Allen Bradley 1794-PS13 Manuel utilisateur

Taper
Manuel utilisateur
Installation Instructions
Original Instructions
FLEX I/O Power Supply Modules
Catalog Numbers 1794-PS13, 1794-PS13K, 1794-PS3, 1794-PS3K
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic Page
Summary of Changes 1
Environment and Enclosure 3
Preventing Electrostatic Discharge 3
Electrical Safety Consideration 3
North American Hazardous Location Approval 4
Install Your Power Supply Module 5
Connect Wiring for your Power Supply Module 5
Diagnostic Indicator 7
Specifications 8
Derating Curve for 1794-PS3 and 1794-PS3K 10
Mounting Dimensions — 1794-PS13, 1794-PS13K 10
Topic Page
Updated template throughout
Added new K catalogs: 1794-PS13K and 1794-PS3K throughout
Updated certifications 9 and 10
2Rockwell Automation Publication 1794-IN069F-EN-P - November 2021
FLEX I/O Power Supply Modules Installation Instructions
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain
this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of
practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
岤䠑㖈㸝鄳ծꂁ縨ծ乼⡲ㄤ絶䫡劥❡ㅷ⵸霼ꢓ靀劥俒咓⟄⿺  Ⱖ➭餴彂  鿈ⴔ⴩ⴀ涸剣Ⱒ霃㢊㸝鄳ծꂁ縨ㄤ乼⡲涸湱䎾俒咓կꤑ✫䨾剣鷓欽錞薴ծ岁䖒ㄤ叻ⲥ
涸湱Ⱒ銳宠⛓㢪欽䨪鵮䗳곢擿䜪㸝鄳ㄤ䱹絁霹僈կ
㸝鄳ծ靈侮ծ䫏鵘ծ⢪欽ծ絆鄳ծ䬒⽸ㄤ絶䫡瘝ぐ고乼⡲䗳곢歋絑鵂鷓䔲雲絅涸⚁⚌➃プ䭽撑鷓欽涸乼⡲錞薴㹊倶կ
㥵卓劢䭽撑ⵖ鸣㉁䭷㹁涸倰䒭⢪欽霪霃㢊ⴭ〳腊⠔䰀㹲霃㢊䲿⣘涸⥂䫡կ
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la
instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de
práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto.
Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com
o código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы,
перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования.
Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требованиями всех применимых норм, законов и
стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться
обученным персоналом в соответствии с применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
󴎤󲼑 : 󳦥󷢢󱡸󷫤󶔨󳸔󳃮󵫪󱕜󱁃󲔛󱑹󳦥󳥆󳦥󳼤󱬼󷫤󶔨󷫤󲕁󳕽󰽳󱛬󶙌󷽺󳛲󷭪󲰳󵶙󳄾󷪹󸋺󳛒󳥆󵕢󸔑
󷭪󲰳󳧵󰾾󴎁󲲓󷧊󳭔󷦳󰻞󱔈󷫤󶔨󸞂󶊁󳅜󹌬󶗠󴯿󲳴󷦳
󷫤󶔨󷰄󳚮󸖋󸋅󸻛󲄤󰾫󵈾󶅉󵰨󷩒󰽥󱁃󲔛󱞎󷲀󰽳󳵠󷭪󲰳󲕌󳜶󷧊󱑲󲲟󷪯󶊻󱜍󸗞󱐗󰽳󳵠󱢟󲕌󷝥󲳴󷦳
󳦥󳼤󱬼󷢢󸔢󳉸󲕁󳜰󴎁󰾫󵈾󱸦󱝖󳼤󱬼󳏀󰿙󱁃󷶋󳐧󲷋
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie
dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und
Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den
anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer,
utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
󻷋󻰧: 󻇇󽴔󻳫󼥗󽴔󻗳󼌧, 󻗳󻳤, 󻱠󺢨󽴔󺫟󺝣󽴔󻯯󻺏󽴔󻇃󻛧󼨧󺋿󽴔󻳓󻪟󽴔󻇇󽴔󻀇󻗫󺹋󽴔󼢻󼨷󼨧󻪻󽴔󻗳󼌧, 󻗳󻳤󽴔󻃞󽴔󻱠󺢨󻪟󽴔󺇏󼨫󽴔󼄇󺆯󽴔󻱟󺶛󽴔󻘈󻘧󻰧󽴔󻀇󻗫󺦳󻰓󽴔󻃧󺦫󻞫󽴔󻱌󺆯󽴔󻛨󻺏󼨧󻞼󻞫󻫳. 󻕻󻭸󻱟󺝣󽴔󺽷󺦯󽴔󺇏󺳷󽴔󺊫󻳤,
󻅤󺊫󽴔󻃞󽴔󼤫󻷏󻪟󻗫󽴔󻭣󺈻󼨧󺝣󽴔󻕻󼨼󻪟󽴔󺟏󼩃󽴔󻃧󺦫󻞫󽴔󻗳󼌧󽴔󻃞󽴔󻃿󻗯󽴔󻺏󼌷󻰓󽴔󻛨󻺏󼩃󻩋󽴔󼨸󺞗󺞳 .
󻗳󼌧 , 󻴿󻳤 , 󺃏󺢨 , 󻕻󻭸 , 󻴿󺺌 , 󻉓󼩃 , 󻯯󻺏󻇃󻛧󽴔󺧀󽴔󺽷󺦯󽴔󻱠󻪔󻰏󽴔󺇏󺳷󽴔󺊫󻳤󻪟󽴔󺧿󺱋󽴔󻳐󻳗󼨫󽴔󺈟󻯰󻰓󽴔󻃪󻰏󽴔󻕻󻭸󻱟󺹋󽴔󼚄󼩃󻗫󺺛󽴔󻛧󼩘󼩃󻩋󽴔󼨸󺞗󺞳 .
󻇇󽴔󻱴󻌓󺹋󽴔󻳫󻴿󻕻󺃏󽴔󺽔󻞫󼨧󻺏󽴔󻨙󻰏󽴔󻃸󻅤󻰋󺴫󽴔󻕻󻭸󼨧󺽃󽴔󻱴󻌓󻰧󽴔󻇃󼬇󽴔󺋿󺝴󻱃󽴔󻙟󻖐󺣯󽴔󻛧󽴔󻱗󻞄󺞗󺞳 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”,
riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e
standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde
yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
岤䠑✲갪㖈㸞酤鏤㹁乽⡲䧴笞隌劥欴ㅷ⵹锞⯓ꠗ隡姽俒⟝⟃⿻⴪倴 չⰦ➮须彂պ畎眏⚥剤ꡠ㸞酤鏤㹁莅乽⡲姽鏤⪔涸俒⟝⢪欽罏䗳갭擿䜫㸞酤ㄤꂂ箁䭸
爚⚛痘ざ䨾剤岁鋊岁䖒ㄤ垦彋銴宠
⺫䭍㸞酤锅侮❜➰⢪欽⢪欽穉酤䬓⽹ㄤ笞隌瘞⹛⡲鿪䗳갭❜歋䊺竤麕黠殹鎯箻涸➃㆞鹎遤⟃痘ざ黠欽涸㻜⡲岁鋊
㥶卓㼟鏤⪔欽倴ꬌ醢鸤㉂䭸㹁涸欽鸁儘〳腋剚鸤䧭鏤⪔䨾䲿⣘涸⥃隌⸆腋「䴦
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace
a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů anorem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające
instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi
kodeksami, prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra
underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in
overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 1794-IN069F-EN-P - November 2021 3
FLEX I/O Power Supply Modules Installation Instructions
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at
altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the
application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be
sure to ground the DIN rail properly. See the Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation® publication 1770-4.1, for
more information.
ATTENTION: Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation
or machine motion.
ATTENTION:
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in
addition to requirements of all applicable codes, laws, and standards.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained
personnel in accordance with applicable code of practice.
In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not
dismantle the module.
This equipment is certified for use only within the surrounding air temperature range of 0…55 °C (32…131 °F). The equipment must not be used outside
of this range.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
Electrical Safety Consideration
ATTENTION: All wirings must comply with applicable electrical installation requirements (for example, N.E.C. article 501-4(b)).
4Rockwell Automation Publication 1794-IN069F-EN-P - November 2021
FLEX I/O Power Supply Modules Installation Instructions
FLEX I/O Power Supply Modules
The 1794-PS13 and 1794-PS13K power supply modules provide sufficient 24V DC power to operate four adapters. Do not attempt to operate an entire FLEX™ I/O system with the 1794-
PS13 or 1794-PS13K power supply module.
The 1794-PS3 and 1794-PS3K power supply modules provide sufficient 24V DC power to operate 10 adapters. You can use the 1794-PS3 or 1794-PS3K power supply module to
operate an entire FLEX I/O system.
North American Hazardous Location Approval
The Following Information Applies When Operating This Equipment In
Hazardous Locations. Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a system, the most
adverse temperature code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of equipment in your system
are subject to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température global
du système. Les combinaisons d'équipements dans le système sont sujettes à inspection
par les autorités locales qualifiées au moment de l'installation.
WARNING:
Explosion Hazard –
Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate to
this equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I,
Division 2.
AVERTISSEMENT:
Risque d’Explosion –
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens fournis avec ce
produit.
La substitution de composants peut rendre cet équipement inadapté
à une utilisation en environnement de Classe I, Division 2.
WARNING:
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
If you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
The module does not support “Removal and Insertion Under Power” (RIUP) capability. Do not connect or disconnect the module while power is
applied. Be sure power is removed before proceeding.
For Class I Division 2 applications, use only Class I Division 2 listed or recognized accessories and modules approved for use within the 1794 platform.
Component Identification
Description Description
1 Power supply module 5 120/230V AC power L1 connections
1794-PS3, 1794-PS3K1794-PS13, 1794-PS13
12
3
4
5
7
6
12
3
4
5
7
6
Rockwell Automation Publication 1794-IN069F-EN-P - November 2021 5
FLEX I/O Power Supply Modules Installation Instructions
Install Your Power Supply Module
1. Hook the lip on the rear of the power supply module onto the top of the DIN rail, and rotate the power supply module onto the rail.
2. Press the power supply module down onto the DIN rail until flush. Locking tab C snaps into position and lock the power supply module to the DIN rail.
3. If the power supply module does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the power supply module flush onto the
DIN rail. Release the locking tab to lock the power supply module in place. If necessary, push up on the locking tab to lock.
4. Connect the power supply wiring as shown in Connect Wiring for your Power Supply Module below.
Note: For panel/wall mounting, see publication 1794-TD013, Panel Mounting Kit, catalog number 1794-NM1.
Connect Wiring for your Power Supply Module
Terminals A, B, and C are 120/230V AC supply terminals. Terminals D, E, and F are available to daisy chain this 120/230V AC power to other 1794-PS power supply modules. If applying
120/230V AC power to the power supply, you can also power the corresponding 120/230V AC modules in your FLEX I/O system.
2 Indicator 6 120/230V AC common L2/N connections
3 24V DC common connections 7 150/230V AC ground
4 +24V DC connections
ATTENTION: During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls
into the module could cause damage on power up.
Component Identification (Continued)
Description Description
B
C
A
C
1794-PS13 shown
A
B
C
FG
ED
H
I
J
Power
24V DC
POWER SUPPLY
1794-PS3
1 3
/(
1794-PS3 shown
6Rockwell Automation Publication 1794-IN069F-EN-P - November 2021
FLEX I/O Power Supply Modules Installation Instructions
1. Connect the 120/230V AC power to the left side terminals on the connectors on the left side of the power supply module as follows:
2. Connect terminal G (+24V DC) to the +24V DC terminal on the first adapter.
3. Connect terminal H (+24V DC common) to the +24V DC common terminal on the first adapter.
4. Connections I and J are used to pass +24V DC power (G) and –24V common (H) to the next adapter in the series (if necessary).
5. Repeat steps 3 and 4 using terminals I and J for the second adapter.
6. Connections D, E, and F are used to pass 120/230V AC power to adjacent FLEX I/O power supply modules, or to power any corresponding 120/230V AC modules in your
FLEX I/O system.
Example of Using a 1794-PS13 or 1794-PS13K Power Supply Module to Power 4 Adapters
IMPORTANT When wiring this power supply, torque terminal screws to 0.8 N•m (7 lb•in).
Connect To
AC ground GND A
120/230V AC common L2/N B
120/230V AC power L1 C
ATTENTION: The total length of wire for terminals H, I, J, and G must not exceed 3 m (9.8 ft). Exceeding the 3 m (9.8 ft) length can reduce noise
immunity.
ATTENTION: Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having
jurisdiction.
24V DC
AC
24V DC
120V AC
All DC powered I/O modules
All AC powered I/O modules
24V DC
24V DC from separate source
24V DC from separate source
Combination AC and DC powered I/O modules
Power
Supply Adapter
Adapter
Adapter
AC
24V DC All AC powered I/O modules
Adapter
Rockwell Automation Publication 1794-IN069F-EN-P - November 2021 7
FLEX I/O Power Supply Modules Installation Instructions
Diagnostic Indicator
The power supply module has one indicator.
Diagnostic Indicator
Indicator Description
ON (green) Output voltage is greater than 20.4V DC, but less than 28V DC
OFF
No power applied to the power supply
Output voltage exceeded 35V DC, and overvoltage protection shut down the unit
Output current is above 1.4 A – 1794-PS13, 1794-PS13K
Above 3.2 A – 1794-PS3, 1794-PS3K
Power
24V DC
POWER SUPPLY
1794-PS13
24V
COM
Power
24V DC
POWER SUPPLY
1794-PS3
24V
COM
The power indicator is on (green) when voltage
at the output is between 20.4V DC and 28V DC.
The power indicator is on (green) when voltage
at the output is between 20.4V DC and 28V DC.
Power indicator
1794-PS3, 1794-PS3K
1794-PS13, 1794-PS13K
8Rockwell Automation Publication 1794-IN069F-EN-P - November 2021
FLEX I/O Power Supply Modules Installation Instructions
Specifications
General Specifications
Attribute 1794-PS13, 1794-PS13K 1794-PS3, 1794-PS3K
Dimensions, approx.
H x W x D 87 x 69 x 69 mm (3.4 x 2.7 x 2.7 in.) 87 x 94 x 69 mm (3.4 x 3.7 x 2.7 in.)
Enclosure type rating None (open-style)
Wire Size 0.34…2.5 mm2 (22...12 AWG) solid or stranded copper wire rated at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation max
Wiring category(1)
(1) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
2 – on power ports
North American temp code T3C T3
Terminal screw torque 0.8 N•m (7 lb•in.)
Input Specifications – 1794-PS13, 1794-PS13K, 1794-PS3, 1794-PS3K
Attribute 1794-PS13, 1794-PS13K 1794-PS3, 1794-PS3K
Nominal supply voltage 120V AC, 50/60 Hz; 0.62 A max
230V AC, 50/60 Hz; 0.42 A max 120V AC, 50/60 Hz; 1.7 A max
230V AC, 50/60 Hz; 1.1 A max
Voltage range 85…265V AC
Frequency range 47…63 Hz
Input current, max 0.7 A 1.9 A
Inrush current 40 A typical, 1 AC cycle @ Vin 265V AC, 55 °C
Interruption Output stays within specification when input drops out for 1/2 cycle @ 47 Hz, 85V AC with max load
Output Specifications – 1794-PS13, 1794-PS13K, 1794-PS3, 1794-PS3K
Attribute 1794-PS13, 1794-PS13K 1794-PS3, 1794-PS3K
Nominal output +24V DC
Voltage range 20.4…27.6V DC (includes noise and 5% AC ripple)
Output current, max 1.3 A 3 A (horizontal mounting)
2.8 A all other mountings
(see Derating Curve for 1794-PS3 and 1794-PS3K)
Output power 31.2 W 72 W
Output ripple, max 1200 mV peak-to-peak
Minimum load 0 mA 50 mA
Output surge Sufficient to drive 4 adapters Sufficient to drive 10 adapters
Overvoltage protection Output internally limited to 35V DC. Cycle power to re-energize.
Leakage Current, max 0.5 mA rms @ rated input and output
Isolation voltage Tested @ 2500V DC for 1 s
Overcurrent protection, min 1.4 A 3.2 A
Thermal dissipation 23.9 BTU/hr 41.0 BTU/hr
Power dissipation, max 7 W 12 W
Rockwell Automation Publication 1794-IN069F-EN-P - November 2021 9
FLEX I/O Power Supply Modules Installation Instructions
Environmental Specifications
Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F)
Temperature, surrounding air, max 55 °C (131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock)
50 g
Emissions IEC 61000-6-4
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
EFT/B immunity IEC 61000-4-4:
± 2 kV at 5 kHz on power ports
Surge transient immunity IEC 61000-4-5:
± 1 kV line-line(DM) and ± 2 kV line-earth(CM) on power ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation
IEC 61000-4-11:
30% dips for 1 period at 0° and 180° on AC supply ports
60% dips for 5 and 50 periods on AC supply ports ±10% fluctuations or 15 min on AC supply ports
> 95% interruptions for 250 periods on AC supply ports
Certifications
Certifications (when product is marked)(1) Value
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
CE
European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical Documentation
RCM Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
10 Rockwell Automation Publication 1794-IN069F-EN-P - November 2021
FLEX I/O Power Supply Modules Installation Instructions
Derating Curve for 1794-PS3 and 1794-PS3K
Mounting Dimensions — 1794-PS13, 1794-PS13K
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
Russian Customs Union TR CU 004/2011 LV Technical Regulation
Morocco Arrêté ministériel n° 6404-15 du 29 ramadan 1436
Arrêté ministériel n° 6404-15 du 1 er muharram 1437
(1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details.
Certifications (Continued)
Certifications (when product is marked)(1) Value
Normal mounting – Horizontal
Other mounting (including vertical and inverted horizontal mounting)
0
0.5
0
2.0
1.0
3.0
10 20 30 40 50 55 60
max.
Output
current (A)
Ambient temperature oC
The area within the curve represents the safe operating range for the module under
various conditions of user supplied 24V DC supply voltages and ambient temperatures.
= Normal mounting safe operating range, (includes ).
= Other mounting positions (including inverted horizontal) safe operating range
2.8
2.5
1.5
(Inches)
Millimeters
87
(3.4)
80
(3.2)
68
(2.7)
21 (.83)
1794-PS13, 1794-PS13K
(3.4H x 2.7W x 2.7D)
87H x 68W x 69D
35
(1.4)
A
59
(2.3)
A= Mounting hole dimensions for optional mounting kit
B
B= DIN rail
50
(2.0)
28
(1.2)
C
C = Secure DIN rail approximately every 200 mm
Power 24V DC
POWER SUPPLY
1794-PS13
24V
COM
Rockwell Automation Publication 1794-IN069F-EN-P - November 2021 11
FLEX I/O Power Supply Modules Installation Instructions
Mounting Dimensions — 1794-PS3, 1794-PS3K
(Inches)
Millimeters
87
(3.4)
80
(3.2)
94
(3.7)
1794-PS3, 1794-PS3K
(3.4H x 3.7W x 2.7D)
87H x 95W x 69D
A
B
= DIN rail
50
(2.0)
28
(1.2)
B
= Secure DIN rail approximately every 200 mm
Power
24V DC
POWER SUPPLY
1794-PS3
24V
COM
A
Publication 1794-IN069F-EN-P - November 2021 | Supersedes Publication 1794-IN069E-EN-P-September 2018
Copyright © 2021 Rockwell Automation, Inc. All rights reserved.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Allen-Bradley, expanding human possibility, FactoryTalk, FLEX, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center
(PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release
notes. rok.auto/pcdc
Connect with us.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Allen Bradley 1794-PS13 Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues