Eaton Crouse-hinds series Operating Instructions Manual

Catégorie
Batteries rechargeables
Taper
Operating Instructions Manual

Ce manuel convient également à

Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
Explosion protected LED-exit luminaire
Series: EXIT N
Bloc autonome d’éclairage de sécurité (LED)
pour atmospres explosives Série: EXIT N
Betriebsanleitung
Operating instructions
Mode d’emploi
CROUSE-HINDS
SERIES
300 8000 2035 D/GB/F (j)
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
2
Wichtige Hinweise
zur Handhabung der Batterie
D
B3.2 Laden während des Betriebes
Der Ladestrom ist bei ordnungsgemäßem
Betrieb der Leuchte so bemessen, dass bei
entladener Batterie innerhalb von 14 h ca. 90 %
und innerhalb von 20 h ca. 100 % der Nenn-
kapazität erreicht werden.
Der Tiefentladeschutz mit Wiedereinschaltsperre
überwacht bei Netzausfall die Batteriespannung
und verhindert die Tiefentladung der Zellen.
Die sich durch Selbstentladung im Normalbe-
trieb reduzierende Batteriekapazität wird, durch
den Mikroprozessor kontrolliert und nachgeladen.
Eine ein- bis zweimalige vollständige Entladung
(Notlichtbetrieb bis zum Erlöschen der
Notlichtlampe) pro Jahr, erhöht die nutzbare
Lebens dauer der Batterie und wird dringend
empfohlen!
Sollte dies aus Sicherheitsgründen nicht möglich
sein, empfehlen wir eine Teilentladung von
mindes tens 40 min bzw. 2 h.
B3.3 Laden nach Lagerung
Nach längerer Lagerung empfiehlt sich eine
erste ununterbrochene Ladung für 20 h, danach
eine Entladung bis zum Ansprechen des
Tiefentladeschutzes (Notlichtlampe verlischt),
und anschließend ein erneutes Laden für
mindestens 14 h.
Zeigt die Kapazitätsanzeige keine 5 grüne LEDs
in Dauerlicht an, sollte der Vorgang wiederholt
werden.
Um nach längerer Lagerung die volle Batterieka-
pazität zu erreichen wird empfohlen, mindestens
3 Lade-/Entladezyklen durchzuführen.
B3. Laden
B3.1 Erstmaliges Laden
Nach Anlegen der Netzspannung gemäß
Schaltplan der Betriebsanleitung der Leuchte
wird die Batterie geladen. Bei Anschluss einer
neuen Batterie kann sich die Ladezustandsanzei-
ge (erste blinkende grüne LED) um einige
Minuten verzögern.
Die Batterie hat nach 14 Stunden Ladezeit
ca. 90 % ihrer Nennkapazität erreicht.
Durch eine Überdimensionierung der Batte-
rie-Kapazität erreicht eine neue Batterie auch mit
diesen 90 % Nennkapazität die eingestellte
Notlicht-Nennbetriebsdauervon 90 min bzw.
180 min.
Bei einer Umgebungstemperatur von ca. 0 °C
benötigt die Erstladung der Batterie in etwa die
doppelte Zeit gegenüber einer Ladung bei über
10 °C.
Bei der Erstinbetriebnahme empfiehlt sich eine
ununterbrochene Ladezeit von 20 h. Hierdurch
wird eine vorzeitige Alterung der Batterie
vermieden.
Der Batteriesatz ist im Auslieferungszustand
nicht vollständig geladen.
Mehrfaches Ein- und Ausschalten der Ver-
sorgungsspannung vor einer ersten vollstän-
digen Ladung der Batterie (empfohlen 20 h,
jedoch mindestens 14 h) kann die Lebens-
dauer der Batterie erheblich reduzieren.
Empfehlung: Bei neuen Batterien wird die
gesamte nutzbare Batteriekapazität erst nach
ca. 3 Lade-/Entladezyklen erreicht.
B1. Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und qualifizierte Personen
gemäß den nationalen Rechtsvorschriften
einschließlich der einschlägigen Normen für
elektrische Geräte in explosionsgefährdeten
Bereichen (EN/IEC 60079-17).
Die Batterie darf nicht in der Zone 0/
Zone 20 verwendet werden!
B2. Informationen zur Ladetechnik
Mit der durch einen Mikrocomputer gesteuerten
Ladetechnik wird der Lade- und Entladestrom
erfasst, aufbereitet und einem Kapazitätszähler
zugeführt. Fünf grüne Leuchtdioden zeigen in
20%-Schritten den jeweiligen Ladezustand der
Batterie an.
Eine Überladung wird durch diese kapazitätsab-
hängige Ladesteuerung vermieden. Nur die
entnommene Energie wird nachgeladen. Auch
der sogenannte Memory-Effekt der Batterie wird
hierbei vermieden.
Das Laden und die Kapazität der Batterie werden
aus elektrochemischen Gründen durch die
Umgebungstemperatur beeinflusst.
Bei Temperaturen unter +5 °C und über +35 °C
verzögert sich der Ladevorgang entsprechend
und es wird nicht sichergestellt, dass die
Batterie vollständig aufgeladen wird.
3
Important notes
for battery handling
GB
B3.2 Charging during operation
The charging current is engineered in such a way
that a discharged battery will have within 14 h
approx. 90 % and within 20 h approx. 100 % of
its capacity.
In emergency operation the battery voltage is
monitored via a deep discharge protection which
prevents a deep discharge of the cells.
The microprocessor controls and recharges any
reduction of capacity due to self-discharge in
normal operation.
It is recommended to have one or two fully
discharges per year. This increases the usable life
time of the battery.
Should this not be possible due to logistic and
safety reasons at least a partial discharge of a
minimum of 40 minutes or 2 hours depending on
the setting, is recommended.
B3.3 Charging after storage
After a long storage of the batteries a full
uninterrupted charge for 20 h should be applied
followed by a full discharge down to deep
discharge protection (emergency lamp off).
If the capacity indication does not show 5 green
LEDs fully lit after 14 h, the above process
should be repeated. For a storage period > 6
months it is recommended to have 3 charging/
discharging cycles.
B3. Charging
B3.1 Initial Charging
Battery charging starts when the power is
switched on. On the connection of a new battery
the indication of the charge state may be delayed
by a few minutes. The first green LED might take
a few minutes to start flashing.
After a charging period of 14 hours the battery
will have reached approx. 90 % of its rated
capacity. As the capacity of the battery is over
specified, this 90 % will be sufficient to provide
a rated discharge for both a 90 minute and
180 minute setting.
Initial charging at 0 °C ambient temperature
might take double the time than at tempera-
tures of >10 °C.
After first mains connection an uninterrupted
charging time of 20 hours is recommended to
avoid early ageing due to power-on power-off
situations. The battery set is only partially
charged when supplied.
Multiple switching (on - off) of the mains
circuit should be avoided before a first initial
charge (recommended 20h, minimum 14h) is
achieved. Such interruptions can significantly
reduce the lifetime of the battery.
Recommendation: New batteries will reach the
full utilisable capacity after approx. 3 charging /
discharging cycles.
B1. Safety instructions
Target group:
For skilled electricians and qualified
personnel in accordance with national
legislation, including the relevant standards
and, where applicable, in acc. with
IEC/EN 60079-17 on electrical apparatus for
explosive atmospheres.
The battery must not be operated in zone 0
or zone 20 hazardous areas!
B2. General information about
the charging technology
The microcomputer controlled charging system
measures the charging and discharging current
and transmits it to a capacity meter. Five green
light emitting diodes indicate in 20%-steps the
actual charge state of the battery.
Overcharging is prevented by means of this
charging control dependent on the capacity.
Only the energy drawn is recharged. The
so-called memory effect is thus also prevented.
For electrochemical reasons charging and the
capacity are influenced at temperatures below
+5 °C and above +35 °C.
At temperatures below +5 °C and above +35 °C
charging will take a longer time and full charging
is not guaranteed.
4
Remarques importantes
pour l’utilisation de la batterie
B3.2 Chargement pendant l´utilisation
Le courant de chargement est calculé de telle
manière qu´une batterie déchargée mettra
environ 14 h pour atteindre 90 % de sa capacité
et 20 h pour atteindre les 100 %.
En cas d´urgence la tension de la batterie est
surveillée par une protection décharge profonde
qui empêche les cellules de se décharger
complètement.
Le microprocesseur contrôle et comble les
réductions de capacité de la batterie par
auto-décharge en fonctionnement normal.
Il est recommandé de procéder à un ou deux
déchargements complets par an. La durée de
vie de la batterie s´en trouve agrandie.
Si cela est impossible pour des raisons de
logistique et de sécurité, alors il est recomman-
dé de procéder à un déchargement d´au moins
40 minutes à 2 heures.
B3.3 Chargement après stockage
Suite à une longue période de stockage des
batteries il convient de les charger en continu
pendant 20 heures avant de procéder à un
déchargement complet jusqu´au niveau de
protection décharge profonde (voyant urgence
éteint), puis de les recharger pendant au moins
14 heures.
Si les 5 voyants verts de capacité ne restent pas
allumés en permanence, alors il faut recommen-
cer le processus depuis le début.
Afin d´obtenir le total de capacité de la batterie
après une longue période de stockage
(> 6 mois), il faut réaliser au moins 3 cycles de
chargement / déchargement.
B3. Chargement
B3.1 Chargement initial
Le chargement de la batterie commence lorsque
le chargeur est mis sous tension. Lors de la
connexion d´une batterie neuve, l´indication de
chargement (première diode verte clignotante
LED) peut ne commencer qu´après plusieurs
minutes.
Après un chargement de 14 heures la batterie
aura atteint environ 90 % de sa capacité
nominale. La capacité de la batterie étant sur
dimensionnée, ces 90 % suffisent pour produire
un temps de décharge de 90 minutes, voire 180
minutes.
Un chargement initial par une température
ambiante de 0 °C peut prendre le double du
temps d´un chargement par >10 °C.
Lors de la première mise en service un temps
ininterrompu de chargement de 20 heures est
recommandé pour éviter un vieillissement
prématuré de la batterie dû à des mises sous et
hors tension fréquentes.
Les mises sous et hors tension fréquentes
doivent être évitées avant le chargement
initial complet (20h recommandées, 14h
minimum) pour éviter un vieillissement
prématuré de la batterie.
Recommandation : les batteries neuves
atteindront leur capacité maximale utilisable
après environ 3 cycles complets de charge-
ment / déchargement.
B1. Consignes de sécurité
Groupe cible:
Électriciens et personnel qualifiés en
conformité avec la législation et les standards
nationaux et, si applicable, en conformité
avec CEI/EN 60079-17 sur les installations
électriques pour les atmosphères explosives.
La batterie ne doit pas être utilisée en zones 0
ou 20!
B2. Information sur la technique de
chargement.
Le système de chargement contrôlé à partir d´un
micro-ordinateur mesure le courant de charge et
de décharge et le transmet à un compteur. Cinq
diodes vertes de 20% chacune montrent le taux
de chargement de la batterie.
Une surcharge est évitée car le contrôle de
charge est dépendant de la capacité. Seule
l´énergie retirée est remplacée. Ainsi, l´effet
mémoire de la batterie est également évitée.
Pour des raisons électrochimiques le charge-
ment et la capacité de la batterie sont influencés
par la température atmosphérique.
À des températures inférieures à +5 °C et
supérieures à +35 °C le chargement ralentit en
conséquence et un chargement complet ne peut
plus être garanti.
F
5
Maßbilder/Dimensional drawings/Dimensions
Bild 1/
fig. 1/
Fig.1
Befestigungsschrauben/
Fixing screws/
vis de fixation
Ø 5 mm
Bild 2 Netzanschluss/
fig. 2 Mains connection/
Fig. 2 schéma des connexions
PE
N
L
Batterie/
Battery/
Batterie
1
6
Bild 4 /
fig.4 /
Fig.4
Dauerlicht => ON
Permanent lighting
lumière permanente
Bereitschaftsleuchte => OFF
Emergency lights
luminaire d´urgence
Bild 3 Ladezustandsanzeige/
fig. 3 charging condition disply/
Fig.3 Affichage de l'état de
charge et de capacité
Kapazität/Capacity/Capacité
> 40 % < 60 %
Ladebetrieb/ Notlichtbetrieb/
Charging operation/ Emergency op./
Batterie charge Fonctionnement
d’éclairage de secours
 aus/off/
 an/on/allumée
 blinkend/flashing/clignotant
100 %
80 %
60 %
40 %
20 %
Batterie/
Battery/
Batterie
1. rote/red/rouge
LED
2.- 6. grüne/green/
verte LEDs
7. gelbe/yellow/
jaune LED
Anzeigedisplay/
indicator display/
rangée de LED’s
}
1
2
2
OFF
ON
Bild 5 Batteriewechsel/
fig.5 battery change/
Fig.5 changement de batterie
1 Nm
1 Nm
7
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
D
EU-Baumusterprüfbescheinigung: BVS 09 ATEX E 029
Gerätekennzeichnung nach 2014/34/EU / und der Normenreihe
EN 60079: ta max + 40 °C:
II 2 G
Ex eb ib mb IIC T5 Gb
ta max + 50 °C:
II 2 G
Ex eb ib mb IIC T4 Gb
II 2 D
Ex tb IIIC T80°C Db
IECEx Konformitätsbescheinigung: IECEx BVS 13.0017
Gerätekenzeichnung nach der Normenreihe:
IEC 60079: ta max + 40 °C: Ex eb ib mb IIC T5 Gb
ta max + 50 °C: Ex eb ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Bemessungsspannung AC: 110 - 277 V *
DC: 110 - 250 V *
*die Angaben berücksichtigen eine zusätzliche Spannungstoleranz von ± 10%
Bemessungsfrequenz: 50 - 60 Hz
Bemessungsstrom 110 V AC/DC: ca. 0,06 A
220 V AC/DC: ca. 0,035 A
Batterie: Akku 2 x 6 V / 0,8 Ah
Ladezeit (Kap. > 90 %): 28 h
Nennbetriebsdauer Notlichtbetrieb: 3 h **
**Hinweis: Bei neuen Batterien wird die gesamte nutzbare Batteriekapazität erst nach ca. 3 Lade/Entladezyclen erreicht!
Schutzklasse nach EN/IEC 61140: I
Schutzart nach EN/IEC 60529: IP 66
Zulässige Umgebungstemperatur: -20 °C ... +40 °C / +50 °C
datenhaltig: +5 °C ... +35 °C
Lagertemperatur in Originalverpackung: -20 °C ... +50 °C
Gewicht mit Batterie ca. 2,5 kg
Klemmvermögen Anschlussklemme
2x je Klemme: 3 x 2,5 mm²
Ex e / Ex t Kabel- und Leitungseinführung M20x1,5
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø Leitung (mm) Nm
Dichtung 1+2+3
1 2
3
min. 5,5 1,5
max.
(1)
7, 0 1,0
Dichtung 1+2
1 2
3
min. 7, 0 1,5
max.
(1))
9,0 1,4
Dichtung 1
1 2
3
min. 9,5 1,0
max.
(1)
13,0 1,7
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann der
Klemmbereich variieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus Dichtungen, so
dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
Metall: M20x1,5 Gewinde
Prüfdrehmoment Einschraubgewinde für
Ex e / Ex t Kabel- und Leitungseinführung
M20x1,5:
2,7 Nm
Prüfdrehmoment für Befestigungsschrauben
Haube:
2,4 Nm
1. Legende
Warnung
Dieses Symbol warnt von einer ernsten
Gefahr. Diese Warnung nicht zu beobachten
kann Tod oder die Zerstörung von Einrich-
tungen zur Folge haben.
Achtung
Dieses Symbol warnt von einem möglichen
Ausfall. Wird diese Warnung nicht beobach-
tet kann den Gesamtausfall der Vorrichtung
oder des Systems oder des Betriebes
erfolgen, an die es angeschlossen wird.
1.1 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und qualifizierte
Personen gemäß den nationalen
Rechtsvorschriften, einschließlich der
einschlägigen Normen für elektrische
Geräte in explosionsgefährdeten Bereichen
(EN/IEC 60079-14).
Die Leuchte darf nicht in der Zone 0 oder
20 eingesetzt werden!
Die auf der Leuchte angegebenen
technischen Daten sind zu beachten!
Die Anforderungen der EN/IEC 60079-31
u.a. in Bezug auf übermäßige Staub-
ablagerungen und Temperatur, sind vom
Anwender zu beachten
Umbauten oder Veränderungen an der
Leuchte sind nicht zulässig!
Die Leuchte ist bestimmungsgemäß in
unbe schädigtem und einwandfreiem
Zustand zu betreiben!
Diese Betriebsanleitung während des
Betriebes nicht in der Leuchte lassen!
Die nationalen Unfallverhütungs- und
Sicherheitsvorschriften und die nachfolgen-
den Sicherheitshinweise, die in dieser
Betriebsanleitung mit einem ( ) gekenn-
zeichnet sind, beachten!
2. Technische Daten
8
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
D
Bei Metall-Kabeleinführungen sind die
Schutzkappen der nicht benutzten Einführun-
gen zu entfernen und durch bescheinigte
Ex-Verschlussstopfen (min. IP66) zu verschließen!
Achtung!
Nur festverlegte Leitungen zulässig! Bei
Verwendung anderer Leitungseinführungen
sind die Angaben des Herstellers hinsichtlich
Klemmvermögen und Zugentlastung zu
beachten!
Klemmen Sie die Leitungen L, N und PE am
Klemmstein sicher an (Bild 2).
Achten Sie auf sichere Lage der Leitungen.
Quetschen Sie keine Leitungen!
Die Schaltungsart kann über einen kleinen
Schalter auf der Platine eingestellt werden. Siehe
hierzu "Schaltungsart".
Montieren Sie die Haube mit den vier Schrauben
(Prüfdrehmoment 2,4 Nm).
5. Funktion
5.1 Anzeigedisplay
Die in der Leuchte eingebaute Notlichtversor-
gungseinheit ist mit einem Mikrocomputer zur
Ladung und Überwachung sowie mit einer aus
7Leuchtdioden bestehendem Anzeigedisplay
ausgestattet. Die fünf grünen LEDs zeigen den
Lade- und Kapazitätszustand der Batterie an. Die
rote LED signalisiert mögliche Störquellen, die
gelbe LED signalisiert den Notlichtbetrieb. (Bild 3)
Siehe hierzu auch: LED-Anzeigezustände
5.2 Schaltungsart
Bedingt durch die Lichtleistung der LED-Licht-
quellen werden damit ausgerüstete Leuchten
fast ausschließlich als Rettungszeichenleuchten
eingesetzt.
Nachdem die Haube abgenommen wurde,
können über einen kleinen Schalter auf der
Platine"Bild 4" zwei Betriebszustände ausgewählt
werden:
Schaltungsart "Dauerlicht"
Schalterstellung "ON", Auslieferungszustand.
Die Leuchte leuchtet im Normal- und im
Notlichtbetrieb.
Schaltungsart "Bereitschaftsleuchte"
Bild 4
Schalter auf der LED Seite.
Schalterstellung "OFF"
Die weißen LEDs sind im Normalbetrieb aus.
Ladezustand und mögliche Störquellen werden
angezeigt.
Bei einem Netzausfall werden die weißen LEDs
eingeschaltet. Die gelbe LED zeigt den Notlichtbe-
trieb an.
Der wöchentliche Funktionstest und der
Teilbetriebsdauertest alle 3 Monate, werden
in der Stellung "OFF" unterdrückt.
3. Normenkonformität
Diese Leuchte ist zum Einsatz in explosionsge-
fährdeten Be rei chen der Zone 1, 2, und 21, 22
gemäß EN/IEC 60079-10-1 und
EN/IEC 60079-10-2 geeignet.
Diese Leuchte entspricht den aufgeführten
Normen, in der separat beigelegten Konformi-
tätserklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4. Installation EXIT N
Die für das Errichten und Betreiben von
explosionsgeschützten elektrischen Betriebs -
mitteln geltenden Sicherheitsvorschriften
gemäß des Geräte- und Produktsicherheits-
gesetzes sowie die allgemein anerkannten
Regeln der Technik sind einzuhalten
(EN/IEC 60079-14)!
Transport und Lagerung der Leuchte ist nur in
Originalverpackung und der angegebenen
Lage gestattet!
4.1 Öffnen und Schließen der Leuchte
- Lösen sie die vier Deckelschrauben
(Schlitz SW4 mm).
- Die Haube kann an den angespritzten
Scharnieren aufgeklappt werden. Zur
leichteren Montage kann die Haube aus den
Scharnieren ausgehängt werden. Beim
Ablegen der Haube auf glatte und saubere
Unterlage achten, damit der Siebdruck auf
der Haube nicht verkratzt wird
4.2 Montage der Leuchte
Warnung - Gefahr durch elektrostatische
Entladung!
Die Leuchte darf nicht in der Nähe von
ladungserzeugenden Prozessen installiert
werden.
Die Leuchte ist an den vier Befestigungspunkte
mit geeigneten Befestigungsschrauben
(Schraube Ø max. 5 mm, Bild 1) sicher auf
tragfähigem Untergrund anzuschrauben.
4.3 Netzanschluss
Der elektrische Anschluss des Betriebsmittels
darf nur durch eine Elektrofachkraft gem.
EN/IEC 60079-14 erfolgen.
Haube wie beschrieben öffnen.
Führen Sie die Netzzuleitung durch die bescheinig-
te Ex e / Ex t Kabel -Leitungseinführung M20x1,5
ein.
Für Leitungen von
Ø 5,5 bis 7,0 mm Dichtungsein sätze 1,2 und 3,
von Ø 7,0 bis 9,0 mm Dichtungsein sätze 1 und 2 und
von Ø 9,5 bis 13,0 mm Dichtungsein satz 1 verwenden.
Achten Sie auf korrekten Sitz des verbleibenden
Dichtungseinsatzes in der Verschraubung.
Bei nicht benutzten Kabel-und Leitungs-
einführungen ist die Schutzscheibe zu
entfernen und durch einen bescheinigten
Verschlussstopfen (Drehmoment 2,7 Nm) zu
verschließen.
Beim Verschließen mit einem Verschlussstop-
fen die Dichtungseinsätze 1 und 2 verwenden!
5.3 Ladetechnik
Mit der durch einen Mikrocomputer gesteuerten
Ladetechnik wird der Lade- und Entladestrom
erfasst, auf bereitet und einem Kapazitätszähler
zugeführt. Fünf grüne Leuchtdioden zeigen in
20%-Schritten den jeweiligen Ladezustand der
Batterie an, siehe Bild 3.
Bei Temperaturen unter +5 °C und über +35 °C
ist aus elektrochemischen Gründen nicht
sichergestellt, dass die Batterie voll aufgeladen
wird.
Beim Ladevorgang zeigt die führende, blinkende
LED die bis zu diesem Zeitpunkt eingeladene
Kapazität an. Die LEDs der bereits eingeladenen
Kapazität zeigen Dauer licht an (Bild 3). Der
Ladevorgang ist beendet, wenn alle 5 grünen
LEDs leuchten und keine mehr blinkt.
Die LED-Anzeige berücksichtigt den Kapazi-
täts-Rückgang der Batterie: d.h., geht z.B. die
Anzeige über die 3. grüne LED auch nach
längerer Ladezeit nicht hinaus, so liegt die
verfügbare Kapazität zwischen 40 und 60 %.
Diese Anzeige wird bei jedem Notlichtbetrieb bis
zur Abschaltung durch den Tiefentladeschutz der
Batterie wieder aktualisiert.
5.4 Automatische Testfunktion
5.4.1 Funktionstest (FT)
Wöchentlich wird automatisch ein
Funktionstest (FT) durchgeführt.
5.4.2 Teil-Betriebsdauertest (TBT)
Alle 3 Monate wird automatisch ein
Teilbetriebsdauertest durchgeführt.
Falls innerhalb der letzten 3 Monate kein
Notlichtbetrieb >30 min. stattgefunden hat.
Hierbei erfolgt für ca 35 min. Notlichtbetrieb.
Die sich durch Selbstentladung im Normalbetrieb
reduzierende Batteriekapazität wird, durch den
Mikroprozessor gesteuert, nachgeladen.
5.5 Notlichtbetrieb
Notlichtbetrieb wird automatisch durch den
FT+TBT, durch Netzausfall oder manuell durch
Abschalten der Netzspannung eingeleitet.
Hierbei wird die gelbe LED im Anzeigedisplay
aktiviert.
Die zur Verfügung stehende Restkapazität wird
durch die 5 grünen Leuchtdioden angezeigt,
siehe Bild 3.
6. Inbetriebnahme
Vor der Inbetriebnahme die korrekte
Funktion und Installation der Leuchte in
Übereinstimmung mit dieser Betriebs anlei-
tung und anderen zutreffenden Bestimmun-
gen überprüfen!
Isolationsmessungen nur zwischen PE und
Außenleiter L sowie zwischen PE und N
durchführen!
– Messspannung: max. 1kV AC/DC
– Messstrom: max. 10 mA
Achtung: Eine Isolationsmessung
zwischen L und N darf nicht durchgeführt
werden, da sonst die Elektronik oder die
Netzein gangs sicherung im Gerät) zerstört wird.
9
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
D
7. Instandhaltung
Die für die Instandhaltung, Wartung und
Prüfung von explosionsgeschützten Betriebs-
mitteln geltenden Bestimmungen
(z.B. EN/IEC 60079-17) sind einzuhalten!
7.1 Batteriewechsel
Siehe Bild 5.
Sollte die Batteriekapazität durch Alterung der
Batterie nicht mehr ausreichend sein, muss die
Batterie ersetzt werden.
Nur zugelassene CEAG/CCH Originaler-
satzteile verwenden (siehe CEAG/CCH
Ersatzteilliste).
Leuchte spannungsfrei schalten!
Sicherstellen, dass beim Öffnen der
Geräte keine explosive Umgebungsatmo-
sphäre vorhanden ist
Leuchte öffnen.
Steckverbindung zwischen Batterie und
Platine trennen.
Befestigungsschrauben der Batterie lösen
und entfernen.
Einbau der neuen Batterie in umgekehrter
Reihenfolge.
8. Wartung
Im Rahmen der Wartung sind vor allem die Teile,
von denen die Zündschutzart abhängt, zu prüfen
z. B.:
- Gehäuse und Schutzwannen auf Risse und
Beschädigungen.
- Dichtungen auf Beschädigungen.
- Klemmen und Verschluss-Stopfen auf festen
Sitz.
- Wegen der Gefahr elektrostatischer
Aufladung darf die Leuchte nur mit einem
feuchten, nicht fasernden Tuch oder
Schwamm gereinigt werden! Dazu nur
übliche Haushaltsspülmittel in vorgeschrie-
bener Verdünnung mit Wasser benutzen! Die
Wassertemperatur darf maximal 50°C
betragen. Anschließend mit klarem Wasser
nachspülen, da sonst Spannungsrisse in der
Schutzwanne entstehen können!
9. Instandsetzung/ Reparaturen
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CEAG/CCH oder
einer qualifizierten Elektrofachkraft in
Übereinstimmung mit national geltenden
Regeln durchgeführt werden
(EN/IEC 60079-19).
Vor dem Austausch oder der Demontage von
Einzelteilen ist folgendes zu beachten:
Das Betriebsmittel vor dem Öffnen oder
vor Instandhaltungsarbeiten erst spannungs-
frei schalten!
Sicherstellen, dass beim Öffnen der
Geräte keine explosive Umgebungsatmo-
sphäre vorhanden ist
Nur zugelassene CEAG/CCH Originalersatz-
teile verwenden (siehe CEAG/CCH Ersatzteillis-
te).
10 Entsorgung /
Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die
jeweils geltenden nationalen Abfallbeseitigungs-
vorschriften zu beachten.
Zusätzliche Informationen zur Entsorgung des
Produktes können Sie bei Ihrer zuständigen
Cooper Crouse-Hinds / EATON Niederlassung
erfragen.
Programmänderungen und -ergänzungen sind
vorbehalten.
10
Explosion protected LED-exit luminaire
Series: EXIT N
GB
1. Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.
1.1 Safety instructions
For skilled electricians and
qualified personnel in accordance
with national legislation, including
the relevant standards and, where
applicable, in acc. with
IEC/EN 60079-14 on electrical apparatus for
explosive atmospheres.
The light fitting must not be operated in
zone 0 or 20 hazardous areas!
The technical data indicated on the light
fitting are to be observed!
The requirements of the
EN/IEC 60079-31 regarding excessive
dust deposits and temperature to be
considered from the user.
Changes of the design and modifications
to the light fitting are not permitted!
The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an ( ) in these operating
instruction, will have to be observed!
2. Technical data
EU-Type Examination Certificate: BVS 09 ATEX E 029
Marking acc. to 2014/34/EU and and standard of series
EN 60079 ta max + 40 °C:
II 2 G
Ex eb ib mb IIC T5 Gb
ta max + 50 °C:
II 2 G
Ex eb ib mb IIC T4 Gb
II 2 D
Ex tb IIIC T80 °C Db
IECEx Certificate of Conformity: IECEx BVS 13.0017
Category of application standard of series
IEC 60079 ta max + 40 °C: Ex eb ib mb IIC T5 Gb
ta max + 50 °C: Ex eb ib mb IIC T4 Gb
Ex tb IIIC T80 °C Db
Rated voltage: AC: 110 - 277 V *
DC: 110 - 250 V *
* the data consider an additional voltage tolerance of ± 10 %
Rated frequency: 50 - 60 Hz
Rated current: 110 V AC/DC: approx. 0.06 A
220 V AC/DC: approx. 0.035 A
Battery: Accu 2 x 6 V/ 0.8 Ah
Charging time: 28 h
Duration of emergency lighting: 3 h **
** Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles
Insulation class to IEC/EN 61140: I
Degree of protection accd. IEC/EN 60529: IP 66
Operation temperature: -20 °C ... +40 °C /+50 °C
specified data: +5 °C ... +35 °C
Storage temperature in original packing: -20 °C ... +50 °C
Weight: approx. 2.5 kg
Supply terminal clamping capacity
2x per terminal: 3 x 2.5 mm²
Ex e / Ex t cable entry M20x1.5
suitable
c
ables and test torques of the pressure screw Ø cable (mm) Nm
Seal 1+2+3:
1 2
3
min. 5.5 1. 5
max.
(1))
7. 0 1. 0
Seal 1+2:
1 2
3
min. 7. 0 1. 5
max.
(1)
9.0 1. 4
Seal 1
1 2
3
min. 9.5 1. 0
max.
(1)
13.0 1. 7
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
metal: M20x1.5 thread
Test torque flange for Ex e / Ex t cable entry
M20x1.5:
2.7 Nm
Test torque for mounting screws cover: 2.4 Nm
11
Explosion protected LED-exit luminaire
Series: EXIT N
GB
3. Conformity with standards
The luminaire is suitable for use in zone 1, 2
and 21, 22 hazardous areas acc. to
EN/IEC 60079-10-1 and EN/IEC 60079-10-2.
The luminaire is conform to the standards
specified in the Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4. Installation EXIT
The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have to be
observed (IEC/EN 60079-14)!
Transport and storage of the luminaire is
permitted in original packing and specified
position only!
4.1 Opening and closing the light fitting
- Unscrew the four screws of the cover.
- The cover can be opened to the molded
hinges. For ease of installation, the cover can
be removed out of the hinges.
If putting down take care to prevent
scratches on the silk screen cover.
4.2 Installation of the fitting
Warning - Hazard due to electrostatic
charges!
Luminaire must not be installed in the
vicinity of charge-generating processes!
The luminaire shall be fitted by using the four
mounting clips with suitable fixing screws
(Ø: 5 mm, fig. 1) onto a suitable surface.
4.3 Mains connection
The electrical connection of the device may
only be carried out by skilled staff
(IEC/EN 60079-14).
Open the cover as described.
Pass the cable through the certified Ex e / Ex t
cable entry M 20 x 1,5. Use
sealing inserts 1,2 and 3
for cables from 5.5 to 7.0 mm Ø,
sealing inserts 1 and 2
for cables from 7.0 to 9.0 mm Ø and
sealing insert 1
for cables from 9.5 to 13.0 mm Ø.
Pay attention to the proper fit of the remaining
sealing insert in the certified cable gland.
In case of unused cable entries, remove
their protective cover and close the entries
with a blanking plug (torque of 2.7 Nm).
When closing the gland with a blanking plug,
always use sealing inserts 1+2!
When metal cable entries are used, the
protective caps of the unused entries are to
be removed and the entries to be closed with
certified Ex blanking plugs (min. IP66)!
Attention!
Only fix laid cable may be used for connection!
If cable glands from other manufacturer are
used the instructions regarding strain relief
and clamping capacity must be observed!
Connect the conductors to the terminals L, N
and PE in accordance with the terminal marking
(see fig. 2).
Take care not to pinch any conductors.
The circuit can be connected via a small switch
on the board. Please refer "Type of connection".
Install the protective cover with the four screws
(Test torque 2.4 Nm).
5. Function
5.1 Display
The luminaire is fitted with a microcomputer for
charging and monitoring and with a display
composed of 7 light emitting diodes. The five
green LED’s indicate the battery’s charge state
and available capacity. The red LED signals
possible failures, the yellow LED signals the
emergency operation (fig. 3).
See also: table of LED indication status.
5.2 Adjustment
Because of the light source energy of the LED
diodes, the luminaires are used almost
exclusively as luminaires for emergency exit
signs.
After removing the hood, it is possible to adjust
to two operating positions by means of the small
switch situated on the front of the plate with the
inscription "Drawing 6A".
"Permanent lighting" position
Position "ON", delivery position.
The light goes on in normal service and
emergency situations.
"Emergency lighting" position
Fig. 4
Switch on the LED side.
Position "OFF", delivery position.
The white LED diodes are off in normal service
conditions.
Loading status and possible sources of
interference will be indicated.
In case of power failure, the white LEDs shine.
The yellow LEDs function in emergency
situations.
The weekly function test and the partial
operating time test, performed every 3
months, will be set in the position ´OFF´.
5.3 Charging
The microcomputer controlled charging system
measures the charging and discharging current
and transmits it to a capacity meter. Five green
light emitting diodes indicate in 20%-steps the
actual charge state of the battery, see fig. 3.
At temperatures below +5 °C and above +35 °C
the battery will not be fully charged for
electrochemical reasons.
During the charging process the leading flashing
LED indicates the amount of capacity charged so
far. The LED’s for the capacity already charged
indicate continuously (fig. 3). The charging
process is complete when all five green LED’s
are illuminated and none is flashing.
The LED display takes into account the decline in
the capacity of the battery: i.e., if the indication
does not go beyond the 3rd green LED even
after an extended charging period, the available
capacity is between 40 and 60 %.
This indication is updated again on each
emergency lighting operation until the battery is
shut down by the deep discharge protection for
the battery.
The reduction in the battery capacity due to
self-discharge in normal operation is automatical-
ly recharged controlled by the microprocessor.
5.4 Automatic function test
5.4.1 Function test (FT)
A function test (FT) is performed automatically.
5.4.2 Partial operating time test (TBT)
Every 3 months a partial operating time test is
performed. If no emergency lighting operation >
30 min. has occurred during the last 3 months.
During this test emergency lighting operation is
performed for approx. 35 min.
5.5. Emergency lighting operation
Emergency lighting operation is automatically
initiated by the FT+TBT, by mains failure, or
manually by shutting down the mains supply.
During this process the emergency luminaire
marked in yellow is switched to battery
operation.
The residual capacity available is indicated by the
5 green light emitting diodes, see figure 3.
6. Taking into operation
Prior to operation, check the light fitting
for its proper functioning and installation in
compliance with these operating instructions
and other applicable regulations!
Only carry out insulation measurements
between PE and the external conductor L as
well as between PE and N.
– measuring voltage: max. 1 kV AC/DC
– measuring current: max. 10 mA
Mind: There must no insulation measure-
ment be carried out between L and N, since
that would destroy the electronics
(mains input fuse in the unit).
12
Explosion protected LED-exit luminaire
Series: EXIT N
GB
7. Maintenance
Observe the national regulations
applicable to the maintenance, servicing and
test of apparatus for explosive atmospheres
e.g IEC/EN 60079-17 as well as the general
rules of engineering!
7.1 Battery replacement
See fig. 5
When the battery shows low capacity because
of ageing the battery has to be changed.
Only use certified genuine CEAG/CCH spare
parts! (See CEAG/CCH spare parts list).
Cut the apparatus off the voltage before
opening it!
Before opening the enclosure ensure that
no potentially explosive atmosphere is
present
Open the luminaire.
Unplug the connection between batterie
printed board.
Unscrew and remove the screws of the
battery housing.
Assemble the new battery in reverse order.
8. Servicing
When servicing, in particular those components
that affect the explosion protection, will have to
be checked, e. g.:
- Housing and protective bowl for any cracks
or damages.
- Gaskets for their perfect condition.
- terminals and blanking plugs for their firm fit.
- Because of the risk of an electrostatic
charge, the light fitting shall only be cleaned
with a damp, non-fibrous cloth or sponge!
Only use customary household washing-up
liquid diluted in water as specified! The
water temperature may be max. 50 °C.
After that, rinse with clear water to prevent
the risk of tension cracks in the protective
bowl!
9. Repair/Overhaul
Repairs that affect the explosion protec-
tion, may only be carried out by CEAG/CCH
or a qualified electrician in compliance with
the applicable national rules
(IEC/EN 60079-19).
Prior to replacing or removing any components,
observe the following:
Cut the apparatus off the voltage before
opening it or carrying out repairs!
Before opening the enclosure ensure that
no potentially explosive atmosphere is
present
Only use certified genuine CEAG/CCH spare
parts (see CEAG/CCH spare parts list).
10 Disposal/Recycling
When the apparatus is disposed of, the
respective national regulations on waste disposal
will have to be observed.
In case of disposal you can obtain additional
information from your Cooper Crouse-Hinds /
EATON branch.
Subject to modifications or supplement of the
product range.
13
Attestation d’examen UE de type: BVS 09 ATEX E 029
Marquage selon 2014/34/UE et directive et normes de la série
EN 60079 ta max + 40 °C:
II 2 G
Ex eb ib mb IIC T5 Gb
ta max + 50 °C:
II 2 G
Ex eb ib mb IIC T4 Gb
II 2 D
Ex tb IIIC T80°C Db
IECEx Certificat de Conformité: IECEx BVS 13.0017
Marquage selon normes de la série
IEC 60079 ta max + 40 °C: Ex eb ib mb IIC T5 Gb
ta max + 50 °C: Ex eb ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Gamme des tensions CA: 110 - 277 V *
CC: 110 - 250 V *
* les indications prennent en considération une tolérance de tension supplémentaire
Gamme des fréquences: 50 - 60 Hz
Courant nom. 110 V CA/CC: env. 0,06 A
220 V CA/CC: env. 0,035 A
Batterie: Cellules 2x 6 V/ 0,8 Ah
Durée de charge: 28 h
Durée de service d’éclairage de secours: 3 h **
** Note: Une batterie neuve n’atteint sa capacité utile totale qu’après 3 cycles de charge et de décharge
Classe d’isolation selon CEI/EN 61140: I
Indice de protection selon CEI/EN 60529: IP 66
Température ambiante: -20 °C ... +40 °C/+50 °C
conseillée: +5 °C ... +35 °C
Température de stockage dans l’emballage original: -20 °C ... +50 °C
Poids: env. 2,5 kg
Capacité de serrage des bornes
2x par borne: 3 x 2,5 mm²
Entrée de câble Ex e / Ex t M20x1,5
câbles appropriés et couples d'essai de la vis
de pression
Ø câble (mm) Nm
Garniture 1+2+3
1 2
3
min. 5,5 1,5
max.
(1)
7, 0 1,0
Garniture 1+2
1 2
3
min. 7, 0 1,5
max.
(1)
9,0 1,4
Garniture 1
1 2
3
min. 9,5 1,0
max.
(1)
13,0 1,7
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
Fils de métal: M20x1,5 fil
Couple de test pour filetage pour
Entrée de câble Ex e / Ex t M20x1,5:
2,7 Nm
Couple de test pour les vis de montage capot: 2,4 Nm
1. Légende
Avertissement
Ce symbole avertit d’un danger grave.
Le non-respect de cet avertissement peut
entrainer la mort ou la destruction de biens.
Attention
Ce symbole met en garde contre un
éventuel défaut. Le non-respect de cette
consigne peut entrainer une panne totale
de l’appareil ou du système ou de l’installa-
tion à laquelle il est connecté.
1.1 Consignes de sécurité
Pour le personnel électricien
qualifié et le personnel instruit
suivant la règle mentation légale, y
compris les normes respectives ainsi que,
le cas échéant, CEI/EN 60079-14 pour
appareils électriques utilisables en
atmosphère explosive.
Il n’est pas permis d’utiliser le luminaire
dans la zone 0, et 20.
Les caractéristiques techniques indi-
quées sur le luminaire doivent être
respectées!
Les exigences des CEI/EN 60079-31 en ce
qui concerne des dépôts de poussière
démesurés et une température doivent
être considérées par I’utilisateur.
Il n’est pas permis de transformer ou de
modifier le luminaire!
Le luminaire ne doit être exploité que
pour la fonction qui lui est dévolue et
qu’en état intact et parfait!
Ce mode d’emploi ne doit pas être laissé
dans le luminaire pendant son exploita-
tion!
Veuillez respecter les prescriptions
nationales de sécurité et de prévoyance
contre les accidents ainsi que les consignes
de sécurité qui sont marquées d’un
( ) dans ce mode d’emploi!
2. Caractéristiques techniques
F
Bloc autonome d’éclairage de sécurité (LED)
pour atmosphères explosives Série: EXIT N
14
5.3 Technique de charge
La technique de charge pilotée par micro-ordinateur
détecte le courant de charge et de décharge, le
conditionne et le transmet à un capacimètre. Cinq
diodes luminescentes vertes indiquent par pas de
20% l’état de charge respectif de la batterie, voir fig. 3.
En cas de températures au-dessous de +5 °C et
au-dessus de +35 °C, une pleine charge des
batteries n’est pas assurée pour des raisons
électrochimiques.
Pendant le processus de charge, la LED clignotant
en tête indique la quantité de capacité absorbée
jusqu’à ce moment. Les diodes luminescentes se
rapportant à la capacité déjà absorbée sont
allumées en continu.
Les diodes luminescentes se rapportant à la
capacité encore manquante ne s’allument pas
(fig. 3). Le processus de charge est terminé
lorsque toutes les 5 diodes vertes s’allument et
qu’aucune diode ne clignote plus.
L’affichage des diodes luminescentes tient compte
de la diminution de capacité de la batterie: à savoir,
si l’affichage ne dépasse pas la 3e LED verte
même après une période de charge prolongée, la
capacité disponible se situe entre 40 et 60%.
Cette indication est réactualisée lors de chaque
fonctionnement d’éclairage de secours jusqu’à la
mise hors service par la protection contre la
décharge profonde de la batterie.
5.4 Fonction de test automatique
5.4.1 Fonction de test (FT)
Une fonction de test (FT) est exécutée automati-
quement chaque semaine.
5.4.2 Test partiel de durée de service (TBT)
Tous les 3 mois, un test partiel de durée de service
est automatiquement effectué. Si aucun fonction-
nement de secours > 30 min n’a eu lieu au cours
des 3 derniers mois. Le fonctionnement d’éclairage
de secours est alors activé pendant env. 35 min..
5.5 Fonctionnement d’éclairage de secours
Le fonctionnement d’éclairage de secours est
automatiquement enclenché par FT+TBT, en cas
de panne de secteur ou manuellement par
coupure de la tension du secteur.
Ce faisant, la lampe d’éclairage de secours
marquée en jaune est commutée sur le
fonctionnement sur batterie.
La capacité résiduelle disponible est indiquée par
les 5 diodes lumineuses vertes, voir figure 5, la
DEL jaune signale le mode éclairage de secours
(figure 3),défectueuse sont reconnus.
6 Mise en service
Vérifiez que l’installation et le fonctionne-
ment corrects de l’afficheur soient conformes
aux instructions de cette notice d’utilisation et
à toutes les autres prescriptions en vigueur !
Les mesures d’isolation ne doivent être
effectuées qu’exclusivement entre PE et les
câbles extérieurs L ainsi qu’entre PE et N !
- Tension de mesure: maximum 1kV AC/DC
- Courant de mesure: maximum 10 mA
Attention: ne pas effectuer de mesure
d’isolation entre L et N, sinon il y a destruction
de l’électronique ou du fusible de protection
d’alimentation secteur de l’appareil.
3. Conformité avec les normes
Ce luminaire convient à l’utilisation dans les
zones 1, 2 et 21, 22 d’une atmosphère explosive
selon CEI/EN 60079-10-1 et CEI/EN 60079-10-2.
Ce luminaire sont conformes aux normes
reprises dans la déclaration de conformité, jointe
séparément.
Les références aux normes et directives dans
cette notice se réfèrent toujours à la dernière
version. Les suppléments éventuels doivent
également être respectés.
4. Installation EXIT N
Lors de l’installation et de l’exploitation
des appareils électriques pour atmosphère
explosive, les règlements nationaux ainsi que
les règles de la technique généralement
reconnues doivent être respectés
(CEI/EN 60079-14)!
Le transport et le stockage ne sont permis
que dans l’emballage original et dans la
position spécifiée!
4.1 Ouverture et fermeture du panneau
- Desserrez les quatre vis du couvercle
(Tournevis 4 mm).
- Enlevez le couvercle. Posez le couvercle sur
une surface propre et lisse afin de ne pas
rayer la sérigraphie du couvercle!
4.2 Montage du panneau
Avertissement - Risque de décharge
électrostatique!
La lumière ne doit pas être installé à
proximité des processus de production de
charge.
Le panneau doit être correctement fixé à l’aide
des quatre pattes de fixation avec des vis
appropriées (vis Ø maximum 5 mm, fig.1) sur un
support solide.
4.3 Raccordement au secteur
Le raccordement électrique du dispositif ne
doit se faire que par du personnel qualifié
(CEI/EN 60079-14).
Ouvrez le capot comme décrit.
Faites passer le câble d’alimentation secteur dans
le Ex e / Ex t passe-câble marqué M 20x1,5.
Utiliser les garnitures d'étanchéité
1,2 et 3 pour les câbles de 5,5 à 7,0 mm Ø,
1 et 2 pour les câbles 7,0 à 9,0 mm Ø et
1 pour câbles de 9,5 à 13,0 mm Ø.
Veiller à ce que les garnitures restent bien
positionnées dans le presse-étoupe.
Veillez à l’assise correcte des inserts
d’étanchéité restants dans l’assemblage
vissé. En cas de non utilisation de câbles ou
de passe-câbles, la rondelle de protection
doit être retirée et remplacée par un bouchon
de fermeture homologué.
(couple de serrage 2,7 Nm).
En fermant par un bouchon de fermeture,
toujours utiliser les 1+2 joints d’étanchéité !
En cas de passe-câble en métal, les capu-
chons de protection des passe-câbles non
utilisés doivent être enlevés et remplacés par
des bouchons de fermeture antidéflagrants
homologués (minimum IP66) !
Attention Seul un câblage fixe est
autorisé ! Dans le cas d’utilisation d’autres
passe-câbles, respectez les instructions du
fabricant en ce qui concerne le serrage des câbles
et l’absence de tension mécanique sur ceux-ci !
Raccordez sûrement les câbles L, N et PE au
bornier (fig. 2).
Veillez à une pose correcte et sûre des câbles.
Evitez tout pincement des câbles !
Le mode de commutation peut être réglé sur la
carte via un petit interrupteur. Voir "Câblage".
Monter le couvercle avec les quatre vis
(Couple de test 2,4 Nm).
5. Fonction
5.1 Afficheur
Du fait de la puissance lumineuse des sources
lumineuses à DEL, les lampes qui en sont
équipées sont utilisées quasi exclusivement en
tant que lampes de signalisation de secours.
Pour cette raison, ces lampes doivent unique-
ment être en circuit en permanence.
Le bloc d’alimentation en lumière de secours
intégré dans la lampe est équipé d’un microcal-
culateur destiné au chargement et à la surveil-
lance ainsi que d’un afficheur composé de 7
diodes lumineuses.
Les 5 DEL vertes indiquent l’état de charge et de
capacité de la pile. La DEL rouge signale
d’éventuelles sources de perturbation, la DEL
jaune signale le mode éclairage de secours (figure 3).
Voir à ce sujet: Etats d’affichage par DEL
5.2 Type de réglage
En raison de la puissance des sources de
lumière LED, les luminaires qui en sont équipés
seront utilisés presque exclusivement comme
luminaires pour panneaux de sortie de secours.
Après retirement du couvercle, il est possible par
le biais d´un petit interrupteur situé sur le côté
avant de la plaque ´Dessin 6A´ de régler deux
positions de service.
Type de réglage ´lumière permanente´
Position ´ON´, livraison dans cette position.
Le luminaire s´allume en situations de service
normal et d´urgence.
Type de réglage ´luminaire d´urgence´
Fig. 4
Interrupteur sur le côté LED.
Position ´OFF´, livraison dans cette position.
Les diodes LED blanches sont éteintes en
situation de service normal.
L´état de chargement et les anomalies éven-
tuelles seront indiqués.
En cas de panne, les diodes LED blanches
s´allument. La diode LED jaune fait état de mode
d´urgence.
Le test de fonction hebdomadaire et le
test partiel de durée de service, effectué tous
les 3 mois, seront enclenchés en position ´OFF´.
F
Bloc autonome d’éclairage de sécurité (LED)
pour atmosphères explosives Série: EXIT N
15
7. Entretien
Respectez la réglementation en vigueur
en ce qui concerne l’entretien, la maintenance
et le contrôle des moyens d’exploitation
antidéflagrants (par ex. CEI/EN 60079-17)!
7.1 Remplacement de la pile
Si un vieillissement affecte la capacité de la pile,
il faut remplacer cette dernière.
N’utilisez que des pièces détachées
agréées d’origine CEAG/CCH (voir liste des
pièces détachées CEAG/CCH).
Mettez la lampe hors tension!
En ouvrant les appareils, s'assurer qu'ils
ne se trouvent pas dans une atmosphère
explosive.
Lampe ouvert.
Connecteur entre la batterie et le conseil
d'administration distinct..
Les vis de fixation et retirer le dégagement
de la batterie.
Montez la nouvelle pile en suivant l’ordre inverse.
8. Maintenance
Il faut avant tout vérifier les pièces desquelles
dépend le type de protection antidéflagrante, par ex.:
- Fissures et dommages au boîtier et au carter
de protection.
- Dommages aux joints.
- Positionnement correct des borniers et des
bouchons de fermeture.
- En raison du risque de charge électrosta-
tique, le panneau ne doit être nettoyé qu’à
l’aide d’un chiffon non pelucheux ou d’une
éponge humides ! N’utilisez pour cela que
des produits de rinçage ménagers dilués
dans de l’eau à la concentration prescrite !
La température de l’eau ne doit pas
dépasser 50 °C. Rincez ensuite à l’eau claire,
sinon il y a risque de fissures de tension
dans le carter de protection !
9. Réparation/Remise en état
Des réparations qui portent sur la
protection contre l’explosion, ne devront être
exécutées que par CEAG/CCH ou par un
électricien qualifié en conformité avec la
règlementation nationale en vigueur
(CEI/EN 60079-17).
Respectez les instructions suivantes avant le
remplacement ou le démontage de pièces
détachées:
Mettre d’abord le panneau hors tension
avant toute ouverture ou travaux de réparation!
En ouvrant les appareils, s'assurer qu'ils
ne se trouvent pas dans une atmosphère
explosive.
N’utilisez que des pièces détachées agréées
d’origine CEAG/CCH (voir liste des pièces
détachées CEAG/CCH).
10 Évacuation des déchets /
Recyclage
Lors de l’évacuation de ce matériel électrique, la
règlementation nationale respective en vigueur
devra être respectée.
En cas d'élimination, vous pouvez obtenir des
informations supplémentaires auprès de votre
branche Cooper Crouse-Hinds / EATON.
Sous réserve de modification ou de supplément
de cette série de produits.
F
Bloc autonome d’éclairage de sécurité (LED)
pour atmosphères explosives Série: EXIT N
1)
Siehe auch 5. Funktion:
Bei reduzierter Batterie-Kapazität wird auch
nur die verfügbare Kapazität angezeigt.
Beispiel:
Wurde beim letzten Kapazitätstest
nur 65% Restkapazität ermittelt, so bleibt
die Anzeige bei 4 grünen LEDs in Dauerlicht
bestehen (verfügbare Kapazität 60-80%).
2)
beliebige Kombinationen der Anzeige
möglich gemäß Lade- / Entladezustand.
1)
See also chapter 5. Function:
In case of reduced battery capacity only the
available capacity is indicated.
Example:
If during the last capacity test only 65%
remaining capacity was found, then the
indication stops at 4 green LEDs continuous-
ly illuminated (available capacity 60-80%).
2)
Any combination of indications possible
depending on charge / discharge state.
1)
Voir également 5. Fonctionnement:
Si la capacité de la batterie est réduite, seule
la capacité disponible est indiquée.
Exemple:
Si une capacité résiduelle de seulement
65% a été déterminée lors du dernier test
de capacité, l’indication reste fixée à 4 LED
vertes allumées en permanence (capacité
disponible 60-80%).
2)
combinaisons quelconques de l’indication
possible suivant l’état de charge ou décharge.
LED-Anzeigezustände/
LED
rot/
red/
rouge
LED
grün/
green/
vert
1)
LED gelb/
yellow/
jaune
Batterie Kapazität/
battery-/capacity/
Capacité de la batterie
Funktion/
Function/
Fonction
Maßnahmen/
Action/
Mesures
-
< 20 %
}
Batterie wird geladen/
battery on charge/
Batterie en charge
Batterie o.k.
Keine/
None/
Aucune
-
< 40 %
-
< 60 %
-
< 80 %
-
< 100 %
-
- 100 %
Batterie ist geladen
battery charge completed
Batterie charge
i. O./ok
Keine/
None/
Aucune
-
80 - 100 %
}
Notlichtbetrieb
emergency operation
Fonctionnementd’éclairage
de secours
Batterie wird entladen
Battery is being discharged
Batterie en cours de décharge
Funktion i. O.
Keine/
None/
Aucune
-
60 - 80 %
-
40 - 60 %
-
20 - 40 %
-
0 - 20 %
- - - 0 %
Batterie entladen/
battery discharged
Batterie déchargée
Netzspannung einschalten/
Switch on mains supply/
Vérifier l’appareil d’éclairage de
secours
(
²)
0 - 100 %
Störung im Notlichtstrom-
kreis/
Emergency circuit defective/
Appareil d’éclairage de
secours défectueux
Notlichtgerät prüfen/
Check emergencylighting device/
Vérifier l’appareil d’éclairage de
secours
oder/or/
ou
Notlichtdauer < 30 min
Batterielade-/Entladezyklus
durchführen
Duration of emergency
lighting < 30 min
Perform battery charging/
discharging cycle
(see chap. 6. Fault indicator)
Durée d’éclairage de secours
< 30 min
charge/décharge de la batterie
(voir chap. 6 Indication de
défaut)
LED blinkt
LED flashing
LED clignotant
LED leuchtet
LED illuminated
LED illuminé
LED Affichage de l'état de charge et
de capacité
LED-indication status/
Publication No.
300 8000 2035 /(j) /
Auflage / 12.2019 / MS
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2019 Eaton
All Rights Reserved
Printed in Germany
dd
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Eaton Crouse-hinds series Operating Instructions Manual

Catégorie
Batteries rechargeables
Taper
Operating Instructions Manual
Ce manuel convient également à

dans d''autres langues