QUICK START GUIDE
E3 Dual Ethernet I/O Module
June 1, 2016 - LP0975A
OVERVIEW
These modules provide simple and secure remote
monitoring for sites located in harsh environments.
Offering the low cost per I/O point and rugged
environmental ratings, they are ideal for both control
rooms and extreme locations across industries that
include oil & gas, power & energy, transportation,
mining, and water/wastewater.
This guide covers initial configuration for the E3
Modules.
FEATURES
Fle
xible mix of I/O Channels support all instrumentation needs
Dual independent Ethernet™ ports enable flexible networking
Extensive health diagnostics and reporting reduce downtime
Rugged design supports extreme temperatures and Class I, Div 2
Marine and of
fshore tested and/or verified to meet standards such as
ABS, DNV 2.4 and LLoyds.
DATA INTERFACES
Ethernet: Dual 10/100 Mbp
s Auto-sensing Female RJ45 port
USB: USB 2.0 Type B Female
GETTING STARTED
1. Mount the Hardware
These I/O modules snap onto standard DIN-Rail in the typical fashion.
Alternatively they can be mounted directly to any flat surface.
2. Connect Power
Connect 10-30 VDC power to the power input screws. A Class 2 power
source is recommended because it has built-in current limiting to protect
against short circuits. However, it is not required.
3. Connect I/O
Make your field wiring connections between the I/O module's screw ter-
minals and your peripheral equipment. Refer to the module's I/O wiring
guide and the remote equipment's user manuals for I/O connection
details.
4. Install Communication Wiring
Make the necessary Ethernet, USB, and/or RS485 communication connec-
tions between the I/O modules and other devices (such as a master I/O
polling device).
5. Set Configuration Jumpers
Remove the configuration door and move the Network Mode and DI COM
jumpers to the desired settings. Note that the Network Mode jumper is
found on the back of the configuration door and the DI COM jumper
resides inside the module.
6. Turn ON the Power
Turn on the 10-30 VDC power. Observe the status (OK) LED. Typically a
solid ON indicates proper operation. A blinking LED may indicate that the
unit needs to be configured. Please view the E3 I/O module manual for
detailed information on the LED status lights.
7. USB Driver Selecton
a. Install Crrimson 3.0 Gold Build 675 or later.
b. Go to the Start-Programs-Red Lion Controls-Drivers to find the E3 USB
Driver files.
c. Click on the file that matches your Windows operating system architec-
ture. Click E3 USB Driver (64-bit) for 64-bit versions of Windows® (this will
apply for most) or E3 USB Driver (32-bit) for 32-bit versions of Windows®.
Driver Selection (Windows 10®and Windows 7®)
8. USB Installation
a. When the windows security window asks “Would you like to install this
device software?” click Install.
b. Click Next when the device driver installation wizard starts.
c. When complete the installation wizard will indicate that the USB Serial
driv
er is ready to use.
Windows Security Window
d. Verify the USB Device Driver is completed.
USB Driver Installation Complete
e. Resume Installation as per the instructions in the Quick Start Guide.
CONNECT. MONITOR. CONTROL © 2015 Red Lion Controls. All Rights Reserved 2
LP0975A Quick Start Guide
9. Configure Using the Web Server
Alternatively, the web server embedded with the I/O module may be used
to make configuration changes in the I/O module. To access the web
server first, open a web browser (Internet Explorer®, Chrome™ or Firefo
supported). Enter the I/O module’s IP address into the web browser’s
address bar (default IP address from the factory is 192.168.1.21).
10. Test the Hardware
Use the Test I/O feature in the web server or Crimson software to verify
proper operation of all I/O modules in your system. Refer to the web
server or Crimson on-line help system for further instructions.
11. Configure your I/O Master
Refer to the user manual for your I/O master software or hardware on
how to configure and run Modbus or Sixnet protocol polling of these I/O
modules.
12. Additional Information / Technical Support
Visit our support page at www.redlion.net to access the module’s docu-
mentation, as well as configuration help, troubleshooting and firmware &
software updates. Or contact Technical Support at 1-877-432-9908 (inside
US) or +1(717)767-6511 (outside US), or [email protected].
DIMENSIONS
MOUNTING THE MODULE
SETUP IS COMPLETE
The E3 module should be ready for basic I/O gathering requirements. For more
advanced configuration, consult the support section on our website:
www.redlion.net
SPECIFICATIONS:
ENVIRONMENTAL
Power Supply voltage: 10-30 VDC
Input current requirement: 150-355mA @ 24 VDC typical with no loads
(See Hardware Manual for more details)
Operating Temperature: -40 to +75 ˚C (-40 to +85 ˚C Storage)
Humidity: 5 to 95% RH (non-condensing)
STANDARDS COMPLIANCE
ATEX/IECEx: EN/IEC 60079-0, -15 CE
Electrical Safety: UL 508, CSA C22.2/142, IEC61010-1, CE
EMI Emissions FCC part 15, ICES-003, Class A; EN-55022; EN6100-6-4; CE
EMC Immunity IEC61000-6-2; (EN61000-4-2,3,4,5,6,8); CE
Vibration: IEC60068-2-27
Shock: IEC60068-2-6
Hazardous locations:
ATEX/IECEx Zone 2 (except E3-16DIAC-1 and E3-16DORLY-1)
ANSI/ISA 12.12.01-2013 Edition (Class I, Div. 2, Groups A, B, C, and D),
CSA C22.2/213
EN 60079-0:2012+A11:2013
EN 60079-15:2010
IEC 60079-0 Ed. 6
IEC 60079-15 Ed. 4
Marine/Offshore: Tested and/or verified to meet standards such as ABS,
DNV 2.4 and Llo
yds
Construction: Aluminum base and steel cover with zinc coating. Dimen-
sions: 5.6" (144mm) x 5.3" (135mm) x 2.9" (74mm)
ETHERNET PORTS
Dual 10/100BaseTX (auto-detecting)
RJ45 (auto-crossover)
1500 Volts RMS 1 minute (60 Hz)
Less than 1 ms per message
Solid indicates link but no activity; Blinking indicates link and activity
Modes: Real-time Ring™ with recovery time of 5 ms per hop; Dual net-
work, each with unique MAC and IP address; Pass-through for daisy-chain-
ing the modules
RS485 SERIAL PORT
2-wire half-duplex
Up to 32 (full-load)
Up to 0.5 miles (baud rate dependent)
Protocols: Master and slave; Sixnet UDR and Modbus RTU / ASCII
USB PORT
Type B device
Inputs and Outputs
Varies by module. See hardware user manual for details.
CONDITIONS OF SAFE USE
The equipment shall only be used in an area of not more than pollution degree
2, as defined in EN/IEC 60664-1.
The equipment shall be installed in an enclosure that provides a degree of
pr
otection not less than IP 54 in accordance with IEC 60079-15.
Provision shall be made to prevent the rated voltage being exceeded by the
tr
ansient disturbances of more than 140% of the peak rated voltage.
Certificate number: DEMKO 15 ATEX 1526X
Protection method and marking string:
II 3 G Ex nA IIC T4 Gc
IECEx Certificate number: IECEX UL 15.0079X
IECEx Protection Method and marking string: Ex nA IIC T4 Gc
CONNECT. MONITOR. CONTROL © 2015 Red Lion Controls. All Rights Reserved 3
LP0975A Quick Start Guide
INSTALLATION AND HAZARDOUS AREA WARNINGS
These products should not be used to replace proper safety interlocking. No
software-based device (or any other solid-state device) should ever be designed
to be responsible for the maintenance of consequential equipment or personnel
safety. In particular, Red Lion Controls disclaims any responsibility for damages,
either direct or consequential, that result from the use of this equipment in any
application.
All power, input and output (I/O) wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the authority having
jurisdiction.
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
WARNING – EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS,
DISCONNECT POWER BEFORE REPLACING OR WIRING MODULES.
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS
POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE
NONHAZARDOUS.
These products are operator interface units to be used within control panels.
These devices are intended for use in Class I, Division 2, Hazardous Locations,
industrial control applications. The enclosure should all be suitable for the
location.
AVERTISSEMENTS POUR INSTALLATION ET ENDROITS DANGEREUX
Ces produits ne doivent pas être utilisés pour remplacer le verrouillage de
sécurité approprié. Aucun dispositif basé sur un logiciel (ou tout autre dispositif
à l'état solide) devraient jamais être conçus pour être responsable de l'entretien
de l'équipement consécutifs ou la sécurité du personnel. En particulier, Red Lion
décline toute responsabilité pour les dommages, directs ou indirects, résultant
de l'utilisation de cet équipement dans n'importe quelle application.
Tout courant, câblage entrée et sortie (I / O) doit être conforme aux méthodes
de câblage à la Classe I, Division 2 et conformément à l'autorité compétente.
AVERTISSEMENT – RISQUE D’EXPLOSION – LA SUBSTITUTION DE TOUT
COMPOSANT PEUT NUIRE À LA CONFORMITÉ DE CLASSE I, DIVISION 2.
AVERTISSEMENT – RISQUE D’EXPLOSION – LORSQUE DANS DES ENDROITS
DANGEREUX, DÉBRANCHEZ LE CORDON D'ALIMENTATION AVANT DE
REMPLACER OU DE BRANCHER LES MODULES.
AVERTISSEMENT – RISQUE D’EXPLOSION – NE DÉBRANCHEZ PAS
L'ÉQUIPEMENT À MOINS QUE L'ALIMENTATION AIT ÉTÉ COUPÉE OU QUE
L’ENVIRONNEMENT EST CONNU POUR ÊTRE NON DANGEREUX.
Ces produits sont des unités d'interface opérateur qui doivent être utilisés à
l'intérieur des panneaux de commande. Ces appareils sont destinés à une
utilisation en Classe I, Division 2, zones dangereuses, applications de contrôle
industriel. L'enclos doit être adapté à l’environnement.
VOLTAGE AND CURRENT CHART
Models Voltage Readings Current Ratings
E3-MIX24880-1 12-24Vdc 150 mA, (0.6A per channel, 4.8A max.)*
E3-MIX24882-1 12-24Vdc 190 mA, (0.6A per channel, 4.8A max.)*
E3-MIX20884-1 12-24Vdc 190 mA, (0.6A per channel, 4.8A max.)*
E3-32DI24-1 12-24Vdc 150 mA*
E3-16DI24-1 12-24Vdc 150 mA*
E3-32DO24-1 12-24Vdc 160 mA, (0.5A per channel, 8A max.)*
E3-16DO24-1 12-24Vdc 150 mA, (0.5A per channel, 8A max.)*
E3-32AI20M-1 12-24Vdc 150 mA*
E3-32AI10V-1 12-24Vdc 150 mA*
E3-8AO20M-1 12-24Vdc 310 mA*
E3-16AI20M-1 12-24Vdc 150 mA*
E3-16AI8AO-1 12-24Vdc 310 mA*
E3-16ISOTC-1 12-24Vdc 150 mA*
E3-16ISO20M-1 12-24Vdc 150 mA*
E3-10RTD-1 12-24Vdc 150 mA*
* All current ratings were measured at 24VDC.