Savant RPM-Q2PWL-01 Guide de référence

Taper
Guide de référence
009-1790-00 | 190221
1 of 2
Copyright © 2019
A
Color LCD
Displays energy usage, lighting load levels
and settings information
B
Inputs
Inputs should be sourced by a +/-24VDC
power supply such as the Schneider
electric QOPLPS.
C
Outputs
Both terminals connect to one Powerlink
breaker
D
Neutral Wire
Pigtail connector is for wiring to the
neutral bar
E
Reset Button
Press and Release: Change GUI screens.
Hold for 1.5 seconds: Device will enter
Configuration mode.
Hold for 4 seconds: Will reset the device.
F
Manual Load
Switch
Specifications
Environmental
Temperature 32° to 104° F (0° to 40° C)
Humidity 5% to 85% Relative Humidity (non-condensing)
Location Indoor Use Only
Dimensions
Height 1.48in (37.7mm)
Width 5.00in (127.0mm)
Depth 2.63in (66.8mm)
Maximum Power
Inputs
120V AC at 60 Hz, 20 Amps Max each.
Load Power
(Max)
2400VA each (20A Resistive Load)
Features of
Automatic
action
Type 1.B action
Recommended Load Center Type
All QO™ compatible lighting modules fit into ¾-inch load centers
Supported Load Types
Standard
Configuration
Relay on / o loads
Terminals
Screw Tighten
Torque
1.34 Nm
Wire /
Conductor
Type
Copper (Cu) only
Standards
Wireless
Bluetooth Low Energy (BLE);
2.4GHz radio frequency
Regulatory
Safety and
Emissions
FCC Part 15 | ICES 003 | UL
Contains:
FCC ID: 2AA9B04
IC: 12208A-04
RoHS Compliant
Single NC/NO Control Relay Module
Installation Manual
Product Description
The single NC/NO Control Relay companion module is designed
to control one Square D™ Powerlink™ Remote controlled circuit
breaker.
Dynamic Load Management
This relay module is an essential building-block within the Savant
critical load management architecture. It can dynamically switch
critical and non-critical loads on / o based upon previously set
parameters.
Key Features
Control capability for Powerlink Remote controlled circuit
breaker
Fits into QO™ compatible panels.
Communicates wirelessly over Bluetooth Low Energy.
Dynamic management of loads.
Color Display for easy identification and load status.
Reset button / Manual load switch.
Network Requirements
This relay module communicates over the BLE mesh network
using the 2.4GHz radio frequency back to the Savant Panel
Bridge Controller (PBC).
FCC and IC Identifier
This device electronically displays the FCC and ID identifier. This
information can be found on the device by doing the following:
Once the device has completely booted, press the pair button two
times.
Cet appareil ache électroniquement les identifiants FCC et ID. Ces
informations peuvent être trouvées sur le périphérique en procédant
comme suit:
Une fois le périphérique complètement démarré, appuyez deux fois
sur le bouton de paire.
A
B
C
D
E
F
Input B
Output B
Output A
Input A
009-1790-00 | 190221
2 of 2
Copyright © 2019
Installation
This relay module is designed to adhere to standard electrical installation practices. Installation is performed by a certified electrician.
Flexibility - These modules accommodates two single relay loads and can be installed in any panel configuration. These snap-in relay modules
consume less space than other specialty panelized lighting installations along with simplified load placement and load maintenance.
All RPE QO™ form factor lighting modules are compatible with Schneider Electric Square D™ QO™ load centers (breaker panels).
Install the Lighting Companion module into the approved breaker panel. Press firmly to ensure full connection into hot bus bar. Connect
Neutral Wire to the neutral bus bar.
Typical Application
1. Install the Lighting Companion module into the approved breaker panel. Press firmly to ensure full connection into hot bus bar. Connect
Neutral Wire to the neutral bus bar.
2. Connect both Output A and Output B of the NC/NO Control relay companion to the white control wire of the Powerlink Remote
controlled circuit breaker that this device will control.
3. Connect the +24VDC from Powerlink Power Source to Input A of the NC/NO Control relay companion as well as the red wire on the
Power link Remote controlled circuit breaker.
4. Connect the -24VDC from Powerlink Power Source to Input B of the NC/NO Control relay companion as well as the black wire on the
Power link Remote controlled circuit breaker.
5. Connect the appropriate load to the Powerlink Remote controlled circuit breaker load connector. (Appropriate load is based on max
load for the Powerlink Remote controlled circuit breaker)
  • Page 1 1
  • Page 2 2

Savant RPM-Q2PWL-01 Guide de référence

Taper
Guide de référence

dans d''autres langues