Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual

Ce manuel convient également à

Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
Explosion-protected control units
GHG 411 and GHG 412
Boites de commande GHG 411 et GHG 412
pour atmosphères explosives
Betriebsanleitung
Operating instructions
Mode d’emploi
22
GHG 410 7001 P0001 D/E/F (r)
CROUSE-HINDS
SERIES
2
Explosionsgeschützte
Steuergeräte
GHG 411 und GHG 412
Explosion-protected
control units
GHG 411 and GHG 412
Boites de commande
GHG 411 et GHG 412 pour
atmosphères explosives
1 Technische Angaben ................................ 3
1.1 Komplette Steuergeräte ........................... 3
1.2 Drucktaster-, Schalter- und
Potentiometersockel allgemein ............... 3
1.2.1 Drucktastersockel 2 polig für
Drucktaster, Schlagtaster, Schalter
und Schlüsseltaster .................................. 4
1.2.2 Drucktastersockel 4 polig für
Drucktaster, Schlagtaster, Schalter
und Schlüsseltaster .................................. 4
1.2.3 Potentiometer .......................................... 4
1.3 Signallampe.............................................. 4
1.4 Messinstrument AM45 / AM72 ............... 5
Messinstrument VM45 / VM72 ............... 5
1.5 Klemmenblock ......................................... 5
1.6 Eigensichere Stromkreise ........................ 5
2 Sicherheitshinweise ................................. 6
3 Normenkonformität .................................. 6
4 Verwendungsbereich ............................... 6
5 Verwendung / Eigenschaften ................... 6
6 Installation ................................................ 7
6.1 Montage / Demontage ............................. 7
6.2 Öffnen des Gerätes/ ..................................
Elektrischer Anschluss ............................. 7
6.3 Kabel- und Leitungseinführungen (KLE);
Verschlussstopfen .................................... 8
6.4 Flansche und Metallplatten *................... 8
6.5 Schließen des Gerätes /
Deckelverschluss ..................................... 8
6.6 Inbetriebnahme ........................................ 9
7 Instandhaltung / Wartung ......................... 9
8 Reparatur / Instandsetzung /
Änderung ................................................. 9
9 Entsorgung /...............................................
Wiederverwertung ................................... 9
Inhalt:
Contents: Contenu:
1 Technical data..........................................10
1.1 Control unit assemblies ..........................10
1.2 Actuator general ......................................10
1.2.1 Actuator 2 pole for push button,
Mushroom head p.b., switch and
Key-operated pushbutton ........................11
1.2.2 Actuator 4 pole for push button,
Mushroom head p.b., switch and
Key-operated pushbutton ........................11
1.2.3 Potentiometer .........................................11
1.3 Signallamp...............................................11
1.4 AM45 / AM72 measuring Instrument
VM45 / VM72 measuring instrument..... 12
1.5 Terminal block ........................................ 12
1.6 Intrinsically safe circuits: ........................ 12
2 Safety instructions ................................. 13
3 Conformity with standards .................... 13
4 Field of application ................................. 13
5 Application / Properties .......................... 13
6 Installation .............................................. 14
6.1 Mounting................................................ 14
6.2 Opening apparatus/ ....................................
Electrical connection .............................. 14
6.3 Cable entries (KLE); ...................................
blanking plugs ........................................ 15
6.4 Flange and metal plates ........................ 15
6.5 Closing apparatus / ....................................
Cover closure ......................................... 15
6.6 Putting into operation ............................. 15
7 Maintenance / Servicing......................... 16
8 Repairs / Overhaul / ....................................
Modification ........................................... 16
9 Disposal /
Recycling ................................................ 16
1 Caractéristiques techniques ...................17
1.1 Boites de commande complete..............17
1.2 Modules général ....................................17
1.2.1 Bouton-poussoir 2
pole et interrupteurer
1.2.2 Bouton-poussoir 4
pole et interrupteur .................................18
1.2.3 Potentiomètre .........................................18
1.3 Lampe de signalisation ...........................18
1.4 Instrument de mesure AM45 / AM72
Instrument de mesure VM45 / VM72 .....19
1.5 Bornier ....................................................19
1.6 Circuit à
sécurité intrinsèque ................................19
2 Consignes de sécurité ........................... 20
3 Conformité avec les normes .................. 20
4 Domaine d’utilisation ............................. 20
5 Utilisation /
Propriétés ............................................... 20
6 Installation .............................................. 21
6.1 Montage................................................. 21
6.2 Ouverture de l’appareil / .............................
Raccordement électrique ....................... 21
6.3 Entrées de câble (KLE) / .............................
Bouchons de fermeture ......................... 22
6.4 Plaques à brides * .................................. 22
6.5 Fermeture de l’appareil /
Fermeture à couvercle ........................... 22
6.6 Mise en service ...................................... 22
7 Maintien / Entretien ............................... 23
8 Réparations / Remise en état ................. 23
9 Évacuation des déchets / ...........................
Recyclage ............................................... 23
Konformitätserklärung separat beigelegt. Declaration of conformity, enclosed separately. Déclaration de conformité, jointe séparément.
3
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
Maßbilder in mm
X = Befestigungsmaße
1 Technische Angaben
1.1 Komplette Steuergeräte
ATEX EG-Baumusterprüfbescheinigung: PTB 00 ATEX 3117
Gerätekennzeichnung nach 2014/34/EU und Norm:
EN 60079-0
D II 2 G Ex e mb IIC T6 Gb
D II 2 G Ex e ib mb IIC T6 Gb
D II 2 G Ex d e mb IIC T6 Gb
D II 2 G Ex d e ib mb IIC T6 Gb
D II 2 D Ex tb IIIC T80 °C Db
IECEx Konformitätsbescheinigung: IECEx BKI 04.0003
Gerätekennzeichnung:
IEC 60079-0 Ex e IIC T6
Ex e ib IIC T6
Ex d e IIC T6
Ex d e ib IIC T6
Bemessungsspannung: bis max. 690 V
Bemessungsstrom: max. 16 A
Zulässige Umgebungstemperatur:
(Abweichende Temperaturen sind bei Sonderversionen möglich)
-20° C bis +40° C (Listenausführung)
Zul. Lagertemperatur in Originalverpackung: -20° C bis +40° C
Schutzart nach EN/IEC 60529: IP 66 (Listenausführung)
IP 65 mit Doppeldrucktaster
Schutzklasse nach EN/IEC 61140: I – mit Metallflansch
II – wird von den Kunststoffsteuergeräten erfüllt
PE-Anschlussklemmen: 2 x 4 mm²
Anschlussklemmen: siehe Einbaukomponenten
Leitungseinführung (Listenausführung): 1 x M25
geeignete Leitungen und Prüfdrehmomente der Druckschraube
Kabel- und Leitungseinführung (KLE) M12 M16 M20 M25 M32
Dichtung 1+2+3
(Ø mm / Nm)
1 2
3
min.
max.
(1)(2)
--- ---
5,5 / 1,5
7,0 / 1,0
8,0 / 1,5
10,0 / 2,0
---
Dichtung 1+2
(Ø mm / Nm)
1 2
3
min.
max.
(1)(2)
---
5,5 / 1,0
7,0 / 1,0
7,0 / 1,5
9,0 / 1,4
10,0 / 2,3
13,0 / 2,6
14,0 / 3,0
17,0 / 4,0
Dichtung 1
(Ø mm / Nm)
1 2
3
min.
max.
(2)
5,0 / 0,8
7,0 / 1,0
7,0 / 1,0
10,0 / 1,4
9,5 / 1,0
13,0 / 1,7
13,5 / 1,3
17,5 /2,3
17,5 / 1,5
21,0 / 1,3
Prüfdrehmomente Einschraubgewinde (Nm) 1,2 3,3 2,7 3,0 5,0
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann
der Klemmbereich v
ariieren. Bitte verwenden Sie im Zwischenbereich die Kombination aus Dichtung 1 + 2 +3.
(2)
Bei der Wahl der Dichtungsgummis darauf achten, dass bei zukünftigen Wartungsarbeiten an der KLE,
die Hutmutter nachgezogen werden kann.
Gewicht:
Steuergerät GHG 411 81 (P411) ca. 0,25 kg (Leergewicht)
Steuergerät GHG 411 82 (P412) ca. 0,35 kg (Leergewicht)
Steuergerät GHG 411 83 (P413) ca. 0,45 kg (Leergewicht)
Steuergerät GHG 412 82 (F412) ca. 0,80 kg (inklusive Messinstrument)
Prüfdrehmomente Deckelschrauben 2,50 Nm
GHG 411 81
GHG 411 82
GHG 411 83
GHG 412 82
Flanschausschnitt für GHG 412 82
ATEX EG-Baumusterprüfbescheinigung: IBExU14ATEX1030U
Gerätekennzeichnung nach 2014/34/EU und Norm:
EN 60079-0
D II 2 G
Ex d e IIC/IIB Gb
D I M 2
Ex d e I Mb
IECEx Konformitätsbescheinigung: IECEx IBE 14.0005U
Gerätekennzeichnung:
IEC60079-0 Ex d e IIC/IIB Gb
Ex d e I Mb
Betriebstemperaturbereich:
II 2 G ... IIC
-45 °C bis +80 °C
II 2 G ... IIB
-60 °C bis +80 °C
1.2 Drucktaster-, Schalter- und Potentiometersockel allgemein
4
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
Maßbilder Bedienelemente
1.2.1 Drucktastersockel 2 polig für
Drucktaster, Schlagtaster, Schalter und Schlüsseltaster
1.2.2 Drucktastersockel 4 polig für
Drucktaster, Schlagtaster, Schalter und Schlüsseltaster
Bemessungsspannung: bis max. 500 V
Bemessungsstrom
maximal
Bemessungsan-
schlussquerschnitt
Umgebungstemperatur
maximal
20 A 2,5 mm² 40 °C
16 A 4,0 mm² starr 40 °C
12 A 2,5 mm² 50 °C
15 A 4,0 mm² starr 50 °C
Schaltvermögen AC 15 (EN 60947-5-1): 250 V / 6 A 500 V / 4,0 A
Schaltvermögen DC 13 (EN 60947-5-1): 24 V / 6 A 60 V / 0,8 A 110 V / 0,5 A
mit Goldspitzkontakten: max. 400 mA
Anschlussklemmen: 2 x 1,0 - 2,5 mm²;
1 x 4,0 mm² starr
Prüfdrehmoment Anschlussklemmen 2,5 Nm
Gewicht: 2 polig ca. 0,15 kg
4 polig ca. 0,35 kg
1.2.3 Potentiometer
Bemessungsspannung: bis 250 V
Leistung: 1 W
Drehbereich: 270°
Skalierung: 0 - 100%
Anschlussklemme/Prüfdrehmoment: 2 x 1,0 - 2,5 mm²
1 x 4,0 mm² starr
Prüfdrehmoment Anschlussklemmen 2,5 Nm
Gewicht: ca. 0,15 kg
1.3 Signallampe
ATEX EG-Baumusterprüfbescheinigung: IBExU 12ATEX 1047 U
Gerätekennzeichnung nach 2014/34/EU und Norm:
EN 60079-0
D II 2 G
Ex de IIC/IIB Gb
D II 2 G
Ex d ia IIC/IIB Gb
IECEx Konformitätsbescheinigung: IECEx IBE 13.0031U
Gerätekennzeichnung:
IEC 60079-0 Ex d e IIC/IIB Gb
Ex d ia IIC/IIB Gb
Betriebstemperaturbereich:
D II 2 G Ex ... IIC
-45 °C bis +60 °C
D II 2 G Ex ... IIB
-60 °C bis +60 °C
(Abweichende Temperaturen sind bei Sonderversionen möglich)
Bemessungsspannung/Bemessungsstrom:
"e" erhöhte Sicherheit 20 V bis 254 V AC/DC 4 bis 15 mA
"i" eigensichere Ausführung 10 V bis 30 V DC max. 25 mA
"e" erhöhte Sicherheit 12 V bis 24 V AC/DC max. 24 mA
Ex-i Daten: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Anschlussklemmen: 2 x 1,0 - 2,5 mm²; 1 x 4,0 mm² starr
Prüfdrehmoment Anschlussklemmen 2,5 Nm
Gewicht: ca. 0,15 kg
Drucktastervorsatz
Doppeldrucktastervorsatz
Schlagtastervorsatz
Signalleuchtenvorsatz mit Kalotte
Schlagtastervorsatz „NOT-AUS“
Schlagtastervorsatz „NOT-AUS“ mit
Schlüsselentriegelung
Schlüsselschalter*-/ tastervorsatz
*
z.Zt. nicht bescheinigt für Kategorie II D
5
Maßbilder Bedienelemente
2
1
Messinstrumentenvorsatz AM/VM45
Messinstrumentenvorsatz AM/VM72
Schalter- und Potentiometervorsatz
X = Befestigungsmaße
Bild 1
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
1.5 Klemmenblock
1.4 Messinstrument AM45 / AM72
Messinstrument VM45/VM72
1.6 Eigensichere Stromkreise
Sicherheitstechnische Maximalspannung U
m
: 690 V
eff
Galvanisch sicher getrennt von allen anderen
Stromkreisen und von Erde
ATEX EG-Baumusterprüfbescheinigung: BVS 14 ATEX E 125U
Gerätekennzeichnung nach 2014/34/EU und Norm:
Dreheisen
D II 2 G
Ex e IIC Gb
D II 2 G
Ex e mb IIC Gb
Drehspule
D II 2 G
Ex ib IIC Gb
IECEx Konformitätsbescheinigung: IECEx BVS 14.0082U
Gerätekennzeichnung:
Dreheisen Ex e IIC Gb
Ex e mb IIC Gb
Drehspule Ex ib IIC Gb
Betriebstemperaturbereich: -55 °C bis +80 °C
Bemessungsspannung: bis max. 500 V
Dreheisen Drehspule
Genauigkeit: Klasse 2,5 Klasse 1,5
Überlastbereich: fach sek.
fach sek.
fach sek.
fach sek
anzeigend
Messbereiche:
direkt
Leistungsaufnahme:
Spule: Windungen
Innenwiderstand:
Li:
Ci:
Ui:
Ii:
Anschlussklemmen: fein- / mehrdrähtig
eindrähtig
Prüfdrehmoment Anschlussklemme:
Gewicht AM/VM 45:
AM/VM 72:
EN 60079-0
IEC 60079-0
10 - - 25 1
0 - - 5
25 - - 4
50 - - 1
1:1,5
AM: n / 1A 0 - 24 mA
0 - 25 A 4 - 24 mA
VM45: 6 - 415 V
VM72: 6 - 660 V
VM45:
0,91 - 1,76 VA
VM72:
0,91 - 2,65 VA
26,5
2,5 Ohm +- 30%
-
max. 0,1 mH
-
max. 0,1 nF
-
max. 30 V
-
max. 150 mA
2 x 0,5 - 2,5 mm²
1 x 4,0 mm²
2,5 Nm
ca. 0,35 Kg
ca. 0,40 Kg
ATEX Konformitätsbescheinigung: SEV 13 ATEX 0178 U
Gerätekennzeichnung nach 2014/34/EU und Norm:
EN 60079-0
II 2 G
Ex eb IIC
IECEx Zertifikat IECEx SEV 13.0012 U
Gerätekennzeichnung: IEC60079-0 Ex eb IIC
Klemmentyp: 6 x MUT 4
Bemessungsspannung: bis 352 V
Anschlussquerschnitt: 2 x 0,2 - 4,0 mm²
Prüfdrehmoment Anschlussklemmen: 0,6 - 0,8 Nm
Gewicht: ca. 0,08 kg
6
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
2 Sicherheitshinweise
a
Zielgruppe:
Elektrofachkräfte und qualifizierte
Personen gemäß den nationalen
Rechtsvorschriften, einschließlich der ein-
schlägigen Normen für elektrische Geräte in
explosionsgefährdeten Bereichen
(EN/IEC 60079-14).
Die Steuergeräte GHG 411 und GHG 412
sind nicht für Zone 0 und Zone 20 geeignet.
Die auf den Steuergeräten angegebene
Temperaturklasse und Explosionsgruppe ist
zu beachten.
Umbauten oder Veränderungen an den
Steuergeräten sind nicht gestattet. Sie sind
bestimmungsgemäß in unbeschädigtem
und einwandfreiem Zustand zu betreiben.
Die Anforderungen der EN/IEC 60079-31 u.a.
in Bezug auf übermäßige Staubablagerun-
gen und Temperatur, sind vom Anwender zu
beachten.
Als Ersatz und zur Reparatur dürfen nur
Originalteile von CEAG verwendet werden.
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von COOPER Crouse-
Hinds oder einer qualifizierten Elektro-
fachkraft in Übereinstimmung mit national
geltenden Regeln durchgeführt werden.
Vor Inbetriebnahme müssen die Steuergerä-
te entsprechend der im Abschnitt 6
genannten Anweisung geprüft werden.
Beachten Sie die nationalen Sicherheits-
und Unfallverhütungsvorschriften und die
nachfolgenden Sicherheitshinweise in dieser
Betriebsanleitung, die wie dieser Text in
Kursivschrift gefasst sind!
3 Normenkonformität
Das Betriebsmittel entspricht den aufgeführten
Normen, in der separat beigelegten Konformi-
tätserklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die Steuergeräte mit den Einbaukomponenten
(siehe "Technische Daten"), sind zum Einsatz in
explosionsgefährdeten Bereichen der Zonen 1
und 2 sowie der Zonen 21 und 22 gemäß
EN/IEC 60079-10-1 und EN/IEC 60079-10-2
geeignet!
Die eingesetzten Gehäusematerialien ein-
schließlich der außenliegenden Metallteile
bestehen aus hochwertigen Werkstoffen, die
einen anwendungsgerechten Korrosionsschutz
und Chemikalienresistenz in „normaler
Industrie atmosphäre gewährleisten:
– schlagfestes Polyamid
– Edelstahl AISI 316 L
Bei einem Einsatz in extrem aggressiver
Atmosphäre, können Sie zusätzliche Informa-
tionen über die Chemikalienbeständigkeit der
eingesetzten Kunststoffe, bei Ihrer zuständigen
Cooper Crouse-Hinds Niederlassung erfragen.
5 Verwendung / Eigenschaften
Die Steuergeräte GHG 411 und GHG 412
dienen zur Vor-Ort-Steuerung elektrischer
Anlagen in explosionsgefährdeten Bereichen.
Diese Geräte sind, abhängig vom Einzelfall, je
nach Bedarf mit den verschiedenen Einbaukom-
ponenten ausgerüstet.
Speziell gekennzeichnete Sonderausführungen
der Steuergeräte können in „eigensicheren
Stromkreisen“ eingesetzt werden.
Die für die „Eigensicherheit maßgebenden
elektrischen Grenzwerte sind zu beachten.
Die Ausführung mit Goldspitzkontakten ist für
die Schaltung von Kleinspannungsstromkreisen
geeignet. Maximale Strombelastung beachten,
(siehe Seite 3, technische Daten). Die
Ausführung mit Goldkontakten ist mit „G“ auf
den Sockeln gekennzeichnet.
Um eine sichere Trennung der Taster- und
Schalterkontakte zu gewährleisten, sind die
Öffnerkontakte als Zwangsöffner ausgeführt.
Die Sockel sind je nach Bedarf auch mit
0,6 W Widerständen, Feinsicherungen und
Dioden bestückt (max. Verlustleistung 1 W).
Die Messinstrumente AM/VM72 und AM/VM45
dienen zur Vor-Ort-Anzeige von elektrischen
Größen. (Ausführung des Messwerkes, der
Genauigkeit sowie Anschlussversion – siehe
Technische Daten“).
Bei Messinstrumenten AM/VM72 und AM/
VM45 für Wandleranschluss n/1A (Bild 1, Pos.
2) können über eine oben am Messinstrument
angebrachte Klappe die Wechselskalen (Bild 1,
Pos. 1) ausgetauscht werden.
Die Kleinsteuerschalter können durch Aus-
schneiden des Schaltkragens an der jeweiligen
Abschließposition über ein Vorhängeschloss
abgeschlossen werden (Ø Schlossbügel bis
5 mm).
7
Der 4-polige Drucktastersockel kann in die
Gehäusegrößen ab 2 Einbaukomponenten
eingebaut werden. Er benötigt zwei Einbaufel-
der. Der Bedienvorsatz liegt dann in der Mitte
der beiden Einbaufelder. Der 4-polige Drucktas-
tersockel kann mit den Standard CCH
Bedien vorsätzen betrieben werden.
Soll der 4-polige Drucktastersockel mit einem
Schlagtaster Not-AUS-Vorsatz mit Verrastung
betrieben werden, so muss dieser Vorsatz mit
einer verstärkten Verrastung ausgestattet sein.
Dieser Vorsatz ist an der roten Schlagscheibe
mit schwarzen Einlegeplättchen erkennbar
und z. B. unter der CCH Artikelnummer
GHG 410 1437R.... erhältlich.
a Angaben aus Punkt 3 und 4 sind bei der
Verwendung zu berücksichtigen.
a Andere als die beschriebenen Anwendun-
gen sind ohne schriftliche Erklärung der
Fa. COOPER Crouse-Hinds nicht zulässig.
a Beim Betrieb sind die in der Betriebs-
anleitung unter Punkt 7 genannten An-
weisungen zu beachten.
a Die Verantwortung hinsichtlich bestim-
mungsgemäßer Verwendung dieser
Steuergeräte unter Bezugnahme der in
dieser Anleitung vorhandenen Rahmenbe-
dingungen (siehe technische Daten) liegt
allein beim Betreiber.
6 Installation
Für das Errichten / Betreiben sind die relevanten
nationalen Vorschriften (z.B. Betr.Si.V, Geräte-
sicherheitsgesetz in Deutschland) sowie die
allgemein anerkannten Regeln der Technik
maßgebend (EN/IEC 60079-14).
a Unsachgemäße Installation der Steu-
er-geräte können zum Verlust der Garantie
führen.
6.1 Montage / Demontage
Die Montage der Steuergeräte GHG 411 kann
ohne Öffnen der Gehäuse erfolgen.
Die Steuergeräte dürfen bei der Direktmontage
an der Wand nur an den vorgesehenen
Befestigungspunkten eben aufliegen. Die
gewählte Schraube muss der Befestigungs-
öffnung angepasst sein (siehe Maßbilder
Seite 3).
Sie dürfen die Öffnung nicht beschädigen
(z.B. Verwendung einer Unterlegscheibe).
a Bei übermäßigem Anziehen können die
Steuergeräte beschädigt werden.
Die Steuergeräte GHG 411 sind zur Befestigung
auf den CEAG-Gerätehaltern mittels Form- oder
selbstschneidenden Schrauben geeignet (siehe
Seite 9).
Die betreffende Montageanleitung ist zu
beachten.
Die Montage der Steuergeräte GHG 412 kann
in den dafür vorgesehenen Flanschausschnitt
(siehe Seite 3) erfolgen.
Dabei ist auf eine ebene Dichtungsfläche und
die Unversehrtheit der eingeschäumten
Dichtung im Gehäusedeckel des Steuergerätes
zu achten.
Die Befestigung des Steuergerätes im
Flanschausschnitt erfolgt durch die hinter den
Flanschausschnitt eingreifenden Befestigungs-
laschen. Sie werden mit den 2 Befestigungs-
schrauben auf der Vorderseite des Gehäuse-
deckels durch festschrauben (rechtsdrehend)
betätigt.
6.2 Öffnen des Gerätes/
Elektrischer Anschluss
a Vor Öffnen der Geräte ist die Spannungs-
freiheit sicherzustellen bzw. sind geeignete
Schutzmaßnahmen zu ergreifen.
a Der elektrische Anschluss des Betriebs-
mittels darf nur durch Fachpersonal
erfolgen. (EN/IEC 60079-14)
Die ordnungsgemäß abisolierten Anschlusslei-
tungen der Kabel sind unter Berücksichtigung
einschlägiger Vorschriften anzuschließen.
Bei der Verwendung von mehr- oder fein-
drähtigen Anschlusskabel /-leitungen sind die
Aderenden entsprechend den geltenden
nationalen und internationalen Vorschriften zu
behandeln (z.B. Verwendung von Aderendhül-
sen).
a Zur Aufrechterhaltung der Zündschutzart
ist der Leiteranschluss mit besonderer
Sorgfalt durchzuführen. Die Isolation der
Anschlussleitungen muss bis an die Klemme
heranreichen. Der Leiter selbst darf nicht
beschädigt sein.
a Bei Mischbestückungen Ex-e / Ex-i sind
die erforderlichen Mindestabstände
einzuhalten (siehe z.B. EN/IEC 60079-11).
Bei geöffneten Geräten ist sicherzustellen
(Spannungsfreiheit herstellen), dass keine
Spannungsverschleppung auf die ange-
schlossenen eigensicheren Stromkreise
übergreift.
Die Errichtungshinweise für eigensichere
elektrische Betriebsmittel sind zu beachten.
Es ist sicherzustellen, dass die für den
speziellen, eigensicheren Stromkreis zulässige
äußere Kapazität und Induktivität nicht
überschritten wird.
Die minimal und maximal anschließbaren
Leiterquerschnitte sind zu beachten (siehe
technische Daten). Die Standardklemmen sind
zum Direktanschluss von Leitern mit Kupfer-
adern ausgelegt.
Drucktastersockel 1 x 4 polig
Drucktastersockel 2 x 2 polig
Schlagtaster mit verstärkter Verrastung
GHG 410 1437R....
21
22 44
43
R1
34
33
11
12
44
43
R2
34
33
24
23
14
13
21
22
R3
11
12
41
42
31
32
44
43
R4
34
33
24
23
11
12
21
22
R5
11
12
31
32
44
43
S 1
S 2
S 4
S 3
S 2
S 4
S 3
S4
S 1
21
22 44
43
R1
34
33
11
12
44
43
R2
34
33
24
23
14
13
21
22
R3
11
12
41
42
31
32
44
43
R4
34
33
24
23
11
12
21
22
R5
11
12
31
32
44
43
S2 S3S1
Schlagscheibe
ROT
Einlegeplättchen
schwarz
Unterteil
gelb
S4S2 S3S1
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
8
Schaltabwicklungen
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
Alle Schrauben und/oder Muttern der An
schlussklemmen, auch die der nicht benutzten,
sind fest anzuziehen.
!
Wird das Betriebsmittel in der Ausführung
„Schutzisoliert“ ausgeführt, kann das
entsprechende Klebeschild ( )
GHG 905 1002 P0005 beim Hersteller
angefordert werden.
!
Wird die eingebaute Klemmentragschiene
nicht komplett mit Reihenklemmen bestückt,
muss die Klemmentragschiene in den
Potentialausgleich mit einbezogen werden.
Das Schaltbild der Einbaukomponenten ist auf
den Komponenten angegeben, dem Schaltgerät
beigelegt oder aus der Betriebsanleitung zu
entnehmen.
Werden die Einbaukomponenten (Messinstru-
ment AM/VM72 und AM/VM45, Drucktaster-
sockel, Signalleuchtensockel, Steuerschalterso-
ckel, Potentiometersockel usw.) zur leichteren
Verdrahtung aus der Profilschiene im Gehäuse-
boden der Steuergeräte ausgeschnappt, sind
die Komponenten hiernach wieder vorschrifts-
mäßig in die entsprechende Einrastposition auf
der Profilschiene einzusetzen. Zum Ausschnap-
pen der Komponenten (u.a. auch die
Messinstru mente AM/VM72 + AM/VM45),
werden die Rasthaken zum entriegeln nach
außen gezogen.
Um ein korrektes Schließen der Geräte zu
gewährleisten, ist ein Schalten an der Schalt-
achse der Schalteinsätze bei geöffnetem Gerät
nicht zulässig.
a Die Einrastpositionen der Ein-
baukomponenten müssen mit den Einker-
bungen der Profilschiene übereinstimmen!
6.3 Kabel- und Leitungs-
einführungen (KLE);
Verschlussstopfen
a Es dürfen generell nur bescheinigte und
geeignete KLE's und Verschlussstopfen
verwendet werden. Für bewegliche
Leitungen sind Trompeten verschraubungen
oder andere geeignete Einführungen mit
zusätzlicher Zugentlastung zu verwenden.
Die für die eingesetzten KLE maßgebenden
Montagerichtlinien sind zu beachten. Beim
Einsatz von KLE mit einer niedrigeren als der für
das Gerät zutreffenden IP-Schutzart, wird die
IP-Schutzart des gesamten Gerätes reduziert.
Eigensichere Stromkreise sind über die farblich
(hellblau) gekennzeichneten KLE einzuführen.
Beim Einsatz von nur für fest verlegte
Leitungen geeigneten Kabel- und Leitungsein-
führungen ist sicherzustellen, dass keine
unzulässig hohe mechanische Beanspruchung
der Kabel- und Leitungseinführung und/oder
deren Dichtung erfolgt.
Nicht benutzte Einführungsöffnungen sind mit
einem bescheinigten Verschlussstopfen zu
verschließen, um die Mindestschutzart
herzustellen.
Es ist darauf zu achten, dass bei der Installation
der KLE’s die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden. Bei ausschneidbaren Dichtungs-
einsätzen ist sicherzustellen, dass der Einsatz
ordnungsgemäß dem Leitungsdurchmesser
angepasst wird. Zur Sicherstellung der
erforderlichen Mindestschutzart sind die KLE’s
fest anzuziehen.
a Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
a Beim Anziehen der Hutmutter der
Metall-KLE (z.B. Typ ADE) ist die Verschrau-
bung mit einem geeigneten Werkzeug gegen
Verdrehen zu sichern.
Alle nicht benutzten metrischen CEAG KLE sind
mit dem bescheinigten Verschluss für
metrische KLE zu verschließen.
6.4 Flansche und Metallplatten *
Müssen Flanschplatten demontiert werden
(z.B. zum Bohren von Einführungsöffnungen),
ist bei der Montage zur Aufrechterhaltung der
Mindestschutzart auf den korrekten Sitz der
Flanschplatte zu achten.
a Von außen herangeführte PE-Leitungen
sind auf die dafür vorgesehene PE-Klemme
am Flansch anzuschließen. Der maximale
Anschlussquerschnitt beträgt 6 mm².
a Metallflansche, Metallplatten und
Metallverschraubungen müssen in den
Potentialausgleich miteinbezogen werden.
* z.Zt. nicht bescheinigt für Kategorie II D
6.5 Schließen des Gerätes /
Deckelverschluss
a Beim Aufsetzen der Gehäusedeckel ist
darauf zu achten, dass die Vorsätze korrekt
mit den Einbaukomponenten übereinstim-
men, dass die Schaltachse der Schalteinsät-
ze korrekt in die Mitnehmeröffnung der
Schaltgriffe eingeführt wird, und der zum
Gehäuse unterteil gehörige Deckel ver-
wendet wird.
Der Schaltgriff muss in der gleichen Stellung
stehen, die er beim Öffnen des Gerätes
innehatte.
Alle Fremdkörper sind aus dem Gerät zu
entfernen.
Zur Sicherstellung der erforderlichen Mindest-
schutzart sind die Deckelschrauben fest
anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Drucktaster
Doppeldrucktaster
Schlagtastertaster
Schlagtastertaster mit Schlüssel
Schlüsseltaster
Potentiometer
Steuerschalter R6201
Steuerschalter R6102
Steuerschalter R6002
Steuerschalter R5307
Steuerschalter R5507
Steuerschalter R8701
9
Befestigungslöcher auf Gerätehalter Größe 1
Befestigungslöcher auf Gerätehalter Größe 2
D
Explosionsgeschützte Steuergeräte
GHG 411 und GHG 412
8 Reparatur / Instandsetzung /
Änderung
Instandsetzungsarbeiten / Reparaturen dürfen
nur mit CEAG Originalersatzteilen vorgenom-
men werden.
a Bei Schäden an der druckfesten Kapse-
lung ist nur ein Austausch zulässig. Im
Zweifels falle ist das betroffene Betriebsmit-
tel an CEAG zur Reparatur zurückzugeben.
a Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von COOPER Crouse-
Hinds oder einer qualifizierten Elektrofach-
kraft in Übereinstimmung mit national
geltenden Regeln durchgeführt werden.
(EN/IEC 60079-19)
Umbauten oder Änderungen am Betriebsmittel
sind nicht gestattet; ausgenommen ist das
Anbringen von zusätzlichen KLE’s im Rahmen
der Zulassung des Betriebsmittels oder nach
Angaben des Herstellers.
Bei Austausch einzelner Einbaukomponenten
(Messinstrument, Taster usw.) ist Pkt. 6.2
„Öffnen des Gerätes / Elektrischer Anschluss“
zu beachten.
9 Entsorgung /
Wiederverwertung
Bei der Entsorgung des Betriebsmittels und
der Einbaukomponenten (Messinstrument,
Signalleuchte, Taster usw.) sind die jeweils
geltenden nationalen Abfallbeseitigungsvor-
schriften zu beachten.
Zur Erleichterung der Wiederverwertbarkeit
von Einzelteilen sind Kunststoffteile mit dem
Kennzeichen des verwendeten Kunststoffes
versehen.
Programmänderungen und -ergänzungen sind
vorbehalten.
6.6 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind
die in den einzelnen nationalen Bestimmungen
genannten Prüfungen durchzuführen.
Außerdem ist vor der Inbetriebnahme die
korrekte Funktion und Installation des Betriebs-
mittels und der Einbaukomponenten (Messinst-
rument, Signalleuchte, Taster usw.) in Überein-
stimmung mit dieser Betriebsanleitung und
anderen anwendbaren Bestimmungen zu
überprüfen.
Die Nullpunkteinstellung des Messinstrumente-
zeigers ist vor der Inbetriebnahme zu über-prü-
fen. Gegebenenfalls mit der Justierschraube
den Messgerätezeiger auf den Nullpunkt
einjustieren.
Die Gasgruppe (II B bzw. II C) des eigensiche-
ren Stromkreises ist zur Bewertung der
Gasgruppe der Einbaukomponenten zu
berücksichtigen.
a Unsachgemäßer Betrieb der Steuergeräte
kann zum Verlust der Garantie führen.
7 Instandhaltung / Wartung
a Die für die Wartung / Instandhaltung von
elektrischen Betriebsmitteln in explosions-
gefährdeten Bereichen geltenden nationalen
Bestimmungen sind einzuhalten
(z.B. EN/IEC 60079-17).
Vor Öffnen des Gehäuses Spannungsfreiheit
sicherstellen bzw. geeignete Schutzmaßnah-
men ergreifen.
Bei eigensicheren Stromkreisen ist das Arbeiten
unter Spannung zulässig.
Die erforderlichen Wartungsintervalle sind
anwendungsspezifisch und daher in Abhängig-
keit von den Einsatzbedingungen vom Betreiber
festzulegen.
Im Rahmen der Wartung sind vor allem die Teile,
von denen die Zündschutzart abhängt, zu
prüfen (z.B. Unversehrtheit der druckfesten
Komponenten, des Gehäuses, der Dichtungen
und der Kabel- und Leitungseinführungen),
sowie die Schaltwerksfunktion.
Sollte bei einer Wartung festgestellt werden,
dass Instandsetzungsarbeiten erforderlich sind,
ist Abschnitt 8 dieser Betriebsanleitung zu
beachten.
Gerätehalter für Gitterrinnen-
und Wand befestigung
Gerätehalter für Gitterrinnen-
und Wand befestigung
Befestigungs-
löcher für
Steuergerät
GHG 411 81
Gerätehalter
für Rohrbefestigung
Gerätehalter für Rohrbefesti-
gung
Befestigungslöcher
für Steuergerät
GHG 411 82
Befestigungslöcher
für Steuergerät
GHG 411 83
10
E
Explosion-protected control units
GHG 411 and 412
Dimensions in mm
X = fixing dimensions
1 Technical data
1.1 Control unit assemblies
ATEX type examination certificate: PTB 00 ATEX 3117
Marking acc. to 2014/34/EU and standard:
EN 60079-0
D II 2 G Ex e mb IIC T6 Gb
D II 2 G Ex e ib mb IIC T6 Gb
D II 2 G Ex d e mb IIC T6 Gb
D II 2 G Ex d e ib mb IIC T6 Gb
D II 2 D Ex tb IIIC T80 °C Db
IECEx type examination certificate: IECEx BKI 04.0003
Category of application:
IEC60079-0 Ex e IIC T6
Ex e ib IIC T6
Ex d e IIC T6
Ex d e ib IIC T6
Rated voltage: up to max. 690 V
Rated current: max. 16 A
Permissible ambient temperature:
Other temperatures possible for special versions.
-20° C to +40° C (standard version)
Perm. storage temperature in original packing:
-20° C to +40° C
Degree of protection to IEC/EN 60529: IP 66 (standard version)
IP 65 Double push button
Insulation class acc. to IEC/EN 61140: I - with metal flange
II - plastic terminal boxes fulfil this requirement
PE- terminal: 2 x 4 mm²
Terminals: see built-in components
Cable entries (standard version): 1 x M25
suitable cables and test torques of the pressure srew
Cabel entry: M12 M16 M20 M25 M32
seel 1+2+3
(Ø mm / Nm)
1 2
3
min.
max.
(1) (2)
--- ---
5,5 / 1,5
7,0 / 1,0
8,0 / 1,5
10,0 / 2,0
---
seel 1+2
(Ø mm / Nm)
1 2
3
min.
max.
(1) (2)
---
5,5 / 1,0
7,0 / 1,0
7,0 / 1,5
9,0 / 1,4
10,0 / 2,3
13,0 / 2,6
14,0 / 3,0
17,0 / 4,0
seel 1
(Ø mm / Nm)
min.
max.
(2)
5,0 / 0,8
7,0 / 1,0
7,0 / 1,0
10,0 / 1,4
9,5 / 1,0
13,0 / 1,7
13,5 / 1,3
17,5 /2,3
17,5 / 1,5
21,0 / 1,3
Test torque for screw in thread cable entry (Nm) 1.2 3.3 2.7 3.0 5.0
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 + 3 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry.
Weight:
Control unit GHG 411 81 (P411) approx. 0.25 kg (empty weight)
Control unit GHG 411 82 (P412) approx. 0.35 kg (empty weight)
Control unit GHG 411 83 (P413) approx. 0.45 kg (empty weight)
Control unit GHG 412 82 (F412) approx. 0.80 kg (incl. measuring instrument)
Test torques: Cover screws 2.50 Nm
GHG 411 81
GHG 411 82
GHG 411 83
GHG 412 82
Flange opening for GHG 412 82
1.2 Actuator general
ATEX type examination certificate: IBExU14ATEX1030U
Marking acc. to 2014/34/EU and standard:
EN 60079-0
D II 2 G
Ex d e IIC/IIB Gb
D I M 2
Ex d e I Mb
IECEx type examination certificate: IECEx IBE 14.0005U
Category of application:
IEC60079-0 Ex d e IIC/IIB Gb
Ex d e I Mb
Operating temperature:
II 2 G ... IIC
-45 °C to +80 °C
II 2 G ... IIB
-60 °C to +80 °C
11
E
Explosion-protected control units
GHG 411 and 412
Dimensions of actuator elements
Pushbutton actuator
Double pushbutton actuator
Mushroom-head pushbutton actuator
Signal lamp bezel with lens
Mushroom-head pushbutton actuator
"EMERGENCY STOP"
Mushroom-head pushbutton actuator
"EMERGENCY STOP"
with key release
Key-operated switch* -/-pushbutton actuator
* not yet certified for category II D
Rated voltage: up to 500 V
Rated current
Rated supply
terminal
Permissible ambient
temperature max.
14 A 2.5 mm² 40 °C
16 A 4.0 mm² single wire 40 °C
12 A 2.5 mm² 50 °C
15 A 4.0 mm² single wire 50 °C
Switching capacity acc. to
AC 15
(EN 60947-5-1): 250 V / 6 A 500 V / 4.0 A
Switching capacity acc. to
DC 13
(EN 60947-5-1): 24 V / 6 A 60 V / 0.8 A 110 V / 0.5 A
with gold-tipped contacts: max. 400 mA
Supply terminal: 2 x 1.0 - 2.5 mm²
1 x 4.0 mm² single wire
Test torques: 2.5 Nm
Weight: 2 pole approx 0.15 kg
4 pole approx 0.35 kg
1.2.1 Actuator 2 pole for
push button, Mushroom head p.b., switch and Key-operated pushbutton
1.2.2 Actuator 4 pole for
push button, Mushroom head p.b., switch and Key-operated pushbutton
12.3 Potentiometer
Rated voltage: up to 250 V
Rating: 1 W
Turning range: 270°
Scale: 0 - 100%
Supply terminal/Test torques: 2 x 1.0 - 2.5 mm²
1 x 4.0 mm² single wire
Test torques: 2.5 Nm
Weight: approx. 0.15 kg
1.3 Signallamp
ATEX type examination certificate: IBExU 12ATEX 1047 U
Marking acc. to 2014/34/EU and standard:
EN 60079-0
D II 2 G
Ex de IIC/IIB Gb
D II 2 G
Ex d ia IIC/IIB Gb
IECEX type examination certificate: IECEx IBE 13.0031U
Category of application:
IEC60079-0 Ex d e IIC/IIB Gb
Ex d ia IIC/IIB Gb
Appliation temperature
D II 2 G Ex ... IIC
-45 °C up to +60 °C
D II 2 G Ex ... IIB
-60 °C up to +60 °C
(Other temperatures possible with special versions)
Rated voltage /Rated current:
"e" increased safety 20 V up to 254 V AC/DC 4 up to 15 mA
"i" intrinsically safe version 10 V up to 30 V DC max. 25 mA
"e" increased safety 12 V up to 24 V AC/DC max. 24 mA
Ex-i Datas: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Supply terminal: 2 x 1.0 - 2.5 mm²; 1 x 4.0 mm² single wire
Test torques: 2.5 Nm
Weight: approx. 0.15 kg
12
Dimension for actuator elements
2
1
Glass for measuring instrument AM/VM45
Glass for measuring instrument AM/VM72
Switch- and potentiometer actuator
X = fixing dimensions
Fig. 1
E
Explosion-protected control units
GHG 411 and 412
1.5 Terminal block
1.4
AM45 / AM72 measuring Instrument
VM45 / VM72 measuring instrument:
ATEX type examination certificate: BVS 14 ATEX E 125
Marking acc. to 2014/34/EU and standard:
Moving iron
D II 2 G
Ex e IIC Gb
D II 2 G
Ex e mb II CGb
Moving coil
D II 2 G
Ex ib IIC Gb
IECEx type examination certificate: IECEx BVS 14.0082U
Category of application:
Moving iron Ex e IIC Gb
Ex e mb IIC Gb
Moving coil Ex ib IIC Gb
Operating temperature -55 °C to +80 °C
Rated voltage: to max. 500 V
Moving iron Moving coil
Measuring accuracy: Klasse 2,5 Klasse 1,5
Overload range:
fold at sec. fold at
sec
fold at sec.
fold at sec
indicated
Measuring range:
direct
Power consumption:
Coil: turns
Internal resistance:
Li:
Ci:
Ui:
Ii:
Supply terminals: fine- / multy wire
solid wire
Test torques:
Weight: AM/VM 45
AM/VM 72
EN 60079-0
IEC 60079-0
10 - - 25 1
0 - - 5
25 - - 4
50 - - 1
1:1,5
AM: n / 1A 0 - 24 mA
0 - 25 A 4 - 24 mA
VM45: 6 - 415V
VM72: 6 - 660V
VM45:
0.91 - 1.76VA
VM72:
0.91 - 2.65VA
26.5
2.5 Ohm +- 30%
-
max. 0.1 mH
-
max. 0.1 nF
-
max. 30 V
-
max. 150 mA
2 x 0.5 - 2.5 mm²
1 x 4.0 mm²
2.5 Nm
approx. 0.35 Kg
approx. 0.40 Kg
1.6 Intrinsically safe circuits:
Intrinsically safe circuits: Max. safe voltage U
m
: 690 V
eff
Safe galvanic isolation from all other circuits
and earth
ATEX certificate: SEV 13 ATEX 0178 U
Marking acc. to 2014/34/EU and standard:
EN 60079-0
II 2 G
Ex eb IIC
IECEx certificate: IECEx SEV 13.0012 U
Category of application: IEC60079-0 Ex eb IIC
Type of terminal: 6 x MUT 4
Rated voltage: up to 352 V
Conductor cross-section: 2 x 0.2 - 4.0 mm²
Test torques: 0.6 - 0.8 Nm
Weight: approx. 0.08 kg
13
2 Safety instructions
a
Target group:
For skilled electricians and qualified
personnel in accordance with
national legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical appara-
tus for explosive atmospheres.
The control units GHG 411 and GHG 412 are
not suitable for zone 0 and Zone 20 hazard-
ous areas.
The temperature class and type of protec-
tion stated on the apparatus shall be
observed.
Modifications or changes to the control
units are not permitted.
They shall be used for their intended
purpose and shall be in a perfect and clean
state.
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the user.
Only original CEAG parts may be used as
replacements and for repairs.
Repairs that affect the explosion protection
may only be carried out by COOPER
Crouse-Hinds or by a qualified electrician in
compliance with the respective national
regulations.
Prior to being put into operation, the control
units shall be checked in accordance with
the instructions as per section 6.
The national safety rules and regulations for
the prevention of accidents, as well as the
safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!!
3 Conformity with standards
The apparatus is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4 Field of application
The control units are intended for use in
potentially explosive atmospheres in zones 1, 2
as well as in Zones 21 and 22 in accordance
with
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The enclosure materials used, including any
external metal parts, are high quality materials
that ensure a corrosion resistance and
resistance to chemical substances according to
the requirements for use in a ”normal industrial
atmosphere
- impact resistant polyamide
- special steel AISI 316 L.
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
5 Application / Properties
The control units GHG 411 and 412 are
intended for the local control of electrical
installations in potentially explosive atmos-
pheres. The units are fitted with built-in
components according to the respective
application.
Specially marked special versions of the control
units can be used in ”intrinsically safe circuits”.
The electrical limiting values that are
decisive for the intrinsic safety shall be
observed.
The version with gold-tipped contacts is suited
for switching extra-low voltage circuits. Special
attention shall be paid to the maximum current
load (see technical data). The contact chamber
of the gold-tipped version is marked with the
letter ”G” or colour-coded.
To ensure a safe and reliable disconnection, the
normally closed contacts are designed as
compulsory opening contacts.
Where required, the bases are fitted with 0.6 W
resistors, fine-wire fuses and diodes
(max. power dissipation 1 W).
The measuring instruments AM/VM72 and
AM/VM45 are used for the local indication of
electrical values. See ”Technical Data” for
details of measuring mechanism, accuracy and
connection.
With measuring instruments AM/VM72 and
AM/VM45 for c.t. connection n/1A (Fig. 1,
item 2) the interchangeable scales can be
exchanged via a flap on the upper part of the
measuring instrument (Fig. 1, item 1).
When the switch collar of small control
switches is cut out at the respective locking
position, they can be padlocked (padlock
shackle Ø up to 5 mm).
E
Explosion-protected control units
GHG 411 and 412
14
The 4 pole pushbutton contact can be added
with the standard CCH actuators.
If the 4 pole pushbutton contact is added with
an Emergency STOP Mushroom-head
pushbutton actuator, then you have to use the
actuators with CCH order number
GHG 410 1437R.
This actuators can be recognized by the red
thrust washer and black inserting sign.
a The data according to sections 3 and 4
shall be taken into account during use.
a Applications other than those described
are not permissible without a written
declaration of consent from Messrs.
COOPER Crouse-Hinds.
a During operation the instructions stated
in section 7 of the operating instructions
shall be observed.
a The sole responsibility with respect to
the suitability and proper use of the control
switches with regard to the basic require-
ments of these instructions (see technical
data) lies with the operator.
6 Installation
The relevant national regulations (e.g. Betr.Si.V,
the equipment safety law for Germany) and
the generally recognized rules of engineering
apply for the installation and operation
IEC/EN 60079-14.
a The improper installation and operation
of control switches may result in the
invalidation of the guarantee.
6.1 Mounting
The control units GHG 411 can be mounted
without opening the enclosure.
When the control units are mounted directly
onto the wall, they shall rest evenly only on the
fastening points provided for this purpose.
The screw chosen shall fit the fixing hole (see
dimensional drawings, page 10) and shall not
damage the hole (e.g. use of a washer).
The apparatus shall be fixed diagonally with a
minimum of 2 screws.
a If the screws are overtightened, the
apparatus may be damaged.
The control units GHG 411 and GHG 412 are
suited for mounting on CEAG apparatus holders
by means of self-cutting screws (see pages 16).
See the respective mounting instructions.
The control units GHG 412 can be mounted in
the flange openings provided for this purpose
(see page 10).
Here special attention shall be paid to an even
sealing surface and the perfect condition of the
seal that is foamed into the enclosure cover of
the control unit.
The control unit is mounted in the flange
opening by means of fixing lugs that engage
behind the flange opening.
These are actuated by turning the 2 fixing
screws on the front of the enclosure cover
clockwise.
6.2 Opening apparatus/
Electrical connection
a Before opening the apparatus, it is
necessary to ensure that there is no voltage
or to take suitable protective measures.
a The electrical connection of the may only
be carried out by specialists.
(IEC/EN 60079-14)
The properly bared conductors of cables shall
be connected with due regard to the respective
regulations.
If multi- or fine-wire connection cables are
used, the wire ends shall be handled according
to the applicable national and international
regulations (e.g. use of multicore cable ends).
a To maintain the explosion protection,
conductors shall be connected with special
care.The insulation shall reach up to the
terminal. The conductor itself shall not be
damaged.
a In the case of mixed Ex-e / Ex-i installa-
tions, the required minimum clearances
shall be maintained (see, for example,
IEC/EN 60079-11).When apparatus is open, it
is necessary to ensure (disconnect voltage
supply) that no voltage is carried over into
the connected intrinsically safe circuits.
The installation instructions for intrinsically safe
electrical apparatus shall be observed.
It is necessary to ensure that the permissible
external capacitance and inductance of the
special intrinsically safe circuits are not
exceeded.
The minimum and maximum conductor cross
sections that can be connected shall be
observed (see technical data).
Actuator 1 x 4 pole
Actuator 2 x 2 pole
Mushroom-head pushbutton actuator
"EMERGENCY STOP" GHG 410 1437R....
21
22 44
43
R1
34
33
11
12
44
43
R2
34
33
24
23
14
13
21
22
R3
11
12
41
42
31
32
44
43
R4
34
33
24
23
11
12
21
22
R5
11
12
31
32
44
43
S 1
S 2
S 4
S 3
S 2
S 4
S 3
S4
S 1
21
22 44
43
R1
34
33
11
12
44
43
R2
34
33
24
23
14
13
21
22
R3
11
12
41
42
31
32
44
43
R4
34
33
24
23
11
12
21
22
R5
11
12
31
32
44
43
S2 S3S1
thrust washer
red
inserting sign
black
base
yellow
S4S2 S3S1
E
Explosion-protected control units
GHG 411 and 412
15
Contact arrangements
All screws and/or nuts of connection terminals,
including those not in use, shall be tightened
down securely.
The standard terminals are designed for the
direct connection of conductors with copper
wires.
The circuit diagram of the built-in components
is shown on the components or attached to
them, or it is shown in the operating instruc-
tions.
!
In the case of building up the electrical
equipment in the "protective insulation" version,
appropriate sticker ( )
GHG 905 1002 P0005 can be requested by the
manufacturer.
!
If the inserted terminal rail is not equipped
completely with line-up terminals, the terminal
rail must be included in the equipotential earth
connection also.
If, to facilitate wiring, the built-in components
(AM/VM72 and AM/VM45 measuring instru-
ments, pushbutton contact block, signal lamp
bases, control switch contact blocks, potenti-
ometer bases, etc.) are snapped off the rail on
the bottom of the enclosure, the components
shall be snapped back properly into the same
notch on the rail.
To snap off components (including the
measuring instruments AM/VM72 and AM/
VM45), pull the hooks outwards to release
them.
To ensure that the apparatus closes correctly,
switching at the switch shaft of the switches
insert is not permitted when the apparatus is
open.
a Warning: the engaging positions of the
built-in components shall matches the
notches on the rail!
6.3 Cable entries (KLE);
blanking plugs
a Generally, only certified cable entries and
blanking plugs may be used. Flexible cables
shall be used with trumpet-shaped cable
glands or other suitable entries with
additional pull relief.
The relevant mounting directives for cables
entries being used shall be observed.
When using cable entries with a degree of
protection that is lower than the IP protection of
the apparatus (see page 9), the degree of IP
protection for the complete unit is reduced.
Intrinsically safe circuits shall be fed through
cable entries that are colour-coded (light blue).
When using cable entries for fixed cables it is
necessary to ensure that no inadmissible high
mechanical stress is applied to the cable entry
or its seal.
In order to ensure the minimum degree of
protection, any unused entry holes shall be
sealed with certified blanking plugs.
When fitting cable entries, care has to be taken
that the sealing inserts are suitable for the cable
diameter. In the case of sealing inserts that are
cut out, it is necessary to ensure that the insert
is properly adapted to the cable diameter.
In order to ensure the required minimum
degree of protection, the cable entries shall be
tightened down securely.
a Overtightening can impair the degree of
protection.
a Warning: When tightening the cap nut of
the metal cable entry (e.g. type ADE;
CMDEL), a suitable tool shall be used to
safeguard the gland against twisting.
Any unused metric CEAG cable entries shall be
sealed with the blanking plug certified for these
metric cable entries.
6.4 Flange and metal plates *
If flange plates have to be dismantled, (e.g. to
drill entry holes), when replacing the plates, in
order to maintain the minimum degree of
protection, it is necessary to ensure that the
flange plate and the fixing clamp fit correctly.
a PE conductors fed from outside shall be
connected to the PE terminal provided on
the flange. the maximum terminal cross
section is 6 mm².
a Warning: Metal flanges, metal plates and
metal glands shall be incorporated in the
potential equalization.
* not yet certified for category II D
6.5 Closing apparatus /
Cover closure
a When fitting the enclosure cover onto the
base, it is necessary to ensure that the
actuator elements correspond correctly with
the built-in components, care shall be taken
to ensure that the switch shaft of the switch
insert engages correctly in the carrier hole of
the switch handle and that the enclosure
cover for the respective base is being used.
The switch handle shall be in the position it had
when the apparatus was opened.
Any foreign matter shall be removed from the
apparatus.
To ensure the required minimum degree of
protection, the cover screws shall be tightened
down.
Overtightening may impair the degree of
protection.
Pushbutton
Double pushbutton
Mushroom-head pushbutton
Mushroom-head pushbutton with key
Key-operated pushbutton
Potentiometer
Control switch R6201
Control switch R6102
Control switch R6002
Control switch R5307
Control switch R5507
Control switch R8701
E
Explosion-protected control units
GHG 411 and 412
16
Fastening holes of the apparatus mounting
plates size 1
Fastening holes of the apparatus mounting
plates size 2
8 Repairs / Overhaul /
Modification
Only original CEAG parts shall be used for
carrying out repairs.
a In the event of damage to the flameproof
encapsulation, replacement of these
components is mandatory. In case of doubt,
the respective apparatus shall be sent to
COOPER Crouse-Hinds for repair.
a Repairs that affect the explosion
protection may only be carried out by
COOPER Crouse-Hinds or by a qualified
electrician in compliance with the respective
national regulations (IEC/EN 60079-19).
Apparatus modifications or design changes are
not permitted; excepted from this is the fitting
of additional cable entries within the scope of
the apparatus approvals or acc. to the instruc-
tions given by the manufacturer.
When replacing individual built-in components
(pushbuttons, etc.) section 6.2 ”Opening
apparatus / Electrical connection” shall be
observed.
9 Disposal / Recycling
The respective valid national regulations for
waste disposal shall be observed when
disposing of apparatus.
To facilitate the recycling of individual parts,
parts made of moulded plastic shall bear the
marking for the type of plastic used.
The product range is subject to changes and
additions.
6.6 Putting into operation
Before putting the apparatus into operation, the
tests specified in the individual national
regulations shall be performed.
In addition to this, before being put into
operation, the correct functioning of the
apparatus and of the built-in components
(measuring instruments, signal lamps,
pushbuttons, etc.) shall be checked in
accordance with these operating instructions
and other applicable regulations.
The zero setting of the measuring instrument
needle shall be checked before putting it into
operation. If necessary, the measuring
instrument needle shall be set to zero using the
adjustment screw.
The gas group (IIB or IIC) of the intrinsically safe
circuit shall be taken into consideration for the
evaluation of the gas group of the built-in
components.
a The improper operation of control units
may result in the invalidation of the
guarantee.
7 Maintenance / Servicing
a The valid national regulations for the
servicing / maintenance of electrical
apparatus for use in potentially explosive
atmospheres shall be observed.
(e.g. IEC/EN 60079-17)
Prior to opening the enclosure, it is
necessary to ensure that the voltage supply
has been isolated or to take suitable
protective measures.
Working with live circuits is permissible for
intrinsically safe circuits.
The necessary intervals between servicing
depend upon the specific application and shall
be stipulated by the operator according to the
respective operating conditions.
During servicing, above all, the parts on which
the explosion protection depend, (e.g.
intactness of the flameproof components, the
enclosure, the seals and cable entries), and the
switch mechanism function of the control
switch shall be checked.
If, in the course of servicing, it is ascertained,
that repairs are necessary, section 8 of these
operating instructions shall be observed.
Apparatus mounting plate for
channel- and wall mounting
Apparatus mounting plate for
channel- and wall mounting
Fastening
holes for
control unit
GHG 411 81
Apparatus mounting plate for pipe mounting
Apparatus mounting plate for
pipe mounting
Fastening holes for
control unit
GHG 411 82
Fastening holes for
control unit
GHG 411 83
E
Explosion-protected control units
GHG 411 and 412
17
F
Boites de commande GHG 411 et GHG 412
pour atmosphères explosives
Dimensions en mm
X = dimensions de fixation
1 Caractéristiques techniques
1.1 Boites de commande complete
ATEX Certificat de Conformité: PTB 00 ATEX 3117
Marquage selon 2014/34/UE et directive:
EN 60079-0
D II 2 G Ex e mb IIC T6 Gb
D II 2 G Ex e ib mb IIC T6 Gb
D II 2 G Ex d e mb IIC T6 Gb
D II 2 G Ex d e ib mb IIC T6 Gb
D II 2 D Ex tb IIIC T80 °C Db
IECEx Certificat de Conformité: IECEx BKI 04.0003
Marquage selon:
IEC60079-0 Ex e IIC T6
Ex e ib IIC T6
Ex d e IIC T6
Ex d e ib IIC T6
Tension nominale: jusqu’à 690 V
Courant nominal: 16 A au maxi
Température ambiante admissible:
D’autres températures possibles avec des modèles spéciaux.
-20° C à +40° C (modèles de liste)
Temp. de stockage dans l’emballage original:
-20° C à + 40° C
Indice de protection selon CEI/EN 60529: IP 66, (modèles de liste)
IP 65,
bouton-poussoir double
Classe d’isolation selon CEI/EN 61140:
I –
avec plaque métalique
II –
est remplie par les boites de bornes d'éclairage
Borne PE: 2 x 4 mm²
Bornes de connexion: voir Composants
Entrées de câble (modèles de liste): 1 x M25
câbles appropriés et couples d’essai de la vis de pression
Entrées de câble M12 M16 M20 M25 M32
Garniture 1+2+6
(Ø mm / Nm)
1 2
3
min.
max.
(1) (2)
--- ---
5,5 / 1,5
7,0 / 1,0
8,0 / 1,5
10,0 / 2,0
---
Garniture 1+2
(Ø mm / Nm)
1 2
3
min.
max.
(1) (2)
---
5,5 / 1,0
7,0 / 1,0
7,0 / 1,5
9,0 / 1,4
10,0 / 2,3
13,0 / 2,6
14,0 / 3,0
17,0 / 4,0
Garniture 1
(Ø mm / Nm)
1 2
3
min.
max.
(2)
5,0 / 0,8
7,0 / 1,0
7,0 / 1,0
10,0 / 1,4
9,5 / 1,0
13,0 / 1,7
13,5 / 1,3
17,5 /2,3
17,5 / 1,5
21,0 / 1,3
Couple d' essai pour l’entrée de câble (Nm) 1,2 3,3 2,7 3,0 5,0
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour la zone intermédiaire, veuillez utiliser la combinaison des bagues d'étanchéité 1 + 2 + 3.
(2)
Lors de la sélection des bagues d’étanchéité au moment de l’installation, il faut s’assurer qu’il reste une
marge de serrage suffisante au niveau du chapeau du presse étoupe. Cela permettra de pouvoir resserrer le
presse étoupe lors d’une future maintenance.
Poids:
Boite de commande GHG 411 81 (P411) env. 0,25 kg (Poids à vide)
Boite de commande GHG 411 82 (P412) env. 0,35 kg (Poids à vide)
Boite de commande GHG 411 83 (P413) env. 0,45 kg (Poids à vide)
Boite de commande GHG 412 82 (F412) env. 0,80 kg (incl. instrument de mesure)
Couples de serrage testés: Vis du couvercle 2,50 Nm
GHG 411 81
GHG 411 82
GHG 411 83
GHG 412 82
Gabarit de perçage pour GHG 412 82
ATEX Certificat de Conformité: IBExU14ATEX1030U
Marquage selon 2014/34/UE et directive:
EN 60079-0
D II 2 G
Ex d e IIC/IIB Gb
D I M 2
Ex d e I Mb
IECEx Certificat de Conformité: IECEx IBE 14.0005U
Marquage selon:
IEC60079-0 Ex d e IIC/IIB Gb
Ex d e I Mb
Température de fonctionnement:
II 2 G ... IIC
-45 °C à +80 °C
II 2 G ... IIB
-60 °C à +80 °C
1.2 Modules général
18
Dimensions des elements de commande
Tête de bouton-poussoir
Tête de double bouton-poussoir
Tête de bouton-poussoir à frapper
Tête de signalisation avec calotte
Tête de bouton-poussoir à frapper
"ARRET D'URGENCE"
Tête de bouton-poussoir à frapper
"ARRET D'URGENCE" avec clé
Tête de commutateur*- /
Tête de bouton-poussoir à clé 
* pour le moment, pas encore certifié Catégorie II D
F
Boites de commande GHG 411 et GHG 412
pour atmosphères explosives
Tension nominale: jusqu’à 500 V
Courant nominal
maxi
Borne de
connexion
Température ambiante
admissible maxi
14 A 2,5 mm² 40 °C
16 A 4,0 mm² rigide 40 °C
12 A 2,5 mm² 50 °C
15 A 4,0 mm² rigide 50 °C
Puissance de coupure AC15 (EN 60947-5-1): 250 V / 6 A 500 V / 4,0 A
Puissance de coupure DC13 (EN 60947-5-1): 24 V / 6 A 60 V / 0,8 A 110 V / 0,5 A
mit Goldspitzkontakten: 400 mA au maxi
Anschlussklemmen: 2 x 1,0 - 2,5 mm²;
1 x 4,0 mm² rigide
Couples de serrage testés bornes de connexion: 2,5 Nm
Poids: 2 pole env. 0,15 kg
4 pole env. 0,35 kg
1.2.1 Bouton-poussoir 2 pole et interrupteurer
1.2.2 Bouton-poussoir 4 pole et interrupteur
1.2.3 Potentiomètre
Tension nominale: jusqu’à 250 V
Puissance: 1 W
Domaine de rotation: 270°
Echelle: 0 - 100%
Borne de raccordement:
2 x 1,0 - 2,5 mm²; 1 x 4,0 mm² rigide
Couples de serrage testés bornes de connexion: 2,5 Nm
Poids: env. 0,15 kg
1.3 Lampe de signalisation
ATEX Certificat de Conformité: IBExU 12ATEX 1047 U
Marquage selon 2014/34/UE et directive:
EN 60079-0
D II 2 G
Ex de IIC/IIB Gb
D II 2 G
Ex d ia IIC/IIB Gb
IECEX Certificat de Conformité: IECEx IBE 13.0031U
Marquage selon:
IEC60079-0 Ex d e IIC/IIB Gb
Ex d ia IIC/IIB Gb
Température ambiante admissible:
D II 2 G Ex ... IIC
-45 °C à +60 °C
D II 2 G Ex ... IIB
-60 °C à +60 °C
(d’autres valeurs sont possibles avec des modèles spéciaux)
Bemessungsspannung/Bemessungsstrom:
"e" une sécurité accrue 20 V à 254 V AC/DC 4
à
15 mA
"i" version à sécurité intrinsèque 10 V à 30 V DC max. 25 mA
"e" une sécurité accrue 12 V à 24 V AC/DC max. 24 mA
Données de Ex-i: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Borne de connexion: 2 x 1,0 - 2,5 mm²; 1 x 4,0 mm² rigide
Couples de serrage testés bornes de connexion: 2,5 Nm
Poids: env. 0,15 kg
19
F
Boites de commande GHG 411 et GHG 412
pour atmosphères explosives
Dimensions des elements de commande
2
1
Tête d'instrument de mesure AM 45
Tête d'instrument de mesure AM 72
Tête de commutateur de commande
X = dimensions de fixation
Fig. 1
1.6 Circuit à sécurité intrinsèque
1.5 Bornier
1.4 Instrument de mesure AM45 / AM72;
Instrument de mesure VM45 / VM72
Attestation d’examen CE de type: BVS 14 ATEX E 125 U
Marquage selon 2014/34/UE et directive:
ferromagnétique
D II 2 G
Ex e IIC Gb
D II 2 G
Ex e mb IIC Gb
magnéto-électrique
D II 2 G
Ex ib IIC Gb
IECEx Certificat de Conformité: IECEx BVS 14.0082U
Marquage selon:
ferromagnétique Ex e IIC Gb
Ex e mb IIC Gb
magnéto-électrique
Ex ib IIC Gb
Température de fonctionnement: -55 °C et +55 °C
Tension nominale: 500 V au maxi
ferromagnétique magnéto-électrique
Justesse: Classe 2,5 Classe 1,5
Gamme de surcharge:
fois à sec. fois à sec.
fois à sec.
fois à sec.
indicatif
Etendue de mesure:
direkt
Consommaton d’énergie:
Coil: tours
Résistance interne:
Li:
Ci:
Ui:
Ii:
Borne de raccordement: fine / brin
rigide
Couples de serrage testés bornes de connexion:
Poids AM/VM 45
AM/VM 72
EN 60079-0
IEC 60079-0
10 - - 25 10 - - 5
25 - - 4
50 - - 1
1:1,5
AM: n / 1A 0 - 24 mA
0 - 25 A 4 - 24 mA
VM45: 6 - 415 V
VM72: 6 - 660 V
VM45:
0,91 - 1,76 VA
VM72:
0,91 - 2,65 VA
26,5
2,5 Ohm +- 30%
-
max. 0,1 mH
-
max. 0,1 nF
-
max. 30 V
-
max. 150 mA
2 x 0,5 - 2,5 mm²
1 x 4,0 mm²
2,5 Nm
env. 0,35 Kg
env. 0,40 Kg
Tension maximale pour sécurité technique U
m
: 690 V
eff
isolation galvanique de tous les autres circuits
à sécurité intrinsèque et de la terre
ATEX Certificat: SEV 13 ATEX 0178 U
Marquage selon 2014/34/UE et directive:
EN 60079-0
II 2 G
Ex eb IIC
IECEx Certificat: IECEx SEV 13.0012 U
Marquage selon: IEC60079-0 Ex eb IIC
Type de borne: 6 x MUT 4
Tension nominale: jusqu’à 352 V
Section transversale du conducteur: 2 x 0,2 - 4,0 mm²
Couples de serrage testés bornes de connexion: 0,6 - 0,8 Nm
Poids: env. 0,08 kg
20
2 Consignes de sécurité
a
Groupe cible:
Électriciens et personnel qualifiés
en conformité avec la législation et
les standards nationaux et, si applicable, en
conformité avec CEI/EN 60079-14 sur les ins-
tallations électriques pour les atmosphères
explosives.
Les boites de commande GHG 411 et
GHG 412 ne conviennent pas à un emploi en
zone 0 et zone 20.
Le groupe d’explosion et la classe de
température marqués sur les appareils
devront être respectés.
Il n’est pas permis de transformer ou de
modifier les boites de commande.
Seuls des boites de commande intactes et
parfaites devront être employées pour la
fonction qui leur est dévolue.
Les exigences des CEI/EN 60079-31 en
ce qui concerne des dépôts de poussière
démesurés et une température doivent être
considérées par I’utilisateur.
Seules des pièces de rechange homologuées
d’origine CEAG devront être utilisées
comme remplacement et pour des répa-
ra-tions.
Des réparations qui portent sur la protection
contre l’explosion, ne devront être exécutées
que par CEAG ou par un électricien qualifié
en conformité avec la règlementation
nationale en vigueur.
Avant la mise en service, les boites de
commande doivent être vérifiées selon
l’instruction donnée dans la section 6.
Respectez les prescriptions nationales de
sécurité et de prévoyance contre les
accidents ainsi que les consignes de sécurité
figurant en italique dans ce mode d’emploi.
3 Conformité avec les normes
Les Appareils sont conformes aux normes
reprises dans la déclaration de conformité,
jointe séparément.
Les références aux normes et directives dans
cette notice se réfèrent toujours à la dernière
version. Les suppléments éventuels doivent
également être respectés.
4 Domaine d’utilisation
Ces boites de commande comportant les
composants décrits dans le chapitre Caractéris-
tiques techniques répondent aux exigences
d’une utilisation en atmosphère explosible,
zones 1, 2 ainsi que l’emploi en zones 21 et 22
selon la norme CEI/EN 60079-10-1 et
CEI/EN 60079-10-2.
Pour l’enveloppe, et les pièces métalliques
extérieures, des matières de qualité supérieure
(polyamide anti-choc) qui assurent une
protection appropriée contre la corrosion et une
résistance aux agents chimiques en ”atmos-
phère normale” ont été employées :
-polyamide anti-choc
-acier spécial AISI 316 L
En cas d‘utilisation en atmosphère extrème-
ment corrosive, vous pouvez obtenir des
informations complémentaires sur la résistance
chimique des plastiques utilisés chez la
succursale Cooper Crouse-Hinds de votre
région.
5 Utilisation / Propriétés
Les boites de commande GHG 411 et GHG 412
servent à la commande sur place d’installations
électriques en atmosphère explosive.
Dépendant de l’emploi spécifique et suivant le
cas, les appareils sont dotés des composants
encastrés appropriés.
Des modèles spéciaux de boites de commande
conçus sur demande peuvent être employés
dans des circuits à sécurité intrinsèque.
Dans ce cas, les valeurs électriques limites
de la sécurité intrinsèque sont à respecter.
Le modèle à pointes de contact or est employé
pour la coupure de valeurs de tension peu
élevées. La tension maximale admise doit être
observée (voir page 17, Caractéristiques
techniques). Ce modèle est reconnaissable au
marquage ”G” sur le socle.
Afin d’obtenir une déconnexion fiable, des
contacts de rupture forcée ont été montés
comme contacts normaux.
Suivant le cas, les socles sont aussi dotés de
résistances de 0,6 W, de fusibles pour faible
intensité et des diodes (puissance dissipée de
1 W maxi).
L’instrument de mesure AM/VM72 et AM/VM45
sert à l’indication sur place des grandeurs
électriques. Le type du mécanisme de mesure,
la justesse et le type de raccordement sont indi-
qués dans les caractéristiques techniques.
En cas d’instruments de mesure pour
connexion au transformateur d’intensité n/1A
(fig. 1, pos. 2), un volet disposé sur la partie
supérieure de l’instrument de mesure permet
d’échanger les cadrans interchangeables (fig. 1,
pos. 1).
Si le collet de commutation des manipulateurs
est découpé à la position de verrouillage
respective, il est possible de les cadenasser
dans cette position (Ø de l’étrier jusqu’à 5 mm).
F
Boites de commande GHG 411 et GHG 412
pour atmosphères explosives
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual
Ce manuel convient également à

dans d''autres langues