Simplicity OPERATOR'S/IPL MANUAL- GENERATOR, CRAFTSMAN, CSA MODEL- 030243-1 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur

Ce manuel convient également à

AC Generator
5600 Watt
Model No.
580.675611
Part No. 208433GS Draft - (09/19/2008)
Generator
Customer Helpline
1-800-222-3136
Operator’s Manual
HOURS: Mon. - Fri. 8 a.m. to 5 p.m. (CT)
Sears Canada, Inc.
Visit our Craftsman website: www.sears.ca
Safety
Assembly
Operation
Maintenance
Parts
Français, p. 36
AVERTISSEMENT
Avant d’utiliser ce produit, veuillez lire le
manuel et suivre toutes les directives
relatives à la sécurité et à l’utilisation.
WARNING
Before using this product, read this
manual and follow all Safety Rules
and Operating Instructions.
This generator is rated and certified to be compliant with CSA (Canadian Standards Association) standard C22.2 No. 100-04 (motors and
generators).
Les caractéristiques nominales et la certification de cette génératrice sont conformes à la norme C22.2 No. 100-04 (moteurs et génératrices)
de l’ACNOR (Association canadienne de normalisation).
2
TABLE OF CONTENTS
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY RULES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
FEATURES AND CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . 6
ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-14
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-19
STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SCHEMATIC/WIRING DIAGRAM. . . . . . . . . . . . . . . . . . 22-23
REPLACEMENT PARTS. . . . . . . . . . . . . . . . . . . . . . . . . 24-33
EMISSIONS SYSTEM WARRANTY . . . . . . . . . . . . . . . . 34-35
FRANÇAIS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-59
HOW TO ORDER PARTS . . . . . . . . . . . . . . . . . . . BACK PAGE
ONE-YEAR FULL WARRANTY ON CRAFTSMAN GENERATOR
If this generator fails due to a defect in material or workmanship within one year from the date of purchase, return it to any
Sears store, other Craftsman outlet, or Sears Parts & Repair Center in the United States or Canada for free repair (or
replacement if repair proves impossible).
Additional One-Year Limited Warranty on Craftsman Generator
For the second year from the date of purchase, if any part of this generator fails due to a defect in material or workmanship, a
new part will be supplied free of charge. You must pay the labor cost if you wish to have it installed.
All warranty coverage applies for only 90 days from date of purchase if this generator is ever used for commercial or rental
purposes.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Sears, Roebuck and Co., Hoffman Estates, IL 60179
Sears Canada Inc., Toronto, Ontario, Canada M5B 2B8
WARRANTY
© Sears Brands, LLC
3
SAFETY RULES
Read this manual carefully and become familiar
with your generator. Know its applications, its
limitations, and any hazards involved.
Important Safety Information
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator unsafe.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol may
be used to represent the type of hazard. The signal word
NOTICE is used to address practices not related to personal
injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE address pratices not related to personal injury.
Fire
Explosion
Toxic Fumes
Hot Surface
Moving Parts
Electrical Shock
Kickback
Flying Objects
Hazardous Chemical
Operator’s Manual
WARNING: Running engine gives off carbon
monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
Operate generator ONLY outdoors.
Install a battery operated carbon monoxide alarm near the
bedrooms.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.
DO NOT start or run engine indoors or in an enclosed area,
(even if windows and doors are open), including the generator
compartment of a recreational vehicle (RV).
WARNING: The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING: Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects or other
reproductive harm. Wash hands after handling.
DANGER: Contents are harmful or fatal if swallowed.
Avoid contact to eyes, skin or clothing.
DO NOT take internally. Avoid breathing
the mist or vapor. Overexposure to eyes
or skin can cause irritation. Keep stabilizer out of the
reach of children.
Fuel stabilizer is a hazardous chemical.**
Fresh Start® fuel cap is designed to hold a cartridge which
contains fuel stabilizer.
If SWALLOWED, call physician immediately. DO NOT induce
vomiting. If inhaled, remove to fresh air. In case of eye or skin
contact, flush with water for 15 minutes.
Store unopened cartridges in a cool, dry, well ventilated area.
Keep open cartridge in fuel cap, and fuel cap closed on fuel tank
when not in use.
In the case of an emergency, contact a physician immediately
and call 1-800-424-9300 for material safety information.
**Fuel stabilizer contains: 2,6-di-tret-butylphenol (128-39-2) and aliphatic petroleum
distillate (64742-47-8).
4
WARNING:
Generator produces hazardous voltage.
Failure to isolate generator from power utility can
result in death or injury to electric utility workers
due to backfeed of electrical energy.
When using generator for backup power, notify utility company.
Use approved transfer equipment to isolate generator from
electric utility.
Use a ground fault circuit interrupter (GFCI) in any damp or
highly conductive area, such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or children to operate or
service generator.
WARNING: Starter cord kickback (rapid retraction) can
result in bodily injury. Kickback will pull hand and
arm toward engine faster than you can let go.
Broken bones, fractures, bruises, or sprains
could result.
When starting engine, pull cord slowly until resistance is felt
and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices plugged in
and turned on.
WARNING: Fuel and its vapors are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
WHEN ADDING OR DRAINING FUEL
Turn generator OFF and let it cool at least 2 minutes before
removing fuel cap. Loosen cap slowly to relieve pressure in
tank.
Fill or drain fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel expansion.
If fuel spills, wait until it evaporates before starting engine.
Keep fuel away from sparks, open flames, pilot lights, heat, and
other ignition sources.
DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
Ensure spark plug, muffler, fuel cap, and air cleaner are in place.
DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
DO NOT tip engine or equipment at angle which causes fuel to
spill.
This generator is not for use in mobile equipment or marine
applications.
WHEN TRANSPORTING OR REPAIRING EQUIPMENT
Transport/repair with fuel tank EMPTY or with fuel shutoff valve
OFF.
Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
Store away from furnaces, stoves, water heaters, clothes
dryers, or other appliances that have pilot light or other ignition
source because they can ignite fuel vapors.
WARNING:
This generator does not meet U. S. Coast Guard Regulation
33CFR-183 and should not be used on marine applications.
Failure to use the appropriate U. S. Coast Guard approved
generator could result in death or serious injury and/or property
damage.
WARNING: Contact with muffler area can result in
serious burns.
Exhaust heat/gases can ignite
combustibles, structures or damage
fuel tank causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 feet (152 cm) of clearance on all sides of
generator including overhead.
It is a violation of California Public Resource Code, Section
4442, to use or operate the engine on any forest-covered,
brush-covered, or grass-covered land unless the exhaust
system is equipped with a spark arrester, as defined in Section
4442, maintained in effective working order. Other states or
federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer
to obtain a spark arrester designed for the exhaust system
installed on this engine.
Replacement parts must be the same and installed in the same
position as the original parts.
NOTICE:
Exceeding generators wattage/amperage capacity
can damage generator and/or electrical devices connected to
it.
DO NOT exceed the generator’s wattage/amperage capacity. See
Don’t Overload Generator in the Operation section.
Start generator and let engine stabilize before connecting electrical
loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator before
stopping generator.
NOTICE:
Improper treatment of generator can damage it and
shorten its life.
Use generator only for intended uses.
If you have questions about intended use, ask dealer or contact
Sears.
Operate generator only on level surfaces.
DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
DO NOT insert any objects through cooling slots.
If connected devices overheat, turn them off and disconnect them
from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
This equipment is designed to be used with Sears authorized
parts ONLY. If equipment is used with parts that DO NOT comply
with minimum specifications, user assumes all risks and
liabilities.
5
WARNING: Unintentional sparking can result in fire or
electric shock.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
Disconnect the spark plug wire from the spark plug and place
the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
WARNING: Starter and other rotating parts can
entangle hands, hair, clothing, or accessories.
NEVER operate generator without protective housing or covers.
DO NOT wear loose clothing, jewelry or anything that may be
caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
CAUTION:
Excessively high operating speeds increase
risk of injury and damage to generator.
Excessively low speeds impose a heavy load.
DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at governed
speed.
DO NOT modify generator in any way.
6
KNOW YOUR GENERATOR
Read the Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator to familiarize yourself with the locations of various controls and
adjustments. Save this manual for future reference.
FEATURES AND CONTROLS
A - Spark Arrester Muffler — Exhaust muffler lowers engine
noise and is equipped with a spark arrester screen.
B - Fuel Tank — Capacity of five (5) U.S. gallons.
C - StatStation™ — Displays the electrical load on generator
based on output frequency. It also has a built in
maintenance reminder.
D - 120 Volt AC, 20 Amp, Duplex Receptacles — May be
used to supply electrical power for the operation of
120 Volt AC, 20 Amp, single phase, 60 Hz electrical,
lighting, appliance, tool and motor loads.
E - 120/240 Volt AC, 30 Amp Locking Receptacle — May be
used to supply electrical power for the operation of
120 and/or 240 Volt AC, 30 Amp, single phase, 60 Hz
electrical, lighting, appliance, tool and motor loads.
F - Oil Fill Cap — Check and add engine oil here. See page
17 for oil recommendations and filling instructions.
G - Double Pole Circuit Breaker (AC) — A double pole
circuit breaker is provided to protect all the receptacles
and generator against electrical overload.
H - Grounding Fastener — Consult your local agency having
jurisdiction for grounding requirements in your area.
J - Identification Label — Provides model, revision and
serial number of generator. Please have these readily
available when calling for assistance.
K - Air Cleaner — Protects engine by filtering dust and
debris out of intake air.
L - Choke Lever — Used when starting a cold engine.
M - Fuel Valve — Used to turn fuel supply on and off to
engine.
N - Recoil Starter — Used to start the engine.
P - On/Off Switch — Set this switch to "On" before using
recoil starter. Set switch to "Off" to switch off engine.
P
B
D
E
F
J
L
K
K
A
N
G
C
M
7
Your Craftsman generator requires some assembly and is
ready for use only after it has been properly serviced with the
recommended oil and fuel.
If you have any problems with the assembly of your
generator, please call the generator helpline at
1-800-222-3136.
Unpacking the Generator
1. Set the carton on a rigid flat surface.
2. Remove everything from carton except generator.
3. Open carton completely by cutting each corner from top
to bottom.
4. Leave generator on carton to install wheel kit.
Carton Contents
Check all contents against those listed below:
Main unit
Engine oil
Operator’s manual
Wheel kit
Adapter cord set
If any parts are missing or damaged, call the generator
helpline at 1-800-222-3136.
Install Wheel Kit
NOTE: Wheel kit is not intended for over-the-road use. DO
NOT tow this unit with a motorized vehicle.
You will need the following tools to install these components:
13mm wrenches
Socket wrench with a 13mm socket
Pliers
Safety glasses
Install the Wheel Kit as Follows:
IMPORTANT: Installing the wheel kit must be completed
prior to adding any oil or fuel.
1. Tip generator so that engine end is up.
2. Slide axle (B) through both mounting brackets.
3. Place a wheel (C) on each side as shown in A.
4. Place a washer (D) on axle and then place an e-ring (E)
in axle groove.
5. Install e-ring with pliers, squeezing from top of e-ring to
bottom of axle.
6. Repeat step 4 and 5 to secure second wheel.
7. Tip generator so that engine side is down.
8. Line up holes in support leg (F) with holes in generator
frame.
9. Attach support leg using 2 capscrews (M8 x 16 mm) (G)
and 2 hex nuts (H). Tighten with a 13mm socket wrench
and 13mm wrench.
10. Return generator to normal operating position (resting
on wheels and support leg).
ASSEMBLY
A
CAUTION:
E-rings can cause eye injury.
E-rings can spring back and become airborne
when installing or removing.
Always wear eye protection when installing/removing e-rings.
B
B
C
G
E
C
D
H
F
BEFORE STARTING THE GENERATOR
Add Engine Oil
1. Place generator on a flat, level surface.
2. Clean area around oil fill and remove yellow oil fill cap.
NOTE: See the section Oil to review oil recommendations.
Verify provided oil bottle is correct viscosity for current
ambient temperature.
3. Using oil funnel (optional), slowly pour contents of
provided oil bottle into oil fill opening.
NOTICE:
Improper treatment of generator can damage it and
shorten its life.
DO NOT attempt to crank or start the engine before it has been
properly serviced with the recommended oil. This may result in an
engine failure.
4. Replace oil fill cap and fully tighten.
Add Fuel
Fuel must meet these requirements:
Clean, fresh, unleaded gasoline.
A minimum of 87 octane/87 AKI (91 RON). High altitude
use, see High Altitude.
Gasoline with up to 10% ethanol (gasohol) or up to 15%
MTBE (methyl tertiary butyl ether) is acceptable.
NOTICE: Avoid generator damage.
Failure to follow Operator’s Manual for fuel
recommendations voids warranty.
DO NOT use unapproved gasoline such as E85.
DO NOT mix oil in gasoline.
DO NOT modify engine to run on alternate fuels.
To protect the fuel system from gum formation, mix in a fuel
stabilizer when adding fuel. See Storage. All fuel is not the
same. If you experience starting or performance problems
after using fuel, switch to a different fuel provider or change
brands. This engine is certified to operate on gasoline. The
emission control system for this engine is EM (Engine
Modifications).
1. Clean area around fuel fill cap, remove cap.
2. Slowly add regular unleaded fuel (A) to fuel tank (B). Be
careful not to overfill. Allow at least 1.5" of tank space
(C) for fuel expansion, as shown here.
3. Install fuel cap and wait for any spilled fuel to evaporate.
CAUTION! Alcohol-blended fuels (called gasohol, ethanol or
methanol) can attract moisture, which leads to separation and
formation of acids during storage. Acidic gas can damage the
fuel system of an engine while in storage.
To avoid engine performance issues, the fuel system should
be treated with a fuel preserver or emptied before storage of
30 days or longer. To protect the fuel system from gum
formation, use Briggs & Stratton FRESH START® fuel
stabilizer plus, or FRESH START continuous fuel preserver
(concentrated liquid cartridge). If fuel preserver is not used,
drain the fuel tank, start the engine and let it run until the fuel
lines and carburetor are empty. Use fresh fuel next season.
See Storage for additional information.
NEVER use engine or carburetor cleaner products in the fuel
tank as permanent damage may occur.
8
WARNING: Fuel and its vapors are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
WHEN ADDING FUEL
Turn generator OFF and let it cool at least 2 minutes before
removing fuel cap. Loosen cap slowly to relieve pressure in
tank.
Fill fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel expansion.
If fuel spills, wait until it evaporates before starting engine.
Keep fuel away from sparks, open flames, pilot lights, heat, and
other ignition sources.
DO NOT light a cigarette or smoke.
C
B
A
9
Fresh Start Fuel Cap
Adding fuel preserver helps keep fuel fresh and carburetors
clean for easier starting, all season long. This new fuel cap
automatically drips concentrated fuel preserver into your fuel
tank.
1. Place cartridge into fuel cap.
2. Push to “snap” cartridge into place.
3. Remove tab to expose membrane.
IMPORTANT: DO NOT remove the silver foil seal on the
opposite side of the cartridge.
4. Reinstall fuel cap on fuel tank.
5. Periodically check the cartridge to ensure there is still
fuel stabilizer inside. If it is empty, remove cartridge and
replace.
High Altitude
At altitudes over 5,000 feet (1524 meters), a minimum
85 octane / 85 AKI (89 RON) gasoline is acceptable. To
remain emissions compliant, high altitude adjustment is
required. Operation without this adjustment will cause
decreased performance, increased fuel consumption, and
increased emissions. See a qualified Sears dealer for high
altitude adjustment information. Operation of the engine at
altitudes below 2,500 feet (762 meters) with the high altitude
kit is not recommended.
DANGER: Contents are harmful or fatal if swallowed.
Avoid contact to eyes, skin or clothing.
DO NOT take internally. Avoid breathing
the mist or vapor. Overexposure to eyes
or skin can cause irritation. Keep stabilizer out of the
reach of children.
Fuel stabilizer is a hazardous chemical.**
If SWALLOWED, call physician immediately.
In the case of an emergency, contact a physician immediately
and call 1-800-424-9300 for material safety information.
**Fuel stabilizer contains: 2,6-di-tret-butylphenol (128-39-2) and aliphatic petroleum
distillate (64742-47-8).
HOW TO USE YOUR GENERATOR
If you have any problems operating your generator after
reading the manual, please call the generator helpline at
1-800-222-3136.
System Ground
The generator has a system ground that connects the
generator frame components to the ground terminals on the
AC output receptacles. The system ground is connected to
the AC neutral wire (the neutral is bonded to the generator
frame).
Special Requirements
There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.
In some areas, generators are required to be registered
with local utility companies.
If the generator is used at a construction site, there may
be additional regulations which must be observed.
Connecting to a Building’s Electrical System
Connections for standby power to a building’s electrical
system must be made by a qualified electrician. The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.
Generator Location
Generator Clearance
Place generator outdoors in an area that will not accumulate
deadly exhaust gas. DO NOT place generator where exhaust
gas (A) could accumulate and enter inside or be drawn into a
potentially occupied building. Ensure exhaust gas is kept
away from any windows, doors, ventilation intakes, or other
openings that can allow exhaust gas to collect in a confined
area. Prevailing winds and air currents should be taken into
consideration when positioning generator.
10
OPERATION
WARNING: Exhaust heat/gases can ignite
combustibles, structures or damage fuel tank
causing a fire.
Keep at least 5 ft. (152 cm) clearance on all sides of generator
including overhead.
WARNING:
Generator produces hazardous voltage.
Failure to isolate generator from power utility can
result in death or injury to electric utility workers
due to backfeed of electrical energy.
When using generator for backup power, notify utility company.
Use approved transfer equipment to isolate generator from
electric utility.
Use a ground fault circuit interrupter (GFCI) in any damp or
highly conductive area, such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or children to operate or ser-
vice generator.
A
11
To Start The Engine
Disconnect all electrical loads from the generator. NEVER
start or stop engine with electrical devices plugged in and
turned ON. Follow start instruction steps in numerical order:
1. Make sure unit is on a level surface.
IMPORTANT: Failure to start and operate unit on a level
surface will cause the unit not to start or shut down during
operation.
2. Turn red fuel valve to “On” position.
3. Place choke lever in “Choke” position.
4. Set On/Off switch to “On” position.
5. Grasp recoil handle and pull slowly until slight resistance
is felt. Then pull rapidly to start engine.
IMPORTANT: If engine floods, place choke lever in “Run
position and crank until engine starts.
6. Move choke lever to “Run” position a short distance at a
time over several seconds in warm weather or minutes
in cold weather. Let engine run smoothly before each
change. Operate with choke in “Run” position.
NOTE: If engine starts after 3 pulls but fails to run, or if unit
shuts down during operation, make sure unit is on a level
surface and check for proper oil level in crankcase. This unit
may be equipped with a low oil protection device. If so, oil
must be at proper level for engine to start.
Connecting Electrical Loads
1. Let engine stabilize and warm up for a few minutes after
starting.
2. Plug in and turn on the desired 120 and/or 240 Volt AC,
single phase, 60 Hz electrical loads.
NOTE:
DO NOT connect 240 Volt loads to the 120 Volt duplex
receptacles.
DO NOT connect 3-phase loads to the generator.
DO NOT connect 50 Hz loads to the generator.
DO NOT OVERLOAD THE GENERATOR. See Don’t
Overload Generator.
NOTICE:
Exceeding generators wattage/amperage capacity
can damage generator and/or electrical devices connected to
it.
DO NOT exceed the generator’s wattage/amperage capacity. See
Don’t Overload Generator in the Operation section.
Start generator and let engine stabilize before connecting electrical
loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator before
stopping generator.
On/Off Switch is shown
in On position
“Off”
Position
“On”
Position
WARNING: Starter cord kickback (rapid retraction) can
result in bodily injury. Kickback will pull hand and
arm toward engine faster than you can let go.
Broken bones, fractures, bruises, or sprains
could result.
When starting engine, pull cord slowly until resistance is felt
and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices plugged in
and turned on.
WARNING: Contact with muffler area can result in
serious burns.
Exhaust heat/gases can ignite
combustibles, structures or damage
fuel tank causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 feet (152 cm) of clearance on all sides of
generator including overhead.
It is a violation of California Public Resource Code, Section
4442, to use or operate the engine on any forest-covered,
brush-covered, or grass-covered land unless the exhaust
system is equipped with a spark arrester, as defined in Section
4442, maintained in effective working order. Other states or
federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer
to obtain a spark arrester designed for the exhaust system
installed on this engine.
Replacement parts must be the same and installed in the same
position as the original parts.
12
Stopping the Engine
1. Turn off and unplug all electrical loads from unit. NEVER
start or stop engine with electrical devices plugged in
and turned on.
2. Let engine run at no-load for two minutes to stabilize
unit’s internal temperatures.
3. Move On/Off switch to “Off” position.
4. Move fuel valve to “Off” position.
Warm Weather Operation
This generator engine is equipped with WeatherGuard, an
innovative feature to prevent carburetor icing in cold weather
conditions. WeatherGuard has been engineered to operate in
all weather conditions. However, product performance can be
increased when operating the generator solely in warm
weather by removing the WeatherGuard shield (A).
Remove the two nuts (B) and loosen the fastener (C) as
shown. Store shield and fasteners for future cold weather
operation.
WARNING:
Backfire, fire or engine damage could
occur.
DO NOT stop engine by moving choke control to “Choke
position ( ).
B
C
A
13
CORD SETS AND RECEPTACLES
Use only high quality, well-insulated, grounded extension
cords with the generator’s 120 Volt electrical receptacles.
Inspect extension cords before each use.
Check the ratings of all extension cords before you use them.
Extension cord sets used should be rated for 125 Volt AC
loads at 20 Amps or greater for most electrical devices.
Some devices, however, may not require this type of
extension cord. Check the operator’s manuals of those
devices for the manufacturer’s recommendations.
Keep extension cords as short as possible, preferably less
than 15 feet long, to prevent voltage drop and possible
overheating of wires.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater). You can use the same 4–wire cord if you plan to
run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 5,600 watts of power (5.6 kW) at
23.3 Amps for 240 Volts or two independent 120 Volt loads
at 23.3 Amps each. The outlet is protected by a double pole
rocker switch circuit breaker.
NOTICE:
Receptacles may be marked with rating value
greater than generator output capacity.
NEVER attempt to power a device requiring more amperage than
generator or receptacle can supply.
DO NOT overload the generator. See Don’t Overload Generator.
120 Volt AC, 20 Amp, Duplex Receptacles
Each duplex receptacle is protected against overload by a
double pole rocker switch circuit breaker.
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at
20 Amps of current. Use cord sets that are rated for 125 Volt
AC loads at 20 Amps (or greater). Inspect cord sets before
each use.
GENERATOR ADAPTER CORD SET
The generator comes with a 25’ generator adapter cord set
designed to provide two sets of 120 Volt, 20 Amp outlets
from one 120 Volt, 20 Amp duplex receptacle.
The maximum load on each outlet is 20 Amps. The maximum
total load on both black wire outlets or white stripe wire outlets
is 20 Amps. If an extension cord is used with adapter cord set,
be sure extension cord is rated for 125V at 20 Amps.
NOTE: Follow all safety precautions when connecting any
extension cord or device to the generator.
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
WARNING:
Overloaded electrical cords can overheat,
arc, and burn resulting in death, bodily injury,
and/or property damage.
ONLY use cords rated for your loads.
Follow all safeties on electrical cords.
14
DON’T OVERLOAD GENERATOR
Capacity
You must make sure your generator can supply enough rated
(running) and surge (starting) watts for the items you will
power at the same time. Follow these simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items. This is the
amount of power your generator must produce to keep
your items running.
3. Estimate how many surge (starting) watts you will need.
Surge wattage is the short burst of power needed to
start electric motor-driven tools or appliances such as a
circular saw or refrigerator. Because not all motors start
at the same time, total surge watts can be estimated by
adding only the item(s) with the highest additional surge
watts to the total rated watts from step 2.
Example:
Total Rated (Running) Watts = 3075
Highest Additional Surge Watts = 1800
Total Generator Output Required = 4875
NOTE: The rated (running) watts cannot exceed 5600. Also,
given the 5600 watt rated limit, additional surge (starting)
watts cannot exceed 8600.
Power Management
To prolong the life of your generator and attached devices, it
is important to take care when adding electrical loads to your
generator. There should be nothing connected to the
generator outlets before starting it's engine. The correct and
safe way to manage generator power is to sequentially add
loads as follows:
1. With nothing connected to the generator, start the
engine as described in this manual.
2. Plug in and turn on the first load, preferably the largest
load you have.
3. Permit the generator output to stabilize (engine runs
smoothly and attached device operates properly).
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
NEVER add more loads than the generator capacity. Take
special care to consider surge loads in generator capacity, as
described above.
*Wattages listed are approximate only. Check tool or
appliance for actual wattage.
Tool or Appliance
Rated (Running)
Watts
Additional Surge
(Starting) Watts
Window Air
Conditioner
1200 1800
Refrigerator 800 1600
Deep Freezer 500 500
Television 500
Light (75 Watts) 75
3075 Total
Running Watts
1800 Highest
Surge Watts
Wattage Reference Guide
Tool or Appliance
Rated*
(Running)
Watts
Additional
Surge
(Starting)
Watts
Essentials
Light Bulb - 75 watt 75
Deep Freezer 500 500
Sump Pump 800 1200
Refrigerator/Freezer - 18 cf 800 1600
Water Well Pump - 1/3 hp 1000 2000
Heating/Cooling
Window AC - 10,000 BTU 1200 1800
Window Fan 300 600
Furnace Fan Blower - 1/2 hp 800 1300
Kitchen
Microwave Oven - 1000 Watt 1000
Coffee Maker 1500
Electric Stove - Single Element 1500
Hot Plate 2500
Family Room
DVD/CD Player 100
VCR 100
Stereo Receiver 450
Color Television - 27 in 500
Personal Computer w/17 in moni-
tor
800
Other
Security System 180
AM/FM Clock Radio 300
Garage Door Opener - 1/2 hp 480 520
Electric Water Heater - 40 gallon 4000
DIY/Job Site
Quartz Halogen Work Light 1000
Airless Sprayer - 1/3 hp 600 1200
Reciprocating Saw 960 960
Electric Drill - 1/2 hp 1000 1000
Circular Saw - 7-1/4 in 1500 1500
Miter Saw - 10 in 1800 1800
Table Planer - 6 in 1800 1800
Table Saw/Radial Arm Saw - 10 in 2000 2000
Air Compressor - 1-1/2 hp 2500 2500
15
ENGINE TECHNICAL INFORMATION
This is a single cylinder, overhead valve(OHV), air cooled
engine. It is a low emissions engine.
In the State of California, Model Series 200000 engines are
certified by the California Air Resources Board to meet
emissions standards for 250 hours. Such certification does
not grant the purchaser, owner or operator of this engine any
additional warranties with respect to the performance or
operational life of this engine. The engine is warranted solely
according to the product and emissions warranties stated
elsewhere in this manual.
Power Ratings
The gross power rating for individual gas engine models is
labeled in accordance with SAE (Society of Automotive
Engineers) code J1940 (Small Engine Power & Torque
Rating Procedure), and rating performance has been
obtained and corrected in accordance with SAE J1995
(Revision 2002-05). Torque values are derived at 3060 RPM;
horsepower values are derived at 3600 RPM. Actual gross
engine power will be lower and is affected by, among other
things, ambient operating conditions and engine-to-engine
variability. Given both the wide array of products on which
engines are placed and the variety of environmental issues
applicable to operating the equipment, the gas engine will not
develop the rated gross power when used in a given piece of
power equipment (actual "on-site" or net power). This
difference is due to a variety of factors including, but not
limited to, accessories (air cleaner, exhaust, charging,
cooling, carburetor, fuel pump, etc.), application limitations,
ambient operating conditions (temperature, humidity,
altitude), and engine-to-engine variability. Due to
manufacturing and capacity limitations, Briggs & Stratton
may substitute an engine of higher rated power for this
Series engine.
This generator is rated and certified to be compliant with CSA
(Canadian Standards Association) standard C22.2 No. 100-04
(motors and generators).
PRODUCT SPECIFICATIONS
Generator Specifications
Starting Wattage . . . . . . . . . . . . . . . . . . . . 8600 Watts (8.6 kW)
Wattage . . . . . . . . . . . . . . . . . . . . . . . . . . 5600 Watts (5.6 kW)
AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120/240 Volts
AC Current
at 240 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.3 Amps
at 120 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46.6 Amps
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hz at 3600 rpm
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single Phase
Fuel Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 U.S. gallons
Engine Specifications
Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.12 in. (79 mm)
Stroke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.44 in. (62 mm)
Displacement . . . . . . . . . . . . . . . . . . . . . . . . 18.64 in. (305 cc)
Spark Plug
Type: . . . . . . . . . . . . . . Briggs & Stratton
491055 or 5066
Set Gap To: . . . . . . . . . . . . . . . . . . . . 0.030 inch (0.76 mm)
Armature Air Gap: . . . . . . . . . . 0.008-0.012 in. (0.20-0.30 mm)
Valve clearance with valve springs installed and piston 1/4 in.
(6 mm) past top dead center (check when engine is cold).
Intake . . . . . . . . . . . . . . . . . . . 0.004-0.006 in. (0.10-0.15 mm)
Exhaust . . . . . . . . . . . . . . . . . . 0.004-0.006 in. (0.10-0.15 mm)
Oil Capacity . . . . . . . . . . . . . . . . . . . .28 Ounces (0.8 Liters)
NOTE: For practical operation, the generator load should not
exceed 85% of rated wattage. Engine power will decrease
3-1/2% for each 1,000 feet (300 meters) above sea level and
1% for each 10° F (5.6° C) above 77° F (25° C). It should
operate satisfactorily at an angle up to 15°.
SPECIFICATIONS
16
MAINTENANCE
MAINTENANCE SCHEDULE
Follow the hourly or calendar intervals, whichever occurs
first. More frequent service is required when operating in
adverse conditions noted below.
1
Service more often under dirty or dusty conditions.
General Recommendations
Regular maintenance will improve the performance and
extend the life of the generator. See a Sears or other qualified
dealer for service.
The generator’s warranty does not cover items that have
been subjected to operator abuse or negligence. To receive
full value from the warranty, the operator must maintain
generator as instructed in this manual.
Some adjustments will need to be made periodically to
properly maintain your generator.
All service and adjustments should be made at least once
each season. Follow the requirements in the Maintenance
Schedule chart above.
NOTE: Once a year you should clean or replace the spark
plug and replace the air filter. A new spark plug and clean air
filter assure proper fuel-air mixture and help your engine run
better and last longer.
Emissions Control
Maintenance, replacement, or repair of the emissions con-
trol devices and systems may be performed by any non-
road engine repair establishment or individual. However,
to obtain ”no charge” emissions control service, the work
must be performed by a factory authorized dealer. See the
Emissions Warranty.
GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and
dry. Operate and store the unit in a clean dry environment
where it will not be exposed to excessive dust, dirt, moisture
or any corrosive vapors. Cooling air slots in the generator
must not become clogged with snow, leaves, or any other
foreign material.
Check the cleanliness of the generator frequently and clean
when dust, dirt, oil, moisture or other foreign substances are
visible on its exterior surface.
NOTE: DO NOT use a garden hose to clean generator. Water
can enter the engine fuel system and cause problems. In
addition, if water enters the generator through cooling air
slots, some of the water will be retained in voids and cracks
of the rotor and stator winding insulation. Water and dirt
buildup on the generator internal windings will eventually
decrease the insulation resistance of these windings.
Generator Cleaning
Daily or before use, clean accumulated debris from
generator. Keep linkage, spring and controls clean. Keep area
around and behind muffler free from any combustible debris.
Inspect cooling air slots and openings on the generator.
These openings must be kept clean and unobstructed.
Generator parts should be kept clean to reduce the risk of
overheating and ignition of accumulated debris.
Use a damp cloth to wipe exterior surfaces clean.
NOTICE:
Improper treatment of generator can damage it and
shorten its life.
DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
DO NOT insert any objects through cooling slots.
Use a soft bristle brush to loosen caked on dirt, oil, etc.
Use a vacuum cleaner to pick up loose dirt and debris.
First 5 Hours
Change engine oil
Every 8 Hours or Daily
Clean debris
Check engine oil level
Every 25 Hours or Yearly
Service engine air cleaner
1
Every 50 Hours or Yearly
Change engine oil
1
Every 100 Hours or Yearly
Service spark plug
Service spark arrester
Clean cooling system
1
Every 250 Hours or Yearly
Check valve clearance
17
StatStation™
The StatStation™ displays the nominal load on generator
based on output frequency. It also has a built in maintenance
reminder.
Wattage Monitor Operation
The display is two seven-segment LEDs that provide an easy-
to-read indication of the amount of power being supplied by
the generator. The load monitor displays the generator’s
output as a percentage.
As generator load increases, the display values will increase.
When the displayed values begin flashing, the user should
stop adding electrical loads to the generator.
If the power usage becomes too high, the letters “OL” (for
Over Load) will flash on the display. The user should reduce
the amount of load attached to the generator.
Maintenance Reminder
The LED will display certain codes to alert you to check oil,
change oil, check or replace air filter and check or replace
spark plug. The following codes will display:
“C1” Check oil at 8 hour increments
“C2” Change oil at 50 hour increments
“C3” Check or replace air filter at 25 hour increments
“C4” Check or replace spark plug at 100 hour increments
To take advantage of the StatStation “maintenance reminder”
capabilities, the user must press the reset button after
completing the maintenance called for in the displayed code
(C1, C2, C3, or C4). This results in a display of “Co” or “CA”,
depending on how long the button is pressed:
1) “Co” - Pressing the reset button once quickly will display
"Co" (clearing to zero). This will clear any maintenance
codes that have elapsed up to that point and they will
begin timing again from zero.
2) “CA” - Pressing and holding the reset button for
2 seconds will display "CA" (clearing all). This clears all
maintenance codes, even if they have not yet reached
their service point, and they will begin timing again from
zero.
If nominal load and maintenance codes appear
simultaneously, the LED shall display, alternately, the
nominal load and code as follows:
The code will display for 3 seconds, then 1/2 second off. The
load will display for 6 seconds and then 1/2 second off.
ENGINE MAINTENANCE
Oil
Oil Recommendations
We recommend the use of Briggs & Stratton Warranty
Certified oils for best performance. Other high-quality
detergent oils are acceptable if classified for service SF, SG,
SH, SJ or higher. DO NOT use special additives.
Outdoor temperatures determine the proper oil viscosity for
the engine. Use the chart to select the best viscosity for the
outdoor temperature range expected.
* Below 40°F (4°C) the use of SAE 30 will result in hard starting.
** Above 80°F (27°C) the use of 10W30 may cause increased oil
consumption. Check oil level more frequently.
NOTE: Synthetic oil meeting ILSAC GF-2, API
certification mark and API service symbol with
“SJ/CF ENERGY CONSERVING” or higher, is an
acceptable oil at all temperatures. Use of synthetic oil
does not alter required oil change intervals.
WARNING: Unintentional sparking can result in fire or
electric shock.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
Disconnect the spark plug wire from the spark plug and place
the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
18
Checking Oil Level
Oil level should be checked prior to each use or at least every
8 hours of operation. Keep oil level maintained.
1. Make sure generator is on a level surface.
2. Clean area around oil fill and remove oil fill cap.
3. Verify oil is at the point of overflowing at oil fill opening.
4. Replace and tighten oil fill cap.
Adding Engine Oil
1. Make sure generator is on a level surface.
2. Check oil level as described in Checking Oil Level.
3. If needed, slowly pour oil into oil fill opening to the point
of overflowing at oil fill.
4. Replace and tighten oil fill cap.
Service Air Cleaner
Your engine will not run properly and may be damaged if you
run it with a dirty air cleaner. Replace more often if operating
under dirty or dusty conditions.
To service the air cleaner, follow these steps:
1. Loosen screws (A) and remove air cleaner cover (B).
2. Carefully remove cartridge (C) from base (D).
3. Install clean (or new) air cleaner assembly inside cover.
Dispose of old filter properly.
4. Assemble air cleaner cover onto base and tighten
screws.
NOTE: You can purchase new air cleaner elements by calling
1-800-4-MY-HOME (469-4663).
Changing Engine Oil
If you are using your generator under extremely dirty or
dusty conditions, or in extremely hot weather, change the oil
more often.
KEEP OUT OF REACH OF CHILDREN. DON'T
POLLUTE. CONSERVE RESOURCES. RETURN
USED OIL TO COLLECTION CENTERS.
Change the oil while the engine is still warm from running, as
follows:
1. Make sure unit is on a level surface.
2. Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
3. Clean area around oil drain plug. The oil drain plug is
located at base of engine, opposite carburetor.
4. Remove oil drain plug and drain oil completely into a
suitable container.
5. Reinstall oil drain plug and tighten securely. Remove oil
fill cap.
6. Slowly pour recommended oil (about 28 oz.) into oil fill
opening to the point of overflowing at oil fill cap.
7. Reinstall oil fill cap. Finger tighten cap securely.
8. Wipe up any spilled oil.
9. Reconnect spark plug wire to spark plug.
Clean/Replace Spark Plug
Changing the spark plug will help your engine to start easier
and run better.
1. Clean area around spark plug.
2. Remove and inspect spark plug.
3. Replace spark plug if electrodes are pitted, burned or
porcelain is cracked. Use a recommended replacement
plug. See Specifications.
4. Check electrode gap with wire feeler gauge and reset
spark plug gap to recommended gap if necessary (see
Specifications).
5. Install spark plug and tighten firmly.
NOTE: You can purchase a new spark plug by calling
1-800-4-MY-HOME (469-4663).
CAUTION: Avoid prolonged or repeated skin contact
with used motor oil.
Used motor oil has been shown to cause skin cancer in certain
laboratory animals.
Thoroughly wash exposed areas with soap and water.
A
B
C
D
Inspect Muffler and Spark Arrester
Inspect the muffler for cracks, corrosion, or other damage.
Remove the spark arrester, if equipped, and inspect for dam-
age or carbon blockage. If replacement parts are required,
make sure to use only original equipement replacement
parts.
NOTE: You can purchase a new spark arrester screen by
calling 1-800-4-MY-HOME (469-4663).
Clean and inspect the spark arrester as follows:
1. To remove muffler heat shield (A) from muffler (B),
remove four screws that connect guard to muffler
bracket.
2. Remove four screws that attach spark arrester screen (C).
3. Inspect screen and obtain a replacement if torn,
perforated or otherwise damaged. DO NOT use a
defective screen. If screen is not damaged, clean it with
commercial solvent.
4. Reattach screen and muffler guard.
Air Cooling System
Over time debris may accumulate in cylinder cooling fins and
cannot be observed without partial engine disassembly. For
this reason, we recommend you have a Sears or other
qualified service dealer clean the cooling system per
recommended intervals (see Maintenance Schedule). Equally
important is to keep top of engine free from debris. See
Generator Cleaning.
Check Valve Clearance
Regular valve clearance check and adjustment will improve
performance and extend engine life. This procedure cannot
be done without partial engine disassembly and the use of
special tools. For this reason we recommend that you have a
Sears or other qualified service dealer check and adjust valve
clearance at recommended intervals.
Carburetor Adjustment
The carburetor on this engine is low emission. It is equipped
with a non-adjustable idle mixture valve and governed idle, if
equipped. Governed idle and top speed have been set at the
factory. If adjustment is required, see a Sears or other
qualified service dealer.
19
WARNING: Contact with muffler area can result in
serious burns.
Exhaust heat/gases can ignite
combustibles, structures or damage
fuel tank causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 feet (152 cm) of clearance on all sides of
generator including overhead.
It is a violation of California Public Resource Code, Section
4442, to use or operate the engine on any forest-covered,
brush-covered, or grass-covered land unless the exhaust
system is equipped with a spark arrester, as defined in Section
4442, maintained in effective working order. Other states or
federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer
to obtain a spark arrester designed for the exhaust system
installed on this engine.
Replacement parts must be the same and installed in the same
position as the original parts.
A
B
C
CAUTION:
Excessively high operating speeds increase
risk of injury and damage to generator.
Excessively low speeds impose a heavy load.
DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at governed
speed.
DO NOT modify generator in any way.
20
STORAGE
GENERAL
The generator should be started at least once every seven
days and allowed to run at least 30 minutes. If this cannot be
done and you must store the unit for more than 30 days, use
the following information as a guide to prepare it for storage.
Long Term Storage Instructions
It is important to prevent gum deposits from forming in
essential fuel system parts, such as the carburetor, fuel filter,
fuel hose or tank during storage. Also, alcohol-blended fuels
(called gasohol, ethanol or methanol) can attract moisture,
which leads to separation and formation of acids during
storage. Acidic fuel can damage the fuel system of an engine
while in storage.
Protect Fuel System
Fuel Preserver:
Fill the fuel tank with fresh fuel allowing at least 1.5" of tank
space for fuel expansion as shown on page 8, when using a
fuel preserver cartridge with the fresh start fuel cap. If only
partially filled, air in the tank will promote fuel deterioration
during storage. Engine and fuel can be stored up to 6 months
with fuel preserver.
Check level of fuel preserver cartridge. Fuel preserver is
dark in color.
If cartridge is almost empty or empty, replace with a new
fuel preserver cartridge following the instructions in Fresh
Start Fuel Cap.
If fuel preserver is not used, remove all fuel from tank and
run engine until it stops from lack of fuel.
Change Oil
While engine is still warm, drain oil from crankcase. Refill
with recommended grade. See Changing Engine Oil.
Generator
1. Clean generator as outlined in Generator Cleaning.
2. Check that cooling air slots and openings on generator
are open and unobstructed.
Other Storage Tips
1. DO NOT store fuel from one season to another unless it
has been treated as described in Protect Fuel System.
2. Replace fuel can if it starts to rust. Contaminated fuel
will cause engine problems.
3. If possible, store unit indoors and cover it to give
protection from dust and dirt.
4. Cover unit with a suitable protective cover that does not
retain moisture.
5. Store generator in clean, dry area.
WARNING: Fuel and its vapors are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
Store away from furnaces, stoves, water heaters, clothes dryers
or other appliances that have pilot light or other ignition source
because they can ignite fuel vapors.
WHEN DRAINING FUEL
Turn generator OFF and let it cool at least 2 minutes before
removing fuel cap. Loosen cap slowly to relieve pressure in
tank.
Drain fuel tank outdoors.
Keep fuel away from sparks, open flames, pilot lights, heat, and
other ignition sources.
DO NOT light a cigarette or smoke.
WARNING:
Storage covers can be flammable.
DO NOT place a storage cover over a hot generator.
Let equipment cool for a sufficient time before placing the cover
on the equipment.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Simplicity OPERATOR'S/IPL MANUAL- GENERATOR, CRAFTSMAN, CSA MODEL- 030243-1 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
Ce manuel convient également à