2112 Fenton Logistics Park Blvd.
Fenton, MO 63026 USA
P/N KIL00921498 FORM NO. K1498 ECO6-081-20 R9/20 Page 2 of 4
Luminaires are designed to be installed in Hazardous Locations: Class I, Division 1 & 2, Groups A, B, C and D; Class 1,
Zones 1 & 2, Groups IIB, IIA; Class II, Div. 1 & 2, Groups E, F, G; Class III; IP66 Suitable for Wet Locations; Suitable for
paint spray booths. T-Code T6 40C & 55C CID1; T6 CIID1 40C; T5 CIID1 55C.
IECEx certificate IECEx QPS 19.0005X. ATEX certificate CML 19ATEX1289X
STANDARD VERSION EMERGENCY VERSION
Ex db op is IIB+H2 T6...T5 Gb Ta: -20°C to +40°C, or Ta: -
20°C to +55°C Ex db op is IIB+H2 T6...T5 Gb Ta: -20°C to +40°C, or
Ta: -20°C to +50°C
Ex tb op is IIIC T85°C... T100°C Db -20°C to +40°C, or Ta:
-20°C to +55°C Ex tb op is IIIC T85°C... T100°C Db -20°C to +40°C, or
Ta: -20°C to +50°C
Light Output Rating: 50Watts-100 Watts. (IECEx and ATEX Certifications are for 120-277VAC 50-60 Hz. 1.22A-.95A
input versions only.)
Protection Standards: IECEx: (IEC) 60079-0:2017, Edition 7.0; 60079-1:2014, Edition 7.0;60079-28:2015, Edition
2.0;60079-31:2013, Edition 2.0. ATEX: (EN) 60079-0:2017; 60079-1:2012; 60079-28:2006; 60079-31:2010.
ATEX Declaration: The equipment is declared to meet the provisions of the ATEX directive (2014/34/EU) by reason of the
EC Type Examination and compliance with the Essential Health and Safety Requirements. T. Michalski : Certifications
Manager
Note: Due to the surge protection provided in the fixture to protect the internal electronics and LEDs, a branch
circuit with the LED fixture may false fail a megohmmeter test (sometimes referred to as a megger test). If a
megohmmeter test is required, the LED fixture should be removed from the branch circuit.
Note: Multiple fluorescent or LED fixtures attached to a single Ground Fault Circuit Interrupter (GFCI) may cause
nuisance tripping of the GFCI. Regulatory agencies allow a small amount of leakage current because of the circuitry
required to mitigate possible issues with electromagnetic compatibility (reference UL8750 and EN61347). The
summation of these leakage currents from multiple fixtures may be enough to trip a GFCI.
NOTE- For Class I, Division 1 / Class II, Division 1 / Class I, Zone 1 Hazardous Locations, use rigid conduit
or appropriate cable connectors/ glands rated for Class I, Division 1 Groups BCD
NOTE – Pour les endroits dangereux Classe I, Division 1 / Classe II, Division 1 / Classe I, Zone 1 utiliser des
Conduits rigides.
L1L INSTALLATION INSTRUCTIONS:
A. A channel is incorporated in the housing for 5/16” or M8 hex bolts or nuts. (See Figure 1)
1. 5/16” or M8 hex bolts can be slid into channels for direct mounting; or used to attach brackets which
include L- brackets, Wall Brackets, Ceiling Brackets, Beam Clamps, and Suspension Chains etc…
2. 5/16” hex nuts or M8 hex nuts can be slid into channels and used with eyebolts, threaded rod etc...
B. The End Caps also have provisions for surface or suspension mounting. (See Figure 2)
C. The “Earthquake Safety Chain” can be attached to the housing using an optional eye bolt. (See
Figure 2).
Figure 1 Figure 2 (Top View)
Special Conditions for Safe Use
The Luminaire shall only be installed where there is a low risk of mechanical damage.
In environments with high dust, the dust will cover the lens and increase the temperature of the fixture. In a high dust
environment make sure the fixture is mounted at an angle so that the aluminum housing will block dust from
accumulating on the lens.