d’alimentation électrique
mis à la terre haute résistance [plus de 30 ohms]) pour
ne pas que le système soit connecté au potentiel de terre
via les condensateurs du filtre CEM. Ceci peut être une
cause de dangers ou endommager l’entraînement
Débrancher le filtre CEM interne lors de l’installation de
l’entraînement sur un système TN à une phase connectée
à la terre pour ne pas endommager l’entraînement
Remarque: Lorsque le filtre CEM interne est débranché,
l’entraînement peut ne pas être conforme aux
normes de compatibilité électromagnétique.
Ne pas tenter d’installer ou de retirer les vis des VOM
et CEM lorsque l’alimentation est appliquée aux bornes
d’entrée de l’entraînement
Sécurité du moteur et de l’équipement
MISE EN GARDE
N’effectuer aucun test de résistance de tension ou au
mégohmmètre sur toute partie de l’entraînement ou
de ses composants. Un test inadéquat peut entraîner
desdommages.
MISE EN GARDE
Avant tout test ou mesure du moteur ou du câble du
moteur, débrancher le câble du moteur au niveau des
bornes de sortie de l’entraînement (U, V, W) pour éviter
d’endommager ce dernier lors des tests.
MISE EN GARDE
Ne toucher aucun composant sur les cartes de circuit.
Les décharges d’électricité statique peuvent endommager
lescomposants.
MISE EN GARDE
Avant de mettre le moteur en marche, vérifier qu’il est
correctement monté et aligné avec l’équipement entraîné.
S’assurer que le démarrage du moteur ne risque pas de
provoquer des blessures ou d’endommager l’équipement
connecté au moteur.
MISE EN GARDE
Régler la vitesse maximale du moteur (fréquence) dans
l’entraînement conformément aux exigences du moteur
et de l’équipement qui lui est connecté. Des réglages de
fréquence maximum incorrects peuvent endommager le
moteur ou l’équipement et causer des blessures.
MISE EN GARDE
Avant d’inverser le sens de rotation du moteur, veiller à ce
que cela ne risque pas de provoquer des blessures ou des
dommages matériels.
MISE EN GARDE
S’assurer qu’aucun condensateur de correction
de puissance n’est connecté à la sortie de
l’entraînement ou aux bornes du moteur pour éviter
un mauvais fonctionnement de l’entraînement et des
dommagespotentiels.
MISE EN GARDE
S’assurer que les bornes de sortie de l’entraînement
(U,V,W) ne sont pas connectées à l’alimentation secteur, ce
qui pourrait causer de graves dommages à l’entraînement.
xix
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
MISE EN GARDE
Lorsque les bornes de commande de deux ou plusieurs
unités d’entraînement sont raccordées en parallèle, la
tension auxiliaire de ces connexions de commande doit être
fournie par une source unique, qui peut être soit l’une des
unités, soit une alimentation externe.
MISE EN GARDE
L’entraînement démarre automatiquement après une
interruption de la tension d’entrée si la commande de
démarrage externe est active.
MISE EN GARDE
Ne pas commander le moteur avec le dispositif de
déconnexion ; à la place, utiliser les touches de marche et
d’arrêt du tableau de contrôle ou les commandes du tableau
des E/S de l’entraînement. Le nombre de cycles de charge
maximum permis des condensateurs CC (c’est-à-dire les
mises sous tension par application de puissance) est de
cinq en dix minutes.
MISE EN GARDE
Fonctionnement incorrect de l’entraînement :
Si l’entraînement n’est pas mis en marche pendant une
longue période, la performance de ses condensateurs
électrolytiques sera réduite
S’il est arrêté pour une période prolongée, le mettre en
marche au moins tous les six mois pendant au moins 5
heures pour restaurer la performance des condensateurs,
puis vérifier son fonctionnement. Il est recommandé de
ne pas brancher l’entraînement directement sur la tension
secteur. La tension doit être augmentée progressivement
en utilisant une source CA réglable
Le non-respect de ces instructions peut entraîner des
blessures ou des dégâts matériels.
Pour plus d’informations techniques, contacter l’usine ou le
représentant commercial local.
xx
PowerXL Series VFD
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128

Eaton PowerXL DH1 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues