SolaHD CVS Hardwired Series 60 Hz Le manuel du propriétaire

Taper
Le manuel du propriétaire
CVS Hardwired Series – 60 Hz
User Manual
Contents
1.0 Important Safety Instructions .................................................................................................................................. 3
2.0 Warnings Defined ..................................................................................................................................................... 3
3.0 Introduction .............................................................................................................................................................. 3
4.0 Installation Instructions ............................................................................................................................................ 3
4.1 Receiving .................................................................................................................................................................................. 3
4.2 Mounting & Ventilation ............................................................................................................................................................. 3
4.3 Mechanical Drawings & Dimensions ........................................................................................................................................ 4
4.4 Electrical ................................................................................................................................................................................... 6
5.0 Parallel & Three-Phase Connections ....................................................................................................................... 9
5.1 Parallel Operation ..................................................................................................................................................................... 9
5.2 Three-Phase Connection Operation ......................................................................................................................................... 9
6.0 Operating Notes & Data ......................................................................................................................................... 10
6.1 Checking with Voltmeters ....................................................................................................................................................... 10
6.2 Load Regulation ..................................................................................................................................................................... 10
6.3 Effect of Load Power Factor .................................................................................................................................................. 10
6.4 Operation with Switch-Mode Power Supplies ....................................................................................................................... 10
6.5 Effect of Frequency ................................................................................................................................................................ 10
6.6 Response Time ....................................................................................................................................................................... 10
6.7 Input Characteristics .............................................................................................................................................................. 10
6.8 Current Limitations ................................................................................................................................................................. 11
6.9 Operation with Motor Loads .................................................................................................................................................. 11
7.0 Service & Maintenance .......................................................................................................................................... 11
7.1 Service & Maintenance ........................................................................................................................................................... 11
7.2 Field Replacement of Capacitors ........................................................................................................................................... 11
8.0 Troubleshooting ...................................................................................................................................................... 11
9.0 Specifications ......................................................................................................................................................... 12
10.0 Warranty & Support .............................................................................................................................................. 12
10.1 Warranty Information ............................................................................................................................................................ 12
10.2 Technical Support ................................................................................................................................................................. 12
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Group, LLC. assumes no responsibility, and disclaims all liability
for damages resulting from use of this information or for any errors or omissions. The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Ofce.
All other product or service names are the property of their registered owners. ©2016 Appleton Group, LLC. All rights reserved. Specications are subject to change
without notice.
CVS HARDWIRED SERIES USER MANUAL | 3
1.0 Important Safety Instructions
Please read all safety, installation, and operating instructions before attempting to install or operate the unit.
!
DANGER! High voltages are present inside the unit. Do not reach inside while it is energized. This unit contains no
user-serviceable parts.
2.0 Warnings Defined
!
DANGER! Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. This signal
word is limited to the most extreme situations.
!
WARNING! Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
!
CAUTION! Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may also
be used to alert against unsafe practices.
3.0 Introduction
The SolaHD Constant Voltage Sinusoidal (CVS) transformer provides voltage regulation and isolation from both transverse and
common mode noise for any type of load. It also suppresses transients with ferroresonant, protects overloads, and serves as a
dedicated line. It is the ultimate in ac power conditioning equipment.
4.0 Installation Instructions
4.1 Receiving
Upon receipt, immediately inspect the unit for obvious signs of shipping damage and/or mishandling. If damaged, photograph the
unit, inform the carrier, and contact your SolaHD representative.
4.2 Mounting & Ventilation
These units are for use in an indoor humidity and temperature controlled environment. Mount the unit in either a horizontal or vertical
position. The unit should be located where contact with the transformer’s hot surface is unlikely. If mounted in a vertical position (e.g.
on a wall), steel mounting hardware must be selected in accordance with Table 1. The wiring compartment should also be facing up.
Table 1: Mounting Hardware
CVS Rated VA Steel Mounting Screws (Minimum Diameter)
30–120 VA #10 machine screws
250 VA 1/4 in. bolts
500–1000 VA 5/16 in. bolts
1500–10000 VA 3/8 in. bolts
15000 VA 1/2 in. bolts
All regulators generate a considerable amount of heat and depend on natural convection for adequate cooling. It is important
that ventilation openings not be obstructed. Mounting in a conned or poorly ventilated space should be avoided, unless special
provisions have been made for ventilation. For proper ventilation, allow a minimum of 12 inches of clearance above the unit and
minimum of 6 inches of clearance on each side.
4 | CVS HARDWIRED SERIES USER MANUAL
4.3 Mechanical Drawings & Dimensions
Table 2: Dimensions—Figure 1
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]
A B C D E F G H
60 23-13-030-2 6.12 [155.4] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
0.22 x 0.59
[5.6 x 15.0]
7.0 [3.2]
60 23-13-060-2 6.94 [176.3] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
0.22 x 0.59
[5.6 x 15.0]
9.0 [4.1]
60 23-22-112-2 8.12 [206.2] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 2.44 [62.0]
0.22 x 0.59
[5.6 x 15.0]
13.0 [5.9]
60 23-23-125-8 10.50 [266.7] 7.56 [192.0] 4.75 [120.6] 5.63 [143.0] 4.75 [120.6] 4.12 [104.6] 3.03 [77.0]
0.31 x 0.69
[7.9 x 17.5]
28.0 [12.7]
60 23-23-150-8 13.00 [330.2] 6.50 [165.1] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 3.06 [77.7]
0.38 x 0.81
[9.7 x 20.6]
37.0 [16.8]
60 23-23-210-8 17.25 [438.2] 6.81 [173.0] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 5.25 [133.4]
0.38 x 0.81
[9.7 x 20.6]
63.0 [28.6]
Table 3: Dimensions—Figure 2
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]
A B C D E F G H
60 23-23-220-8 17.58 [446.5] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 3.88 [98.6] 5.19 [131.8]
0.44 x 0.69
[11.2 x 17.5]
109.0 [49.4]
60 23-23-230-8 18.96 [481.6] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 5.25 133.4] 5.19 [131.8]
0.44 x 0.69
[11.2 x 17.5]
142.0 [64.4]
60 23-23-250-8 28.53 [724.7] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 8.25 [209.5] 8.88 [225.6]
0.44 x 0.69
[11.2 x 17.5]
222.0 [100.7]
FIGURE 1
FIGURE 2
CVS HARDWIRED SERIES USER MANUAL | 5
Table 4: Dimensions—Figure 3
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]
A B C D E F G H
60 23-28-275-6 26.91 [683.5] 9.27 [235.6] 23.55 [598.2] 25.81 [655.6] 24.81 [630.2] 6.62 [168.1] 8.88 [225.6]
0.44 x 0.69
[11.2 x 17.5]
365.0 [165.6]
FIGURE 3
6 | CVS HARDWIRED SERIES USER MANUAL
4.4 Electrical
!
Caution! All hardwired units should be installed in accordance with local and national electrical codes.
FIGURE 4
Table 5: Electrical Connections—Figure 4
Catalog Number Primary Voltage Interconnect Connect Lines to
23-13-030-2 120 H3 and H4 are NOT used H1 and H2
23-13-060-2 120 H3 and H4 are NOT used H1 and H2
23-22-112-2
120
H1 to H3
H2 to H4
H1 and H4
240 H2 to H3 H1 and H4
23-28-275-6
240
H1 to H3
H2 to H4
H1 and H4
480 H2 to H3 H1 and H4
Catalog Number Secondary Voltage Interconnect Connect Lines to
23-13-030-2 120 --- X1 and X2
23-13-060-2 120 --- X1 and X2
23-22-112-2 120 --- X1 and X2
23-28-275-6
120 --- X1 and X2 OR X3 and X2
240 --- X1 and X3
NOTE: Secondaries are not grounded. Ground X2 per code.
Table 6: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-13-030-2 30 60
23-13-060-2 60 85
23-22-112-2 120 136
23-28-275-6 7500 2407
Table 7: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-13-030-2 1 A/14 AWG --- --- --- --- 14 AWG --- ---
23-13-060-2 2 A/14 AWG --- --- --- --- 14 AWG --- ---
23-22-112-2 3 A/14 AWG --- 3 A/14 AWG --- --- 14 AWG --- ---
23-28-275-6 --- --- 60 A/6 AWG 30 A/10 AWG --- 4 AWG 8 AWG 8 AWG
CVS HARDWIRED SERIES USER MANUAL | 7
Table 8: Electrical Connections—Figure 5
Catalog Numbers Primary Voltage Interconnect Connect Lines to
23-23-125-8
120
H1 to H3 to H5 to H7
H2 to H4 to H6 to H8
H1 and H2
240
H2 to H3 H6 to H7
H1 to H5 H4 to H8
H1 and H4
480
H2 to H3 H4 to H5
H6 to H7
H1 and H8
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2
FIGURE 5
Table 10: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-125-8 6 A/14 AWG --- 3 A/14 AWG 1 A/14 AWG --- 14 AWG --- ---
Table 9: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-125-8 250 225
8 | CVS HARDWIRED SERIES USER MANUAL
FIGURE 6
Table 11: Electrical Connections—Figure 6
Catalog Number Primary Voltage Interconnect Connect Lines to
23-23-150-8
23-23-210-8
23-23-220-8
23-23-230-8
23-23-250-8
120
H1 to H3 to H6 to H8
H2 to H5 to H7 to H10
H1 and H2
208
H2 to H3 H7 to H8
H1 to H6 H4 to H9
H1 and H4
240
H2 to H3 H7 to H8
H1 to H6 H5 to H10
H1 and H5
480
H2 to H3 H5 to H6
H7 to H8
H1 and H10
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2 OR X3 and X2
240 --- X1 and X3
Table 13: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-150-8 10 A/14 AWG 6 A/14 AWG 6 A/14 AWG 3 A/14 AWG --- 14 AWG
23-23-210-8 15 A/14 AWG 10 A/14 AWG 10 A/14 AWG 6 A/14 AWG --- 14 AWG
23-23-220-8 30 A/10 AWG 20 A/12 AWG 15 A/14 AWG 10 A/14 AWG --- 10 AWG 14 AWG
23-23-230-8 45 A/8 AWG 25 A/10 AWG 25 A/10 AWG 15 A/14 AWG --- 8 AWG 12 AWG
23-23-250-8 80 A/4 AWG 40 A/8 AWG 40 A/8 AWG 20 A/12 AWG --- 8 AWG* 10 AWG
*Leads in the wiring compartment must have 105°C sleeving
Table 12: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-150-8 500 280
23-23-210-8 1000 519
23-23-220-8 2000 1229
23-23-230-8 3000 1331
23-23-250-8 5000 2117
CVS HARDWIRED SERIES USER MANUAL | 9
FIGURE 6
5.0 Parallel & Three-Phase Connections
5.1 Parallel Operation
Units of the same SolaHD catalog number may be connected in parallel to obtain a larger load capacity. Both input and output
connections must be made in parallel (see Figure 6). The SolaHD catalog number must end in -8 or -C8 and must be larger than 1
kVA. No portable units can be paralleled.
All input and output paralleling wires must be tied together in an external paralleling “box” provided by the user. Do not attempt to
jumper the wires of one unit to the terminal block of the other unit. The terminal block may not be rated to carry the total currents
of both units. The input of each unit must be properly and separately fused.
!
CAUTION! Failure to adhere to these requirements may damage the windings.
For units smaller than 5 kVA: When connecting in parallel the 208 Volt windings, other output voltage ratings (120 V, 240 V) can’t
be paralleled at the same time and vice versa. It is suggested that the installer remove X2 grounding on each unit, then connect
X2 from each unit to one location and ground at that location only.
5.2 Three-Phase Connection Operation
Loads requiring 4-wire WYE connection may be served by three ferroresonant power conditioners with the same SolaHD catalog
number. The inputs must be connected in Delta. Input fuses must be connected in the primary of each unit, not in the three-phase
lines. The outputs must be connected in WYE with the neutral solidly connected to a WYE load. Alternatively, these three outputs
may serve three independent single-phase loads. Phase angles may vary somewhat from 120 degrees even with balanced
loading.
This circuit arrangement is not intended to serve single-phase line-to-line loading or three-phase Delta loading. Outputs must
serve three independent, single-phase loads of the same total Volt-Amphere (VA) rating. Connections should be made in one of
two ways as shown in Figure 6.
The outputs of the unit are isolated from the input lines. Voltage generated by internal leakage currents will occur with respect
to ground, which can have undesirable effects in electronic equipment. Therefore, if circuit “B” is used, it is suggested that the
installer remove X2 grounding on -8 units, then connect all X2 from each phase to one location and ground at that location only.
This is not required for circuit “A” and will not affect regulation or the ability to reject power line noise or transients.
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(A) Isolated Single-Phase Loads
A
B
C
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(B) Separte Single-Phase Loads
In Grounded WYE
A
B
C
Unit A
Unit B
Input
Input
Output
Output
Ac Single-Phase
Input
10 | CVS HARDWIRED SERIES USER MANUAL
6.0 Operating Notes & Data
!
DANGER! High voltages are present inside the unit. Do not reach inside while it is energized. To measure voltage,
de-energize the unit, connect the meter, and then re-energize the unit.
6.1 Checking with Voltmeters
All input and output voltage measurements should be made with a true RMS voltmeter. A certain amount of harmonics in the
output may cause other types—particularly rectier types—to give inaccurate indications.
6.2 Load Regulation
Changes in output voltage resulting from changes in resistive loads, from no load to full load (100% pF), are approximately 4%.
6.3 Effect of Load Power Factor
“Median” value of output voltage will vary from the label rating if the load has a power factor different from the unit’s design. Load
regulation will also be greater as the inductive load power factor is decreased. However, the resulting median values of output
voltage will be regulated against supply line changes at any reasonable load or load power factor.
6.4 Operation with Switch-Mode Power Supplies
If an MCR is used as a source for a switch-mode power supply, a slight amount of ringing may be noticed on the sine wave
output of the unit at half cycle intervals for a short duration. This ringing occurs at the point when the switch-mode power supply
current demand drops to zero. The ringing need not be a cause for concern since it is of relatively low magnitude and frequency.
Both series have been tested with a variety of switch-mode power supplies and it has been determined that the ringing does not
affect the dc outputs, nor has it been found to degrade the components of any switch-mode power supply.
6.5 Effect of Frequency
Changes in the frequency of the supply voltage will be directly reected in the output voltage. A change of about 1.8% in output
voltage will occur for every 1% change in input frequency, and in the same direction as the frequency change.
6.6 Response Time
An important advantage of the SolaHD principle of static magnetic regulation is its exceedingly fast response time compared
with other types of ac regulators. Transient changes in supply voltage are usually corrected with 1-1/2 cycles or less; the output
voltage will not uctuate more than a few percent.
6.7 Input Characteristics
The MCR’s transformer includes a resonant circuit, which is energized whether it is serving a load or not. Therefore, the input
current at no load is approximately 35% of the full-load level, even at light or no load. Input power factor will average 90–100% at
full load, but may drop to about 75% at half load and 25% at no load. In any case, it is always leading.
FIGURE 7
CVS HARDWIRED SERIES USER MANUAL | 11
6.8 Current Limitations
When the load is increased beyond the MCR’s rated value, a point is reached where the output voltage suddenly collapses and
will not regain its normal value until the load is partially released. Under short-circuit conditions, the load current is limited to
approximately twice of the rated full-load value, and the input power to less than 10% of normal. The unit will protect both itself
and its load against damage from excessive fault currents. Fusing of load circuits is not necessary.
6.9 Operation with Motor Loads
Because of the current-limiting effect described above, special attention should be given to motor applications. In general, the
regulator must have a load rating nearly equal to the maximum power drawn during the starting cycle. This may run from two to
eight times the normal (running) rating of the motor. In doubtful cases, it is advisable to measure the actual starting current.
7.1 Service & Maintenance
The unit is a simple, rugged device with no moving parts. Routine service and/or maintenance is not required. If a problem does
occur, please refer to “8.0 Troubleshooting” or contact SolaHD Technical Support for assistance.
7.2 Field Replacement of Capacitors
Capacitors used in our units are the highest commercial grade, with each one given a rigid acceptance test upon receipt. SolaHD
guarantees free replacement of any capacitors which fail within one year of sale. Older units can be replaced at a moderate
charge.
NOTE: It may be possible to test and identify defective capacitors in the eld. Please contact SolaHD Technical Support at
1.800.377.4384 or 1.847.268.6651 for further assistance.
8.0 Troubleshooting
Table 14: Troubleshooting
Problem Action
Nominal voltage too high
1. The load may be considerably less than the full rating. See “6.2 Load Regulation”.
2. The load may have a leading power factor.
Nominal voltage too low
1. The load power factor may be lagging.
2. The unit may be slightly overloaded. See “6.8 Current Limitations”.
Unit does not regulate closely
1. The unit may be slightly overloaded. See “6.8 Current Limitations”.
2. The actual line voltage swings may be outside the rate range of the unit, particularly on the low
side.
3. On varying loads, a certain amount of load regulation may be mixed with the line voltage regu-
lating action. See “6.2 Load Regulation”.
Output voltage is very low (20–60 V)
1. Unsuspected or unplanned overloads of substantial size may occur intermittently (motor-
starting currents, solenoid inrush currents, etc.). See “6.8 Current Limitations”.
2. One or more capacitors in the regulator may be defective.
No output voltage
1. Check power source breakers or fuses.
2. Check input switch.
3. Check continuity between input terminals, and also between output terminals.
Transformer operating temperature
1. The transformer used in the unit is designed to operate at high ux density and relatively high
temperatures. After connection to the line for 30 minutes or so, the transformer core structure
may be too hot to touch with your bare hands. This is normal and should not cause concern.
Unit is operating, but does not appear to
have the correct output
The steps below will usually establish whether the apparent poor performance is due to a fault in
the unit or to some peculiarity of the working load.
1. Disconnect the working load.
2. Connect a dummy load of lamps, heaters, or other resistive loads (substantially equal to the
full load rating of the regulator) directly across the output terminals.
3. Measure the output voltage of the regulator (using a true RMS type voltmeter) directly across
the output terminals.
Support
Please contact SolaHD Technical Support at 1.800.377.4384/1.847.268.6651 or by e-mail at [email protected] for further
assistance.
7.0 Service & Maintenance
12 | CVS HARDWIRED SERIES USER MANUAL
Table 15: General Specifications
Phase Single
Frequency 60 Hz
Output Voltage Regulation ±1% for an input line variation of +10% to -20%
Output Harmonic Distortion Less than 3% total RMS content at full load
Efficiency Up to 92% at full load (typical) – model dependent
Noise Reduction Common mode noise rejection exceeds 120 dB; Transverse noise rejection exceeds 60 dB
Voltage Surge Suppression Meets ANSI/IEEE C62.41 Category A & B waveforms (formerly IEEE 587-1980)
Ambient Temperature Operating: -20°C to +50°C; Storage: -20°C to +85°C
Humidity <95% non-condensing
Directives RoHS complaint
Certifications
UL 1012, CSA C22.2 No. 107.1
Model Certification
23-13-030-2
cULus
23-13-060-2
23-22-112-2
23-23-125-8
23-23-150-8
23-23-220-8
23-23-230-8
23-23-250-8
23-28-275-6
Warranty 10 year limited warranty
9.0 Specifications
10.0 Warranty & Support
10.1 Warranty Information
Please refer to the “Terms & Conditions of Sale”.
10.2 Technical Support
Phone: 1.800.377.4384 or 1.847.268.6651
Web site: www.solahd.com
1.800. 377.4384 (US) • 1.847.268.6651 (International) • www.solahd.com
P/N: A272-283 Rev. 2 8/16
Série CVS câblée – 60 Hz
Manuel d’utilisation
16 | MANUEL D’UTILISATION DE LA SÉRIE CVS CÂBLÉE
Sommaire
1.0Consignes de sécurité importantes ....................................................................................................................... 16
2.0 Définitions des avertissements .............................................................................................................................. 16
3.0 Introduction ............................................................................................................................................................ 16
4.0 Instructions d’installation ....................................................................................................................................... 16
4.1 Réception ............................................................................................................................................................................... 16
4.2 Montage et ventilation ............................................................................................................................................................ 16
4.3 Dimensions et caractéristiques physiques ............................................................................................................................. 17
4.4 Branchements électriques ...................................................................................................................................................... 19
5.0 Branchements en parallèle et branchements triphasés ....................................................................................... 22
5.1 Fonctionnement en parallèle .................................................................................................................................................. 22
5.2 Fonctionnement en branchement triphasé ............................................................................................................................ 22
6.0Remarques et informations sur le fonctionnement............................................................................................... 23
6.1 Vérications à l’aide de voltmètres ......................................................................................................................................... 23
6.2 Régulation de la charge .......................................................................................................................................................... 23
6.3 Effets du facteur de puissance de charge .............................................................................................................................. 23
6.4 Utilisation avec des alimentations à découpage .................................................................................................................... 23
6.5 Effets de la fréquence ............................................................................................................................................................. 23
6.6 Temps de réponse .................................................................................................................................................................. 23
6.7 Caractéristiques de l’entrée ................................................................................................................................................... 23
6.8 Limitations du courant ............................................................................................................................................................ 24
6.9 Utilisation avec des charges de moteur ................................................................................................................................. 24
7.0 Dépannage et entretien .......................................................................................................................................... 24
7.1 Dépannage et entretien .......................................................................................................................................................... 24
7.2 Remplacement des condensateurs sur place ........................................................................................................................ 24
8.0 Dépannage ............................................................................................................................................................. 24
9.0 Spécifications ......................................................................................................................................................... 25
10.0 Garantie et assistance ......................................................................................................................................... 25
10.1 Informations relatives à la garantie ....................................................................................................................................... 25
10.2 Assistance technique ........................................................................................................................................................... 25
Bien que toutes les précautions possibles aient été prises pour garantir l’exactitude et l’exhaustivité de ce manuel, Appleton Group, LLC. décline toute responsabilité
quant aux dommages résultant de l’utilisation de ces informations ou aux erreurs ou omissions éventuelles. Les logos SolaHD et Emerson sont déposés auprès du
bureau des brevets et des marques déposées des États-Unis (U.S. Patent and Trademark Ofce). Tous les autres noms de produits ou de services appartiennent à leurs
propriétaires respectifs. ©2016 Appleton Group, LLC. Tous droits réservés. Les spécications sont sujettes à modication sans préavis.
MANUEL D’UTILISATION DE LA SÉRIE CVS CÂBLÉE | 17
1.0Consignes de sécurité importantes
Lire l’intégralité des instructions relatives à la sécurité, l’installation et le fonctionnement avant d’essayer d’installer ou d’utiliser
l’appareil.
!
DANGER! Des tensions élevées sont présentes dans l’appareil. Ne pas toucher l’intérieur lorsqu’il est sous tension.
Cet appareil contient des pièces ne pouvant pas être réparées par l’utilisateur.
2.0 Définitions des avertissements
!
DANGER! Signale une situation de danger imminent qui entraînera des blessures graves, voire mortelles, si elle n’est pas
évitée. L’emploi de ce terme est limité aux situations les plus extrêmes.
!
MISE EN GARDE ! Indique une situation potentiellement dangereuse susceptible d’entraîner des blessures graves, voire
mortelles, si elle n’est pas évitée.
!
ATTENTION! Signale une situation de danger potentiel susceptible d’entraîner des blessures légères ou modérées si elle
n’est pas évitée. Ce terme peut aussi servir à mettre en garde contre des pratiques dangereuses.
3.0 Introduction
CVS de SolaHD assure la régulation de la tension et isole les bruits de mode transversal et commun pour n’importe quel type de
charge. Il élimine également les transitoires des appareils ferrorésonants, protège contre les surcharges et sert de ligne dédiée. Il
constitue le parfait équipement en matière de conditionnement d’alimentation en courant alternatif.
4.0 Instructions d’installation
4.1 Réception
Lors de la réception de l’unité, l’inspecter immédiatement pour identier tout signe de dommages pendant le transport ou de
manutention inadéquate. Si l’appareil est endommagé, prendre une photo de la partie endommagée, en informer le transporteur
et contacter un représentant SolaHD local.
4.2 Montage et ventilation
Ces appareils sont destinés à être utilisés dans un environnement intérieur où l’humidité et la température sont contrôlées. Monter
l’appareil en position horizontale ou verticale. Il doit être installé à un emplacement ne présentant aucun risque de contact avec la
surface chaude du transformateur. En cas d’installation à la verticale (parex., contre un mur), consulter le tableau1 pour choisir les
éléments de xation en acier. Le compartiment de câblage doit être orienté vers le haut.
Tableau 1: Éléments de fixation
VA (MCR) Vis à tête fendue en acier inoxydable (diamètre miminal)
120 VA Vis mécaniques n° 10
250 VA Boulons 1/4 in.
500–1000 VA Boulons 5/16 in.
1500–10000 VA Boulons 3/8 in.
15000 VA Boulons 1/2 in.
Tous les régulateurs produisent une grande quantité de chaleur, et leur refroidissement s’effectue par convexion naturelle. Il est
important de ne pas obstruer les prises d’air de ventilation. Éviter de monter l’appareil dans un espace restreint ou mal aéré,
sauf si des dispositions spéciales ont été prises pour la ventilation. Pour obtenir une ventilation adéquate, prévoir un dégagement
d’au moins 12pouces au-dessus de l’appareil et de 6pouces sur chaque côté.
18 | MANUEL D’UTILISATION DE LA SÉRIE CVS CÂBLÉE
4.3 Dimensions et caractéristiques physiques
Tableau 2: Dimensions—Figure 1
Hz
Référence
catalogue
Dimensions en in [mm,]
Poids à l’ex-
pédition
lb [kg]
A B C D E F G H
60 23-13-030-2 6,12 [155,4] 5,19 [131,8] 3,47 [88,1] 4,00 [101,6] 3,50 [88,9] 3,00 [76,2] 1,75 [44,4]
0,22 x 0,59
[5,6 x 15,0]
7,0 [3,2]
60 23-13-060-2 6,94 [176,3] 5,19 [131,8] 3,47 [88,1] 4,00 [101,6] 3,50 [88,9] 3,00 [76,2] 1,75 [44,4]
0,22 x 0,59
[5,6 x 15,0]
9,0 [4,1]
60 23-22-112-2 8,12 [206,2] 5,19 [131,8] 3,47 [88,1] 4,00 [101,6] 3,50 [88,9] 3,00 [76,2] 2,44 [62,0]
0,22 x 0,59
[5,6 x 15,0]
13,0 [5,9]
60 23-23-125-8 10,50 [266,7] 7,56 [192,0] 4,75 [120,6] 5,63 [143,0] 4,75 [120,6] 4,12 [104,6] 3,03 [77,0]
0,31 x 0,69
[7,9 x 17,5]
28,0 [12,7]
60 23-23-150-8 13,00 [330,2] 6,50 [165,1] 8,12 [206,2] 9,00 [228,6] 8,12 [206,2] 5,62 [142,7] 3,06 [77,7]
0,38 x 0,81
[9,7 x 20,6]
37,0 [16,8]
60 23-23-210-8 17,25 [438,2] 6,81 [173,0] 8,12 [206,2] 9,00 [228,6] 8,12 [206,2] 5,62 [142,7] 5,25 [133,4]
0,38 x 0,81
[9,7 x 20,6]
63,0 [28,6]
Tableau 3: Dimensions—Figure 2
Hz
Référence
catalogue
Dimensions en in [mm,]
Poids à
l’expédition
lb [kg]
A B C D E F G H
60 23-23-220-8 17,58 [446,5] 9,44 [239,8] 10,56 [268,2] 12,75 [323,8] 11,75 [298,5] 3,88 [98,6] 5,19 [131,8]
0,44 x 0,69
[11,2 x 17,5]
109,0 [49,4]
60 23-23-230-8 18,96 [481,6] 9,44 [239,8] 10,56 [268,2] 12,75 [323,8] 11,75 [298,5] 5,25 133,4] 5,19 [131,8]
0,44 x 0,69
[11,2 x 17,5]
142,0 [64,4]
60 23-23-250-8 28,53 [724,7] 9,44 [239,8] 10,56 [268,2] 12,75 [323,8] 11,75 [298,5] 8,25 [209,5] 8,88 [225,6]
0,44 x 0,69
[11,2 x 17,5]
222,0 [100,7]
FIGURE 1
FIGURE 2
MANUEL D’UTILISATION DE LA SÉRIE CVS CÂBLÉE | 19
Tableau 4: Dimensions—Figure 3
Hz
Référence
catalogue
Dimensions en in [mm,]
Poids à
l’expédition
lb [kg]
A B C D E F G H
60 23-28-275-6 26,91 [683,5] 9,27 [235,6] 23,55 [598,2] 25,81 [655,6] 24,81 [630,2] 6,62 [168,1] 8,88 [225,6]
0,44 x 0,69
[11,2 x 17,5]
365,0 [165,6]
FIGURE 3
20 | MANUEL D’UTILISATION DE LA SÉRIE CVS CÂBLÉE
4.4 Branchements électriques
Tous les appareils câblés doivent être installés conformément aux codes électriques nationaux et locaux.
FIGURE 4
Tableau 5: Raccordements électriques—Figure 4
Référence catalogue Tension primaire Interconnexion Brancher les câbles à
23-13-030-2 120 H3 et H4 ne sont pas utilisés H1 et H2
23-13-060-2 120 H3 et H4 ne sont pas utilisés H1 et H2
23-22-112-2
120
H1 à H3
H2 à H4
H1 et H4
240 H2 à H3 H1 et H4
23-28-275-6
240
H1 à H3
H2 à H4
H1 et H4
480 H2 à H3 H1 et H4
Référence catalogue Tension secondaire Interconnexion Brancher les câbles à
23-13-030-2 120 --- X1 et X2
23-13-060-2 120 --- X1 et X2
23-22-112-2 120 --- X1 et X2
23-28-275-6
120 --- X1 et X2 OU X3 et X2
240 --- X1 et X3
REMARQUE: Secondaires ne sont pas ancrées. Terrain X2 en vertu du code.
Tableau 6: Paramètres du produit
Référence catalogue VA
Sortie en BTU à charge maximale,
temp. ambiante de +40°C
23-13-030-2 30 60
23-13-060-2 60 85
23-22-112-2 120 136
23-28-275-6 7500 2407
Tableau 7: Fusibles et câblage
Référence
catalogue
Protection exigée du circuit/calibre minimal des câbles à 90°C Calibre minimal des câbles à 90°C
Tension d’entrée Tension de sortie
95–130 175–235 190–260 380–520 475–650 120 208 240
23-13-030-2 1 A/14 AWG --- --- --- --- 14 AWG --- ---
23-13-060-2 2 A/14 AWG --- --- --- --- 14 AWG --- ---
23-22-112-2 3 A/14 AWG --- 3 A/14 AWG --- --- 14 AWG --- ---
23-28-275-6 --- --- 60 A/6 AWG 30 A/10 AWG --- 4 AWG 8 AWG 8 AWG
Tension d’entrée Inférieure Tension d’entrée Supérieure
Sortie Unique Sortie de Trois Fils
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

SolaHD CVS Hardwired Series 60 Hz Le manuel du propriétaire

Taper
Le manuel du propriétaire

dans d''autres langues