Tripp Lite SmartOnline® S3MX 3-Phase UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
Owner’s Manual
SmartOnline
®
S3MX
3-Phase UPS Systems
Models: S3M100KX, S3M100KXD, S3M120KX, S3M120KXD,
S3M160KX, S3M160KXD, S3M200KX, S3M200KXD
Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 3Ø 4-Wire + PE
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved.
2
Table of Contents
1. Introduction 3
2. Important Safety Warnings 4
2.1 UPS Location Warnings 4
2.2 Equipment Connection Warnings 4
2.3 Battery Warnings 4
2.4 Transportation and Storage 5
2.5 Preparation 5
2.6 Installation 5
2.7 Connection Warnings 5
2.8 Operation 6
2.9 Standards 6
3. Installation and Setup 7
3.1. Unpacking and Inspection 7
3.2. Open Front Panel View 9
3.2.1 Interface and Communication 10
3.2.2 Power Stage/Module 10
3.3 Rear Panel View 11
3.4 Wiring Terminal Views 12
3.5 Single UPS Installation 13
3.6 UPS Installation for Parallel Systems 15
3.6.1 Input and Output Wiring 15
3.6.2 Parallel Board Setting 17
3.6.3 Parallel Function Setting 19
3.6.4 Parallel Cable Connection 19
3.6.5 Parallel System Turn On Procedure 20
3.7 Dual AC Input Installation 20
4. Control Panel and LCD Operation 21
4.1 Control Panel Description 21
4.2 LCD Screen Description 22
4.2.1 Initial Screen 22
4.2.2 Main Screen 22
4.2.3 Control Screen 23
4.2.4 Measurement Screen 24
4.2.5 Setup Screen 26
4.2.6 Information Screen 37
4.2.7 Event Screen 38
4.3 Alarm List 40
4.4 History Record 41
5. Interface and Communication 42
5.1 X1 – Temperature Detection Port for 42
External Battery Pack
5.2 X2 – Remote EPO Input Port 43
5.3 Other Communication Interfaces 43
6. Operation Principles 44
6.1 UPS Block Diagram 44
6.2 Operation Modes 45
6.2.1 Standby Mode 45
6.2.2 Line Mode 46
6.2.3 Battery Mode 47
6.2.4 Frequency Conversion Mode 48
6.2.5 Bypass Mode 49
6.2.6 ECO Mode 50
6.2.7 Shutdown Mode 51
6.2.8 Maintenance Bypass Mode 52
7. UPS Operation 53
7.1 AC Startup 53
7.2 Cold Start Startup 55
7.3 Maintenance Bypass Operation 57
7.3.1 Transfer Critical Load from Line Mode to 57
Maintenance Bypass
7.3.2 Transfer Critical Load from 59
Maintenance Bypass to Line Mode
7.4 Turn Off Operation 61
7.4.1 Turn Off Operation in Line Mode 61
7.4.2 Turn Off Operation in Battery Mode 62
8. Troubleshooting 64
9. Storage and Service 66
9.1 Storage 66
9.2 Service 66
9.3 Batteries 66
9.4 Fans 66
10. Specifications 67
Warranty 70
Español 71
Français 142
Русский 212
Deutsch 283
3
1. Introduction
Tripp Lite’s SmartOnline S3MX-Series Uninterruptible Power Supply (UPS) is a Voltage and Frequency Independent (VFI) true on-line,
double-conversion 3-phase UPS system. This UPS continuously conditions the incoming electrical power supply, eliminating power
disturbances that will otherwise damage sensitive electronic devices and minimising system downtime from power fluctuations and
interruptions.
S3MX-Series UPS systems are designed to the highest quality and performance standards and offer the following features:
Model Agency Number Capacity
S3M100KX, S3M100KXD* AG-6100 100kVA
S3M120KX, S3M120KXD* AG-6120 120kVA
S3M160KX, S3M160KXD* AG-6160 160kVA
S3M200KX, S3M200KXD* AG-6200 200kVA
* “KXD” models are dual-AC input capable.
True on-line UPS – the highest level of UPS protection, fully regulates the incoming power with zero transfer time to battery in the event
of an extended mains failure, so critical loads remain continuously supported
Paralleling for redundancy and capacity for up to two UPS systems
High-efficiency performance in AC On-line and Battery Standby Modes to minimise energy consumption
Market-leading small size and footprint
ECO Mode allows the UPS to operate on bypass in stable utility conditions and immediately transfers to inverter to support the load
when the utility input drops below tolerance
High output power factor – more actual power allows more equipment to be supported
Automatic and manual bypass increase system reliability and allow for maintenance without removing power from the attached load
Wide input voltage window – the UPS system regulates even poor-quality incoming power without reverting to battery, maximising system
uptime and protecting battery life
Matching external battery cabinets allow for increased battery autonomy
Emergency shutdown via REPO
SNMP Network Monitoring and volt-free contact options provide optimum configurability
Optional dual-AC input “KXD” models available
SmartOnline S3MX-Series UPS systems are ideally suited for protecting 4-wire loads in the following mission-critical electrical applications:
IT infrastructure and data centres
• Telecommunications
Networks (LAN/WAN)
Corporate infrastructure
Security and emergency systems
Financial institutions
Healthcare and hospitals
4
2. Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation and maintenance
of all Tripp Lite SmartOnline S3MX 3-Phase 100kVA, 120kVA, 160kVA and 200kVA UPS Systems and their batteries.
Failure to heed these warnings may affect your warranty.
2.1 UPS Location Warnings
Install the UPS indoors, away from heat, direct sunlight, dust, and excess moisture or other conductive contaminants.
Install the UPS in a structurally sound area. The UPS is extremely heavy; take care when moving and lifting the unit.
Only operate the UPS at indoor temperatures between 0° C and 40° C.
Optimum UPS performance and maximum battery life is obtained when the operating temperature is maintained between 17° C and 25° C.
Ensure the installation area has sufficient space for maintenance and ventilation of the UPS system. Maintain a minimum clearance of
50 cm from the front and rear of the UPS for maintenance and ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
2.2 Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended.
The UPS system contains its own energy source (battery). The output terminals may be live, even when the UPS is not connected to an
AC supply.
The UPS models covered in this manual are not compatible with loads that do not have a Neutral Reference or Delta load.
2.3 Battery Warnings
This UPS contains LETHAL VOLTAGES. The UPS is designed to supply power, even when disconnected from utility power. Only
AUTHORISED SERVICE PERSONNEL should access the interior of the UPS after disconnecting utility and DC power.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be
performed by only qualified service personnel observing proper precautions. Turn off the UPS before connecting or disconnecting internal
batteries. Use tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.
The batteries are recyclable. Refer to local codes for disposal requirements or visit tripplite.com/support/recycling-program for recycling
information.
Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings. Escaping electrolytes may be toxic and
cause injury to skin and eyes.
Do not disconnect the batteries while the UPS is in Battery Mode.
Disconnect the charging source prior to connecting or disconnecting terminals.
The following precautions should be observed:
1) Remove watches, rings and other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries or battery cabinets.
5) Determine whether the battery supply (+, -, N) is inadvertently grounded. If it is, remove the source of the ground. Contact with any
part of a grounded battery can result in electric shock. The likelihood of an electric shock is reduced if such grounds are removed
during installation and maintenance.
Battery replacement should be performed only by authorised service personnel, using the same number and type of batteries
(sealed lead acid).
WARNING: In order to avoid any hazardous conditions during UPS installation and maintenance, these tasks may be
performed only by qualified and experienced electricians.
Please read this Owner’s Manual and safety instructions carefully before installing or using the unit.
5
2.4 Transportation and Storage
To protect against shock and impact, transport the UPS system using only its original packaging.
The UPS must be stored in a room that is dry and ventilated.
2.5 Preparation
Condensation may occur if the UPS system is moved directly from a cold to warm environment. The UPS system must be completely
dry before being installed. Please allow at least two hours for the UPS system to adjust to the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system in direct sunlight or near heat sources.
Do not block the ventilation holes on the UPS system’s housing.
2.6 Installation
Do not connect appliances or devices that could overload the UPS (i.e., equipment with large electrical motors) to the UPS output
sockets or terminal.
Carefully arrange cables so no one can step on or trip over them.
Do not block the UPS system’s air vents. The UPS must be installed in a location with good ventilation. Ensure adequate ventilation
space on each side of the unit.
The UPS contains an earthed terminal. In the final installed system configuration, ensure equipotential earth grounding to the external
UPS battery cabinet by connecting the earth terminals of both cabinets together.
The UPS should only be installed by qualified service personnel.
An appropriate disconnect device such as short-circuit backup protection must be provided in the building wiring installation.
An integral single-emergency switching device should be included in the building wiring installation.
Connect the earth ground before connecting to the building wiring terminal.
Installation and wiring must be performed in accordance with local electrical codes and regulations.
2.7 Connection Warnings
The UPS system does not contain standard backfeed protection inside. Isolate the UPS before working on this circuit. The isolation
device must be able to carry the UPS input current.
This UPS should be connected with TN earthing system.
The power supply for this unit must be 3-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
• The input power to 3-phase UPS models require a 3-pole breaker.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended.
Connect the UPS power module’s grounding terminal to a grounding electrode conductor.
The UPS is connected to a DC energy source (battery). The output terminals may still be live, even when the UPS is not connected to an
AC supply.
2. Important Safety Warnings
Input
UPS
«Automatic backfeed protection
system» input, external to the UPS
(EN-IEC 62040-1)
6
2. Important Safety Warnings
When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit.
Be sure to place a warning label on all primary power isolators installed remotely from the UPS area and on any external access points
between such isolators and the UPS. The warning label shall carry the following wording or equivalent.
Before working on this circuit
- Isolate Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals
including the protective earth.
Risk of Voltage Backfeed
2.8 Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals at any time, as this will cancel the protective
earth of the UPS system.
In order to fully disconnect the UPS system, first press the “OFF” button, then disconnect the mains.
Ensure no liquid or other foreign objects can enter into the UPS system.
2.9 Standards
*Safety
IEC 62040-1: 2008+A1:2013
*EMI
Conducted Emission ..................................... EN 62040-2: 2006 Category C3
Radiated Emission ....................................... EN 62040-2: 2006 Category C3
*EMS
ESD............................................................ EN 61000-4-2 Level 4
RS ............................................................. EN 61000-4-3 Level 3
EFT ............................................................ EN 61000-4-4 Level 4
SURGE ....................................................... EN 61000-4-5 Level 4
CS ............................................................. EN 61000-4-6 Level 3
Power-Frequency Magnetic Field .................... EN 61000-4-8 Level 4
Low-Frequency Signals ................................. EN 61000-2-2
Warning: This is a product for commercial applications. Installation restrictions or additional precautions may be needed to
prevent disturbances.
7
3. Installation and Setup
3.1 Unpacking and Inspection
Unpack the unit and inspect its contents. Packaging may include additional accessories and components, depending on specific customer
orders.
One (1) UPS
One (1) Owner’s Manual
One (1) RS-232 Cable
One (1) paralleling cable for every set of UPS units being paralleled: P100200KIT
Other Accessory or Component Options Available Upon Request
One (1) Battery Charger Temperature Compensation Thermostat: TEMPC100200
Note: Do not turn on the unit. Make sure to inspect the unit prior to installation. Ensure nothing inside the package was damaged during transportation.
Notify the carrier and dealer immediately if there is any damage or missing parts. Please keep the original packaging in a safe place for future use.
1. Use a forklift to move the product to the installed area. Make sure the bearing capacity of forklift is sufficient. Refer to Figure 3.1.
2. Follow the unpacking order in Figure 3.2 to remove carton (
1
,
2
) and foams (
3
).
3. Remove two fixing plates located on the two sides of the unit (
1
,
2
and
3
) in Figure 3.3. Loosen leveling feet (
4
) by rotating them
counterclockwise. Once loosened, move the cabinet from the pallet.
4. To fix the cabinet into position, simply rotate leveling feet clockwise. Refer to Figure 3.4.
S3M100KX, S3M100KXD and S3M120KX, S3M120KXD Models
Figure 3.1A
Figure 3.4A Figure 3.5A
Figure 3.2A Figure 3.3A
1125 mm
1175 mm
705 mm
1
2
3
4
4
3
1
2
3
8
3. Installation and Setup
S3M160KX, S3M160KXD, and S3M200KX, S3M200KXD Models
Figure 3.1B
Figure 3.4B Figure 3.5B
Figure 3.2B Figure 3.3B
1125 mm
1610 mm
705 mm
1
2
3
4
4
3
1
2
3
9
3. Installation and Setup
Remove the accessory package and inspect the package contents. The standard
shipping package should contain an Owner’s Manual and RS-232 cable. The key to
the UPS is attached to the front door with a cable tie. Packaging may also include
additional accessories and components, depending on specific customer orders.
Note: Before installing, please inspect the unit. Ensure there is no physical damage to
the unit. Do not turn on the unit. Notify the carrier and dealer immediately if there is any
damage or missing parts and accessories. Keep the original packaging for future use. It is
recommended you keep each equipment and battery set in their original packaging, as it is
designed to provide maximum protection during transportation and storage.
3.2 Open Front Panel View
Each UPS comes equipped with a front door key. The key can be found attached to the front door with a cable tie. Upon opening the
front door, you will see the communication area and several power stages/modules inside. From each power stage/module you can easily
identify its ID.
Table 3.1 Power Stage ID
Power Rating 100K 120K 160K 200K
Stage ID—Individual Unit
Operation
Stage ID—For Parallel
UPS
Owner’s Manual
RS-232 Cable
P100200KIT Paralleling Cable
10
3. Installation and Setup
3.2.1 Interface and Communication
These UPS systems come equipped with various communication devices. Please refer to section 5. Interface and Communication for
further details.
1
Dry Contact Port X1 (Optional battery temperature
compensation thermostat)
2
Dry Contact Port X2 (EPO)
3
SNMP Slot (Optional WEBCARDLX or RELAYCARDSV card)
4
RS-232 Port
5
USB Port
3.2.2 Power Stage/Module
Each power stage/module includes a power factor correction rectifier, a battery charger, an inverter and control circuit.
No. Item Description
1
Fan
Air enters the power stage through the front grills and is exhausted through the rear of the module. Do not
block the ventilation vent.
2
Stage Address DIP
Switches
There are three DIP switches for Power Stage address setting. In the same cabinet, each Power Stage ID
MUST be exclusive. Refer to Table 3.1 Power Stage ID for more information.
3
Battery Start Button When AC input is not available, use this button to start UPS battery power.
4
FAULT LED
ON The power stage is in fault condition.
ON/OFF 0.5 sec The power stage IDs are in conflict.
5
RUN LED
ON The power stage normally works as a secondary stage.
ON/OFF 0.5 sec The power stage normally works as a primary stage.
ON/OFF 0.15 sec The CAN Bus communication does not work.
11
3. Installation and Setup
3.3 Rear Panel View
Several breakers are located on the rear panel of the UPS. Models with a second AC input (Q2) are also available. The breakers shown are
Q1 input 1, Q2 input 2*, Q3 output and Q4 maintenance bypass.
Q 3
Ma inte nance By pas s
Q 1
In put 1
Q 4
O utpu t
Q 2
In put 2
Q 2
In put 2
160KVA /200KVA100KVA /120KVA
*Second AC circuit breaker (Q2) only applicable on second AC-input models with “KXD” suffix.
Q3
Output
100KVA / 120KVA 160KVA / 200KVA
Q4
Maintenance
Bypass
Q4
Maintenance
Bypass
Q1
Input 1
Q1
Input 1
Q2
Input 2*
Q2
Input 2*
Q3
Output
12
3. Installation and Setup
3.4 Wiring Terminal Views
*
*
Q4
Q3
Mai ntena nce Byp ass
Q1
Inp ut 1Out put
Q2
Inp ut 2
2
Q2
Inp ut 2
2
1
4
3
2
3
3
4
2
1
5
5
No. Item Function Description
1
Output Block Connects to the critical loads Includes R, S, T and Neutral terminals.
2
Main Input Block Connects to main AC source Includes R, S, T and Neutral terminals.
3
Ground Connection For UPS grounding Includes one grounding terminal.
4
Battery Input Block Connects to an external battery cabinet
Includes:
Positive (+), Negative (-) and Neutral (N) terminals.
5
*
Second Input Block Connect to second AC source Includes R, S, T and Neutral terminals.
*Second AC input block only applicable on second AC-input models with “KXD” suffix.
100KVA / 120KVA 160KVA / 200KVA
13
N
+
-
N
+
-
Q4
Q3
Main tenan ce Bypa ss
Q1
Inpu t 1Outp ut
Q2
Inpu t 2
2
Q2
Inpu t 2
2
3. Installation and Setup
3.5 Single UPS Installation
Installation and wiring must conform with the local electric laws/regulations. The following procedures must be performed by a professional
electrician:
1) Make sure the mains wire and breakers in the building provide adequate power for the rated UPS capacity so as to avoid electrical
shock or fire hazards.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS system’s maximum input current.
Otherwise, the receptacle may be shorted and destroyed.
2) Switch off the mains in the building before installation.
3) Turn off all connected devices before connecting to the UPS.
4) Prepare the power cables according to Table 3.2. Refer to Table 3.3 for UPS Input Breaker sizes and Table 3.4 for Battery Cabinet
Batteries and Breaker sizes.
Warning:
• Before connecting any wires, make sure the AC input and battery power are completely shut off.
Table 3.2 Power Cables
Model
Power cable (mm
2
and AWG)
Input(Ph) Output(Ph) Neutral Battery Ground
100KVA
70 mm
2
(2/0 AWG)
70 mm
2
(2/0 AWG)
70 mm
2
(2/0 AWG)
150 mm
2
(300 MCM)
70 mm
2
(2/0 AWG)
120KVA
95 mm
2
(3/0 AWG)
95 mm
2
(3/0 AWG)
95 mm
2
(3/0 AWG)
240 mm
2
(500 MCM)
95 mm
2
(3/0 AWG)
160KVA
150 mm
2
(300 MCM)
150 mm
2
(300 MCM)
150 mm
2
(300 MCM)
120 mm
2
x 2
(4/0 AWG x 2)
150 mm
2
(300 MCM)
200KVA
185 mm
2
(400 MCM)
185 mm
2
(400 MCM)
185 mm
2
(400 MCM)
185 mm
2
x 2
(400 MCM x 2)
185 mm
2
(400 MCM)
100kVA / 120KVA
+BATTERY -BATTERY
External
Battery
Input/Output
Breaker
160KVA / 200KVA
14
3. Installation and Setup
Table 3.3 UPS Input Breakers
Model (Series Number) Breaker Size
S3M100KX, S3M100KXD (AG-6100) 200A, 3-Pole
S3M120KX, S3M120KXD (AG-6120) 250A, 3-Pole
S3M160KX, S3M160KXD (AG-6160) 400A, 3-Pole
S3M200KX, S3M200KXD (AG-6200) 400A, 3-Pole
Table 3.4 Battery Cabinet Batteries and Breakers
Model Batteries Included Battery Size and Qty. Breaker Size
BP480V100
Yes
100Ah x 40 400A, 3-Pole
BP480V65 65Ah x 40 300A, 3-Pole
BP480V40 40Ah x 40 200A, 3-Pole
BP480V100-NIB
No
(Designed For) 100Ah x 40 400A, 3-Pole
BP480V65-NIB (Designed For) 65Ah x 40 300A, 3-Pole
BP480V40-NIB (Designed For) 40Ah x 40 200A, 3-Pole
Warning:
Before connecting any wires, make sure the AC input and battery power are completely shut off.
Make sure the breakers, input1 breaker (Q1), input2 breaker (input2, Q2 on dual input models only), output breaker
(Q3 @120K/160K/200K) maintenance breaker (Q4 @ 120K/160K/200K) and battery breaker are all in the “OFF
position. For further reference, review the UPS rear panel images in section 3.3.
Make sure the maintenance bypass switch is in “UPS” position (@ 100K).
5) Remove the terminal block cover on the rear panel of the UPS. Connect the input1, (input2 @ dual input UPS models), output
and battery wires according to the function indicated on terminal block. Make sure to connect the grounding/earth wires first when
establishing a wire connection. Disconnect the grounding/earth wire last when performing wire disconnection.
Notes:
Ensure the wires are tightly and securely connected to the terminals.
This breaker must have leakage current protective function.
Be sure to also add an equipotential bonding wire between the UPS and the External Battery Cabinets.
6) Reattach the terminal block cover to the rear panel of the UPS.
Warning:
Make sure a DC breaker or other protection device is installed between the UPS and external battery pack.
Switch off the battery breaker before installation.
Note: Set the battery pack breaker to the “OFF” position before installing the battery pack.
Pay special attention to the rated battery voltage marked on the label. If you want to change the numbers of the
battery pack, make sure to modify the setting accordingly. The connection with the wrong battery voltage may
cause permanent damage to the UPS.
Make sure the protective grounding/earth wiring is correct. The current spec, colour, position, connection and
conductance reliability of the wires must be checked carefully.
Make sure the utility input and output wiring is correct. The current spec, colour, position, connection and
conductance reliability of the wires must be checked carefully. Make sure the L/N is correct, not reversed or
short-circuited.
15
3. Installation and Setup
3.6 UPS Installation for Parallel Systems
Warning:
The input harmonic current distortion will be between 3% and 4.5% in parallel UPS operations.
One parallel kit is needed for every two UPS systems.
3.6.1 Input and Output Wiring
1. When installing the parallel system, the length of input wires (R, S, T, N) in one UPS must be equal to the input wires of the other UPS.
Likewise, the length of output wires (R, S, T, N) must also be in equal length. If not, it will cause unbalanced current on the output load.
Figure 3.6 Single Input Wiring In Parallel System
Maintenance
Breaker
Output
Breaker
Input
Breaker
AC I/P 1
Parallel Cable
Load
Input 2 Input 1
Output
Static Switch
UPS Module
Bat Module
Bat Module
UPS Module
RECT Inv
Charger
Charger
Maintenance
Breaker
Static Switch
Output
Breaker
Input
Breaker
Input 2 Input 1
Output
UPS Module
Bat Module
Bat Module
UPS Module
RECT Inv
Charger
Charger
16
3. Installation and Setup
Figure 3.7 For Dual Input Models Wiring models In Parallel System
Maintenance
Breaker
Output
Breaker
Input
Breaker
Input
Breaker
AC I/P 1
AC I/P 2
Parallel Cable
Load
Input 2 Input 1
Output
Static Switch
UPS Module
Bat Module
Bat Module
UPS Module
RECT Inv
Charger
Charger
Maintenance
Breaker
Static Switch
Output
Breaker
Input
Breaker
Input
Breaker
Input 2 Input 1
Output
UPS Module
Bat Module
Bat Module
UPS Module
RECT Inv
Charger
Charger
17
3. Installation and Setup
3.6.2 Parallel Board Setting
3.6.2.1 Configure Parallel Board of UPS 1
1. Set SW2 on the parallel board of the UPS 1 to the right side.
Q2
Inp ut 2
2
C 10
N
C 9
N
C 7
N
C 8
N
Figure 3.8 SW2 Position on UPS 1 (Default Setting)
18
3. Installation and Setup
3.6.2.2 Configure Parallel Board of UPS 2
1. Set SW2 on the parallel board of the UPS 2 to the left side.
Figure 3.9 SW2 Position on UPS 2
19
3. Installation and Setup
3.6.3 Parallel Function Setting
1. For input and output wiring, make sure to follow the instructions in section 3.6.1.
2. For the parallel board setting, make sure to follow the instructions in section 3.6.2.
Confirm no power is applied to either UPS at this time.
Once the two steps above and the battery configuration have been completed correctly, proceed with the following steps:
1. Do not connect Parallel Cable until informed.
2. Set the input breakers (Q1) of two UPS systems to the “ON” position. Make sure to keep the output breakers (Q3) of two UPS systems
set to the “OFF” position.
3. Turn on the battery breaker.
4. Turn on the external AC source breaker to apply the AC input source to both UPS systems.
5. Wait for the the power-cycles to complete. Proceed to set UPS 1.
6. Use the LCD panel on UPS 1 to set up the parallel function. Enter the “PARALLEL” menu in the “SETUP” page (refer to section 4.2.5.5
Setup-Parallel Screen for more information).
7. Enable “UPS Parallel” function of UPS 1 (ignore the “Parallel UPS Cable Loose” warning).
8. Choose the battery configuration as “independent” or “common” battery, depending on your preference.
9. To save your settings, select the “Save Setting” icon in the “General” screen of the “SETUP” page.
10. Proceed to set up UPS 2.
11. Set up the parallel function through the LCD panel on UPS 2. Enter the “PARALLEL” menu in the “SETUP” page (refer to section
4.2.5.5 Setup-Parallel Screen for more information).
12. Enable the “UPS Parallel” function of UPS 2 (ignore the “Parallel UPS Cable Loose” warning).
13. Choose the battery configuration as “independent” or “common” battery, depending on your preference.
14. To save your settings, select the “Save Setting” icon in the “General” screen of the “SETUP” page.
15. Turn off the external AC source breaker and wait for complete shutdown of both UPS systems.
16. Turn off the battery breakers.
3.6.4 Parallel Cable Connection
There are three connectors at the end of each parallel cable: one 16-pin connector and two 2-pin connectors.
Notes:
For 100K and 120K UPS with One Parallel Board: Connect the 16-pin connector and the short 2-pin connector.
For 160K and 200K UPS with Two Parallel Boards: Connect the 16-pin connector and the short 2-pin connector to the bottom board. Then, connect the
long 2-pin connector to the top board.
If the 2-pin connector is disconnected by accident, the UPS will prompt a fault: “Warning! Parallel UPS Cable Loose”. Insert the 16-pin connector into
CN7 and the 2-pin connector into CN10 of the Parallel Board of UPS 1. Connect the other end of the parallel cable into the Parallel Board of UPS 2,
again connecting the 16-pin connector into CN7 and the 2-pin connector into CN10.
Figure 3.10 UPS 1 Parallel Board Figure 3.11 UPS 2 Parallel Board
16-Pin
Long 2-Pin
Short 2-Pin
20
3. Installation and Setup
Warning:
Improper parallel cable connections will result in abnormal operations. Verify each step while connecting the parallel
cables on each UPS.
Confirm no power is applied to either UPS at this time.
3.6.5 Parallel System Turn On Procedure
1. Make sure to follow sections 3.6.1 to 3.6.4 correctly.
2. Confirm the input breaker and output breakers of each UPS have been turned “ON”.
3. Turn ON the battery breaker.
4. Turn ON the external AC source breaker to apply AC input source to both UPS systems.
5. Watch for abnormal event messages on the LCD display (refer to section 4.2.7 Event Screen for more information).
6. Switch ON the UPS by pressing the power button on the UPS front panel or through the control page on the LCD panel (refer to section
4.2.3 Control Screen for more information).
3.7 Dual AC Input Installation
Dual AC Input UPS (or suffix “KXD”) models are defaulted to a Single AC Input configuration via the placement of three shorting jumpers
between AC Input 1 and AC Input 2. If you desire to operate the “KXD” models in a dual AC configuration, remove these three jumpers,
and wire AC input 1 and AC Input 2 accordingly.
Jumpers on “KXD” dual-AC input models.
100KVA / 120KVA 160KVA / 200KVA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356

Tripp Lite SmartOnline® S3MX 3-Phase UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire