Anybus AB7316 Guide d'installation

Taper
Guide d'installation
1
3
5
2
4
6
Bus ReadyBus Error
HW Settings StatusProcessing
Device StatusCAN Subnet Status
Modbus RTU
Connector
LED Ind.
Switch 3 - 4, Parity
Switch 5,
Physical Interface
Switch 1 - 7,
Node Address
Switch 8,1,2
Baud Rate
SP1311, rev 2.20, AB7316 www.anybus.com
Module Front
Bottom View
Accessories Checklist
The following items are required for installaƟ on:
• Anybus Con guraƟ on Manager - Communicator CAN (available at
www.anybus.com)
CAN cable (included D-sub can be used)
USB cable (type B) for con guraƟ on download
Modbus RTU cable (not included)
Modbus Notes:
Modbus start address for input registers is 1 (data from CAN to
Modbus). Modbus start address for holding registers is 1025 (data
from Modbus to CAN).
If the physical interface is RS485, check that the Modbus cables
are terminated correctly.
Installation and Startup Summary
Build the con guraƟ on in the Anybus Con guraƟ on Manager.
Set the Modbus switches to the desired values.
Mount the Communicator at its proper posiƟ on.
Connect the USB, Modbus and CAN cables (if needed, use cables
with terminaƟ ons or add terminaƟ ons).
Power up the module and download the con guraƟ on.
Remove the USB cable.
Further informaƟ on and documents about this product can be found at
the product pages on www.anybus.com.
Technical Details
• Power supply:
24 V DC (-10% to +10%).
• Power consumpƟ on:
Maximum power consumpƟ on is 250 mA @ 24 V DC.
Typical power consumpƟ on: 100 mA @ 24 V DC.
• ProtecƟ ve Earth (PE):
Internal connecƟ on to PE via DIN-rail.
Note: Make sure the DIN-rail is properly connected to PE.
LED Indicators
LED no Indication Meaning
1 (Bus Error) Off
Red
Normal operation
Bus Error
2 (Bus Ready) Off
Green
Red
No power
Bus ready
Bus timeout error
3 (Processing) Off
Flashing green
No query is currently being processed
Processing query
4 (HW Settings
Status)
Off
Red
Using switch settings, normal operation
Not con gured. Operating at 19200 bps. Will only
respond to broadcast messages.
5 (CAN Subnet
Status)
Off
Green
Flashing red
Red
Power off/no CAN communication
Running with no transaction errors/timeout
Transaction error/timeout or subnetwork stopped
Fatal error
6 (Device Status) Off
Alternating red/green
Green
Flashing green
Red
Power off/initializing
Invalid or missing con guration
Run
Idle
Fatal error
A
B
1
5
6
9
CAN Connector
Pin no. Description
2 CAN_L
5 Shield
7 CAN_H
3, 6 CAN_GND
1, 4, 8, 9 (not connected)
USB port:
Connect a PC to the
USB port for rm-
ware upgrades.
Power:
A. +24 V DC
B. GND
Modbus Support
Technical quesƟ ons regarding the Modbus RTU eldbus system should
be addressed to the Modbus IDA organizaƟ on.
Online: www.modbus-ida.org
For maintenance and support, contact the HMS support department.
Contact informaƟ on is available at the support pages at
www.anybus.com.
Modbus RTU Connector
Pin no Name Function
2 RS232 - Tx Transmit signal
3 RS232 - Rx Receive signal
5 GND Signal ground
6 +5 V Power supply
7 RS485 D0
8 RS485 D1
Casing PE
1, 4, 9 - (not connected)
51
69
Anybus® CommunicatorTM CAN - Modbus RTU
INSTALLATION SHEET
HMS Industrial Networks AB
Box 4126
300 04 Halmstad, Sweden
Con guration Switches
NOTE: Changes to the con guration switches will only take effect
after the gateway has been restarted.
The rst 7 switches are used to set the node ID, using binary format.
Sw.
1
Sw.
2
Sw.
3
Sw.
4
Sw.
5
Sw.
6
Sw.
7Node ID
64 32 16 8 4 2 1
OFF OFF OFF OFF OFF OFF OFF (invalid)
OFF OFF OFF OFF OFF OFF ON 1
... ... ... ... ... ... ...
ON ON ON ON ON ON ON 127 (64+32+16+8+4+2+1)
The remaining switches are used to set the baud rate, the parity and
stop bits, and the physical interface type. Bold text = default value.
Sw.
8
Sw.
1
Sw.
2Baud rate
OFF OFF OFF (invalid)
OFF OFF ON 1200 bps
OFF ON OFF 2400 bps
OFF ON ON 4800 bps
ON OFF OFF 9600 bps
ON OFF ON 19200
bps
ON ON OFF 38400 bps
ON ON ON 57600 bps
Sw.
3
Sw.
4Parity Stop bits
OFF OFF (invalid) (invalid)
OFF ON None 2
ON OFF Even 1
ON ON Odd 1
Sw.
5Interface
OFF RS485
ON RS232
Anybus® CommunicatorTM CAN
INSTALLATION SHEET
UL Certi cation
This product is in accordance with the EMC directive 2014/30/EU
through conformance with the following standards:
EN 61000-6-4 (2007)
Emission standard for industrial environment
EN 55016-2-3, Class A (2010)
EN 55022, Class A (2011)
EN 61000-6-2 (2005)
Immunity for industrial environment
EN 61000-4-2 (2009)
EN 61000-4-3 (2006)
EN 61000-4-4 (2012)
EN 61000-4-5 (2014)
EN 61000-4-6 (2014)
EMC Compliance (CE)
Warnings
WARNING - EXPLOSION HAZARD - SUBSTITION OF ANY
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2.
WARNING - EXPLOSION HAZARD - WHEN IN HAZARD-
OUS LOCATIONS, TURN OFF POWER BEFORE REPLAC-
ING OR WIRING MODULES.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT WHILE THE CURCUIT IS LIVE OR UNLESS
THE AREA IS KNOWN TO BE FREE OF IGNITABLE CON-
CENTRATIONS.
WARNING - EXPLOSION HAZARD - THE USB CONNEC-
TOR IS NOT FOR USE IN HAZARDOUS LOCATIONS AND
FOR TEMPORARY CONNECTION ONLY. DO NOT USE,
CONNECT OR DISCONNECT UNLESS THE AREA IS
KNOWN TO BE NONHAZARDOUS. CONNECTION OR DIS-
CONNECTION IN AN EXPLOSIVE ATMOSPHERE COULD
RESULT IN AN EXPLOSION.
WARNING - INSTALL IN AN ENCLOSURE CONSIDERED
REPRESENTATIVE OF THE INTENDED USE.
ATEX Certi cation
1
2
1
2
DIN Rail Mounting
To mount the gateway on a DIN
rail, rst press it downwards (1)
to compress the spring in the rail
mechanism, then push it against
the rail as to make it snap on (2).
To dismount the gateway, push it
downwards (1) and pull it out from
the rail (2).
Further information and documents about this product can be
found at the product pages on www.anybus.com.
HMS Industrial Networks AB
Box 4126
300 04 Halmstad, Sweden
Attention!
ATTENTION – RISQUE D’EXPLOSION – LE
REMPLACEMENT DE TOUT COMPOSANTS INVALIDE LA
CERTIFICATION CLASS I, DIVISION 2.
ATTENTION – RISQUE D’EXPLOSION – EN ZONE
EXPLOSIVE, VEUILLEZ COUPER L’ALIMENTATION
ÉLECTRIQUE AVANT LE REMPLACEMENT OU LE
RACCORDEMENT DES MODULES.
ATTENTION – RISQUE D’EXPLOSION – NE PAS
DÉCONNECTER L’ÉQUIPEMENT TANT QUE
L’ALIMENTATION EST TOUJOURS PRÉSENTE OU QUE LE
PRODUIT EST TOUJOURS EN ZONE
EXPLOSIVE ACTIVE.
ATTENTION – RISQUE D’EXPLOSION – LE CONNECTEUR
USB N’EST PAS FAIT POUR UN USAGE EN MILIEU
EXPLOSIF. NE PAS, BRANCHER ET DEBRANCHER
SANS SAVOIR SI LA ZONE N’EST PAS IDENTIFIEE NON
EXPLOSIVE. BRANCHER OU DEBRANCHER EN ZONE
EXPLOSIVE PEUT ENTRAINER UNE EXPLOSION.
AVERTISSEMENT – INSTALLER DANS UNE ARMOIRE
VERROUILLEE VALIDANT L’ACTE VOLONTAIRE
D’UTILISATION.
Additional Installation and Operating Instructions
This equipment requires a regulated 24 V (21.6 V to 26.4 V) DC
power source
Field wiring terminal markings (wire type (Cu only, 14-30 AWG))
Use 60/75 or 75 °C copper (Cu) wire only.
Terminal tightening torque: 5–7 lb-in (0.5–0.8 Nm)
Use in Overvoltage Category I Pollution Degree 2 Environment
conforming to EN 60664-1.
Operating temperature/Surrounding temperature:
-25 to +55 °C @ 250 mA @ 24 V DC
Maximum surface temperature: 135 °C
Pressure: 850–1050 millibar (85–105 kPa)
This product is designed to safely operate in class I, division 2 Haz-
ardous location according to ANSI/ISA 12.12.01-2013 and category 3,
zone 2 according to EN 60079-0:2012 and EN 60079-15:2010.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C
AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS
LOCATIONS ONLY.
To comply with ATEX directives, the equipment must be installed
within an IP54 enclosure and must be installed with a transient sup-
pressor on the supply that does not exceed 140 % (33.6 V DC) of the
nominal rated supply voltage.
  • Page 1 1
  • Page 2 2

Anybus AB7316 Guide d'installation

Taper
Guide d'installation

dans d''autres langues