Allen-Bradley 1794-PS3 Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

Installation Instructions
FLEX I/O Power Supply Modules
Catalog number 1794-PS13 and 1794-PS3
Table of Contents
Topic Page
Important User Information 2
Environment and Enclosure 3
Preventing Electrostatic Discharge 3
North American Hazardous Location Approval 5
Install Your Power Supply Module 7
Connect Wiring for your Power Supply Module 8
Diagnostic Indicator 10
Specifications 11
Derating Curve for 1794-PS3 (for any mounting other than horizontal) 14
Mounting Dimensions 15
2 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls
(Publication SGI-1.1
available from your local Rockwell Automation Sales Office or online at
http://www.rockwellautomation.com/literature/
) describes some important differences between
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you
identify a hazard, avoid a hazard, and recognize the consequences.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
FLEX I/O Power Supply Modules 3
Publication 1794-IN069E-EN-P - September 2018
Environment and Enclosure
Preventing Electrostatic Discharge
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1),
at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application
if nonmetallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
, for additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
degrees of protection provided by enclosures.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
4 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Electrical Safety Consideration
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail
properly. Refer to Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation publication 1770-4.1
, for more information.
ATTENTION: Do not remove or replace a Terminal Base unit while power is
applied. Interruption of the backplane can result in unintentional operation or
machine motion.
ATTENTION:
If this equipment is used in a manner not specified by the manufacturer,
the protection provided by the equipment may be impaired.
Read this document and the documents listed in the Additional Resources
section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are
required to familiarize themselves with installation and wiring instructions
in addition to requirements of all applicable codes, laws, and standards.
Installation, adjustments, putting into service, use, assembly, disassembly,
and maintenance are required to be carried out by suitably trained
personnel in accordance with applicable code of practice.
In case of malfunction or damage, no attempts at repair should be made.
The module should be returned to the manufacturer for repair. Do not
dismantle the module.
This equipment is certified for use only within the surrounding air
temperature range of 0…55 °C (32…131 °F). The equipment must not be
used outside of this range.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use
any cleaning agents.
ATTENTION: All wiring must comply with applicable electrical installation
requirements (for example, N.E.C. article 501-4(b)).
FLEX I/O Power Supply Modules 5
Publication 1794-IN069E-EN-P - September 2018
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
1794-PS13 and 1794-PS3.
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet
équipement en environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des marquages sur
sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code
de température le plus défavorable (code de température le
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par
les autorités locales qualifiées au moment de l'installation.
EXPLOSION HAZARD
Do not disconnect equipment unless power
has been removed or the area is known to
be nonhazardous.
• Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut rendre
cet équipement inadapté à une utilisation
en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
WARNING:
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
If you insert or remove the module while backplane power is on, an
electric arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
The module does not support “Removal and Insertion Under Power”
(RIUP) capability. Do not connect or disconnect the module while power
is applied. Be sure power is removed before proceeding.
For Class I Division 2 applications, use only Class I Division 2 listed or
recognized accessories and modules approved for use within the 1794
platform.
6 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
FLEX I/O 1794-PS13 and 1794-PS3 Power Supply Modules
The 1794-PS13 power supply provides sufficient 24V DC power to operate 4 adapter
modules. Do not attempt to operate an entire FLEX I/O system with the 1794-PS13
power supply.
The 1794-PS3 power supply provides sufficient 24V DC power to operate 10 adapter
modules. You can use this 1794-PS3 power supply to operate an entire FLEX I/O system.
Component Identification
Description
1 Power supply module
2 Indicator
3 150/230V AC ground
4 120/230V AC common L2/N connections
5 120/230V AC power L1 connections
6 +24V DC connections
7 24V DC common connections
1
2
3
4
5
6
7
3
4
5
1
2
6
7
1794-PS13
1794-PS3
FLEX I/O Power Supply Modules 7
Publication 1794-IN069E-EN-P - September 2018
Install Your Power Supply Module
1. Hook the lip on the rear of the power supply module onto the top of the DIN
rail, and rotate the power supply module onto the rail.
2. Press the power supply module down onto the DIN rail until flush. Locking
tab C will snap into position and lock the power supply module to the DIN rail.
3. If the power supply module does not lock in place, use a screwdriver or similar
device to move the locking tab down while pressing the power supply module
flush onto the DIN rail, and release the locking tab to lock the power supply
module in place. If necessary, push up on the locking tab to lock.
4. Connect the power supply wiring as shown in Connect
Wiring for your Power
Supply Module below.
Note: For panel/Wall mounting, refer to publication 1794-TD013
, Panel Mounting Kit,
catalog number 1794-NM1.
ATTENTION: During mounting of all devices, be sure that all debris (metal
chips, wire strands, etc.) is kept from falling into the module. Debris that falls
into the module could cause damage on power up.
B
C
A
C
1794-PS13 shown
8 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Connect Wiring for your Power Supply Module
Terminals A, B and C are 120/230V AC supply terminals. Terminals D, E and F are available
to daisychain this 120/230V AC power to other 1794-PS power supply modules. If applying
120/230V AC power to the power supply, you can also power the corresponding 120/230V
AC modules in your FLEX I/O system.
1. Connect the 120/230V AC power to the left side terminals on the connectors on
the left side of the power supply module as follows:
2. Connect terminal G (+24V DC) to the +24V DC terminal on the first adapter.
3. Connect terminal H (+24V DC common) to the +24V DC common terminal
on the first adapter.
4. Connections I and J are used to pass +24V DC power (G) and –24V common
(H) to the next adapter in the series (if required).
IMPORTANT
When wiring this power supply, torque terminal screws to 0.8 Nm
(7 lbs-in.).
Connect To
AC ground GND A
120/230V AC common L2/N B
120/230V AC power L1 C
A
B
C
F
G
ED
H
I
J
Power
24V DC
POWER SUPPLY
1794-PS3
1 3
/(
1794-PS3 shown
FLEX I/O Power Supply Modules 9
Publication 1794-IN069E-EN-P - September 2018
5. Repeat steps 3 and 4 using terminals I and J for the second adapter.
6. Connections D, E and F are used to pass 120/230V AC power to adjacent 1794
power supplies, or to power any corresponding120/230V AC modules in your
FLEX I/O system.
Example of Using a 1794-PS13 Power Supply to Power 4 Adapter Modules
ATTENTION: The total length of wire for terminals H, I, J and G must not
exceed 3m (9.8ft). Exceeding the 3m (9.8ft) length can reduce noise immunity.
ATTENTION: Input and output wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the authority having
jurisdiction.
24V DC
AC
24V DC
120V AC
All DC powered I/O modules
All AC powered I/O modules
24V DC
24V DC from separate source
24V DC from separate source
Combination AC and DC powered I/O modules
Power
Supply
Adapter
Adapter
Adapter
AC
24V DC
All AC powered I/O modules
Adapter
10 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Diagnostic Indicator
The power supplies have 1 indicator.
Diagnostic Indicator
Indicator Description
ON (green) Output voltage is greater than 20.4V DC, but less than 28V DC
OFF No power applied to the power supply
Output voltage exceeded 35V DC, and overvoltage protection shut the unit down
Output current is above 1.4A (1794-PS13) or above 3.2A (1794-PS3)
Power
24V DC
POWER SUPPLY
1794-PS13
24V
COM
Power
24V DC
POWER SUPPLY
1794-PS3
24V
COM
The power indicator is on (green) when voltage at the
output is between 20.4V DC and 28V DC.
The power indicator is on (green) when voltage at the
output is between 20.4V DC and 28V DC.
Power indicator
Power indicator
1794-PS3
1794-PS13
FLEX I/O Power Supply Modules 11
Publication 1794-IN069E-EN-P - September 2018
Specifications
General – 1794-PS13 and 1794-PS3
Attribute 1794-PS13 1794-PS3
Dimensions, approx.
H x W x D
87 x 69 x 69 mm
3.4 x 2.7 x 2.7 inches
87 x 94 x 69 mm
3.4 x 3.7 x 2.7 inches
Enclosure type rating None (open-style)
Wire Size 0.34…2.5 mm
2
(22...12 AWG) solid or stranded copper wire rated at 75 °C
(167 °F ), or greater, 1.2 mm (3/64 in.) insulation max
Wiring category
(1)
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
2 – on power ports
North American temp code T3
Terminal screw torque 0.8 Nm (7 lbs-in.)
Input – 1794-PS13 and 1794-PS3
Attribute 1794-PS13 1794-PS3
Nominal supply voltage 120V AC, 50/60 Hz; 0.6 A max.
230V AC, 50/60 Hz; 0.42 A max.
120V AC, 50/60 Hz; 1.7 A max.
230V AC, 50/60 Hz; 1.1 A max.
Voltage range 85…265V AC
Frequency range 47…63 Hz
Input current, max. 0.7 A 1.9 A
Inrush current 40 A typical, 1 AC cycle @ V
in
265V AC, 55 °C
Interruption Output will stay within specification when input drops out for 1/2 cycle @
47 Hz, 85V AC with max. load
Output – 1794-PS13 and 1794-PS3
Attribute 1794-PS13 1794-PS3
Nominal output +24V DC
Voltage range 20.4…27.6V DC (includes noise and 5% AC ripple)
Output current, max. 1.3 A 3 A (horizontal mounting)
2.8 A all other mountings
(see Derating Curve)
Output power 31.2 W 72 W
Output ripple, max. 1200 mV peak-to-peak
12 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Minimum load 0 mA 50 mA
Output surge Sufficient to drive 4 adapters Sufficient to drive 10 adapters
Overvoltage protection Output internally limited to 35V DC. Cycle power to re-energize.
Leakage Current, max. 0.5 mA rms @ rated input and output
Isolation voltage Tested at 2500V DC for 1 s
Overcurrrent protection, min 1.4 A 3.2 A
Thermal dissipation 23.9 BTU/hr 41.0 BTU/hr
Power dissipation, max 7 W 12 W
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F)
Temperature, surrounding air,
max.
55 °C (131 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock)
50 g
Emissions IEC 61000-6-4
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Output – 1794-PS13 and 1794-PS3
Attribute 1794-PS13 1794-PS3
FLEX I/O Power Supply Modules 13
Publication 1794-IN069E-EN-P - September 2018
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
EFT/B immunity IEC 61000-4-4:
± 2kV at 5 kHz on power ports
Surge transient immunity IEC 61000-4-5:
± 1kV line-line(DM) and ± 2kV line-earth(CM) on power ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation IEC 61000-4-11:
30% dips for 1 period at 0 ° and 180 ° on AC supply ports
60% dips for 5 and 50 periods on AC supply ports ±10% fluctuations or 15
min on AC supply ports
> 95% interruptions for 250 periods on AC supply ports
Certifications
Certifications (when
product is marked)
(1)
Value
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified
for U.S. and Canada. See UL File E334470.
UL Listed Industrial Control Equipment, certified for US and Canada. See UL
File E322657.
CE European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
EN 61010-2-201; Control Equipment Safety Requirements
RCM Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3 (1794-PS3 only)
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1)
See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declarations of
Conformity, Certificates, and other certification details.
Environmental Specifications
Attribute Value
14 FLEX I/O Power Supply Modules
Publication 1794-IN069E-EN-P - September 2018
Derating Curve for 1794-PS3 (for any mounting other than horizontal)
At the end of its life, this equipment should be collected separately from
any unsorted municipal waste.
0
0.5
0
2.0
1.0
3.0
10 20 30 40 50 55 60
Max.
Output
Current
(A)
Ambient Temperature
o
C
The area within the curve represents the safe operating range for the module under
various conditions of user supplied 24V DC supply voltages and ambient temperatures.
= Normal mounting safe operating range, (includes ).
= Other mounting positions (including inverted horizontal) safe operating range
2.8
2.5
1.5
Normal Mounting – Horizontal
Other Mounting (including Vertical, and Inverted Horizontal Mounting)
FLEX I/O Power Supply Modules 15
Publication 1794-IN069E-EN-P - September 2018
Mounting Dimensions
PS13
PS3
(Inches)
Millimeters
87
(3.4)
80
(3.2)
68
(2.7)
21 (.83)
1794-PS13
(3.4H x 2.7W x 2.7D)
87H x 68W x 69D
35
(1.4)
A
59
(2.3)
A
= Mounting hole dimensions for optional mounting kit
B
B
= DIN rail
50
(2.0)
28
(1.2)
C
C
= Secure DIN rail approximately every 200 mm
Power
24V DC
POWER SUPPLY
1794-PS13
24V
COM
(Inches)
Millimeters
87
(3.4)
80
(3.2)
94
(3.7)
1794-PS3
(3.4H x 3.7W x 2.7D)
87H x 95W x 69D
A
B
= DIN rail
50
(2.0)
28
(1.2)
B
= Secure DIN rail approximately every 200 mm
Power
24V DC
POWER SUPPLY
1794-PS3
24V
COM
A
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
, available at
http://www.rockwellautomation.com/literature/
.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at
http://www.rockwellautomation.com/support/americas/phone_en.html
, or
contact your local Rockwell Automation representative.
United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
Publication 1794-IN069E-EN-P - September 2018
Supersedes Publication 1794-IN069D-EN-P - June 2015 Copyright © 2018 Rockwell Automation, Inc. All rights reserved.
Allen-Bradley, Rockwell Automation, FLEX I/O, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwell
automation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Allen-Bradley 1794-PS3 Installation Instructions Manual

Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues