Aerial AD 110 Condensation Dehumidifier Manuel utilisateur

Taper
Manuel utilisateur

Ce manuel convient également à

1
Luftentfeuchter/Dehumidifier
Serie/Series
AD 110
2
1212
22
32
43
54
64
74
85
96
106
117
127
V2.1_02-2021 5506-0091
2
I. DE - BETRIEBSANLEITUNG (Original)
1 Produktübersicht ................................................................................... 2
2 Übersicht Bedienfeld ............................................................................. 4
3 Übersicht Wandbefestigung ................................................................. 5
4 Zu dieser Betriebsanleitung ................................................................. 5
5 Produktbeschreibung ............................................................................ 5
6 Sicherheit ............................................................................................... 6
7 Auspacken ............................................................................................. 7
8 Transport und Anschluss ..................................................................... 7
9 Bedienung .............................................................................................. 8
10 Wartung und Pflege ............................................................................... 8
11 Störungsbehebung ................................................................................ 9
12 Außerbetriebnahme, Lagerung und Entsorgung .............................. 11
13 EG-Konformitätserklärung .................................................................. 11
1 Produktübersicht
Fig. 1: Vorderansicht
1
Luftansaugfläche mit Filter
2
Bedienfeld
3
Luftaustritt
1
3
2
3
Fig. 2: Rückansicht
1
Aufhängung für Wandhalterung
2
Ablaufstutzen für
Ablaufschlauch
3
Netzstecker
4
Ablaufschlauch
Fig. 3: Innenansicht
1
Abdeckung Wärmetauscher
2
Pumpe
3
Ventilator
4
Kompressor
1
3
2
1
2
3
4
4
4
2 Übersicht Bedienfeld
Fig. 4: Übersicht Bedienfeld
1
Hygrostat:
0 = Aus
Cont. = Dauerbetrieb
4
Betriebsstunden
2
Signalleuchten
5
Betriebszustand/
Soll-Raumfeuchte
3
Ist-Raumtemperatur/
Ist-Raumfeuchte
Signalleuchte
Zustand
Bedeutung
Leuchtet
Soll-Raumfeuchte erreicht
Leuchtet
Raum wird entfeuchtet
Leuchtet
Außentemperatur <1°C oder
> 34 °C
Leuchtet
Störung
Blinkt
Pumpenstörung. Nach
Behebung läuft die Pumpe
automatisch wieder an.
1
2
3
4
5
5
3 Übersicht Wandbefestigung
Angaben in cm
Fig 5: Übersicht Wandbefestigung
1
Wandhalterung
3
Obere Kante Wandhalterung
2
Bohrloch Ø = 8 mm (2 Stück)
4 Zu dieser
Betriebsanleitung
Diese Betriebsanleitung darf ohne
schriftliche Genehmigung des
Herstellers nicht reproduziert, verviel-
fältigt und verbreitet werden.
Wichtig: Vor Gebrauch sorgfältig lesen.
Für späteres Nachschlagen auf-
bewahren.
5 Produktbeschreibung
Der Luftentfeuchter regelt die Luft-
feuchte im Raum. Das dabei
entstandene Kondensat-Wasser wird
über einen Ablaufschlauch abgepumpt.
Der Luftentfeuchter ist mit einer
automatischen Abtauung ausgestattet.
Der Luftentfeuchter ist für die Wand-
befestigung ausgelegt.
Lieferumfang
Luftentfeuchter
Betriebsanleitung
Wandhalterung
Universal-Montagesatz für
Wandbefestigung
Ablaufschlauch 12 x 2 mm mit
Schlauchschelle
Typenschild
Das Typenschild befindet sich am
Gehäuse.
1
2
3
6
6 Sicherheit
Bestimmungsgemäße Verwendung
und Einsatzbedingungen
Der Luftentfeuchter dient der
Entfeuchtung von Luft bei Atmos-
phärendruck in geschlossenen Innen-
räumen wie Keller, Garagen oder
Lagerhallen und ist zur Wandmontage
konzipiert.
Der Luftentfeuchter darf nur in Räumen
mit einer Grundfläche größer als 4 m2
aufgehängt, betrieben und gelagert
werden.
Der Luftentfeuchter darf nur unter
Einhaltung der Technischen Daten
(siehe letzte Seite) verwendet werden.
Die Benutzung des Luftentfeuchters ist
für Personen mit physischen,
sensorischen oder psychischen Ein-
schränkungen oder Kindern nicht ge-
stattet.
Jeder Benutzer muss die Betriebsan-
leitung gelesen und verstanden haben.
Vorhersehbare Fehlanwendung
Der Luftentfeuchter darf nicht eingesetzt
werden:
In Räumen mit explosions-
gefährdeten Atmosphären.
In Räumen mit aggressiven Atmos-
phären (z.B. durch Chemikalien
verursacht).
In Räumen mit Wasser, dessen pH-
Wert außerhalb von 7,0 bis 7,4 liegt.
In Räumen mit Salz oder Flüssig-
keiten mit einem Salzgehalt > 1 %,
z.B. Solebäder.
In Räumen mit Ozon-behandelter
Luft, hoher Lösemittelkonzentration
oder hoher Staubbelastung.
Allgemeine Sicherheitshinweise
WARNUNG! Explosionsgefahr,
Verbrennungen und Vergiftungen
durch Kältemittel!
Im Gerät befindet sich ein geruchloses,
brennbares Kältemittel, welches bei
falschem Umgang zu Explosionen und
Brand sowie zu Verletzungen und
Vergiftungen führen kann. Der Kälte-
mittelkreislauf steht unter Druck.
Keine Gegenstände zur Be-
schleunigung des Abtauprozesses
verwenden.
Luftentfeuchter nicht in Räumen mit
dauerhaften Zündquellen wie offene
Flammen, eingeschaltete Gas-
geräte oder Elektroheizer auf-
bewahren.
Luftentfeuchter nicht anbohren oder
anbrennen.
Gerät nur in einem ausreichend
belüfteten Raum mit einer Grund-
fläche größer als 4 m2 betreiben.
Jegliche Arbeiten am ltemittel-
kreislauf nur vom Hersteller oder
von ihm autorisierten Fachpersonal
durchführen lassen. Vor Arbeiten
am Kältemittelkreislauf muss dieser
an den vorgesehenen Ein-
richtungen entlastet werden.
Nationale Vorschriften für Gas-
installationen beachten.
Kältemittel nicht ablassen oder im
Hausmüll entsorgen.
Kontakt mit Kältemittel vermeiden.
WARNUNG! Stromschlag!
Arbeiten an spannungsführenden Bau-
teilen oder Wasser auf spannungs-
führenden Bauteilen kann lebens-
gefährliche Stromschläge verursachen.
Kontakt zwischen Wasser und
spannungsführenden Bauteilen
vermeiden.
Vor jedem Ortswechsel des Geräts
den Luftentfeuchter ausschalten
und den Netzstecker ziehen.
7
Arbeiten an elektrischen Bauteilen
nur durch den Hersteller oder
autorisiertes Personal durchführen
lassen.
7 Auspacken
Vorgehensweise
1. Lieferumfang auf Vollständigkeit
prüfen. Bei Schäden oder
unvollständiger Lieferung den Fach-
händler kontaktieren.
2. Verpackung entfernen und gemäß
den örtlichen Bestimmungen ent-
sorgen.
8 Transport und Anschluss
Transport
WARNUNG! Quetschen durch den
Verlust der Standfestigkeit!
Luftentfeuchter stehend trans-
portieren und gegen Kippen oder
Abrutschen sichern.
Luftentfeuchter auf ebenen und
festen Oberflächen aufstellen.
WARNUNG! Schnitt- und Quetsch-
verletzungen durch falsche
Transporthandhabung
Nicht in Öffnungen wie Luftfilter
greifen.
Luftentfeuchter mit zwei Personen
transportieren und geeignete Hebe-
und Transportmittel verwenden.
Vorgehensweise
1. Sicherstellen, dass der Ablauf-
schlauch und das Netzkabel vom
Gerät abgezogen sind.
2. Luftentfeuchter an den Einsatzort
transportieren.
Luftentfeuchter montieren
WARNUNG! Herunterfallen des Luft-
entfeuchters durch falsche Montage!
Nur mitgelieferte Wandhalterung
und Universal-Montagesatz ver-
wenden.
Luftentfeuchter mit zwei Personen
montieren.
Sicherstellen, dass die Wand stabil
und tragfähig ist.
Anforderungen
Die Luft muss frei zirkulieren. Die Luft-
öffnungen nicht abdecken. Der Freiraum
vor dem Luftaustritt und dem Luftfilter
muss mindestens 100 cm betragen.
Über der Wandhalterung müssen
mindestens 10 cm Abstand zum
nächsten Gegenstand sein, um das
Einhängen des Geräts zu ermöglichen.
Unterhalb der Wandhalterung müssen
mindestens 60 cm Abstand zum
nächsten Gegenstand sein.
Vorgehensweise
1. Die zwei Schrauben, mit denen die
Wandhalterung am Luftentfeuchter
vormontiert ist, entfernen und
aufbewahren.
2. Wandhalterung mit einer Wasser-
waage waagerecht ausrichten und
mit dem Universal-Montagesatz
gemäß Fig. 5 an der Wand
befestigen.
Bohrloch-Ø = 8 mm.
3. Luftentfeuchter mit der Aufhängung
in die Wandhalterung einhängen.
4. Luftentfeuchter mit den zwei
Schrauben vom 1.
Handlungsschritt an der
Wandhalterung fest-schrauben, um
das Gerät gegen Herabfallen zu
sichern.
8
Ablaufschlauch anschließen
ACHTUNG! Unzureichende Geräte-
leistung!
Ablaufschlauch nicht knicken.
Keine Gegenstände auf den
Schlauch stellen.
Vorgehensweise
1. Ablaufschlauch an der Rückseite
des Geräts am Ablaufstutzen
befestigen und mit Schlauchschelle
sichern.
2. Ablaufschlauch vom Luft-
entfeuchter weg in einen Abfluss
leiten (maximaler Höhen-
unterschied 3 m).
Elektrischer Anschluss
Vorgehensweise
1. Sicherstellen, dass die Netz-
spannung der Anschlussspannung
in den technischen Daten
entspricht.
2. Steckdose und Versorgungsnetz
ausreichend absichern.
3. In Feuchträumen bzw. auf Bau-
stellen einen FI-Schutzschalter
installieren.
4. Sicherstellen, dass der Netzstecker
für die Gebäudesteckdose geeignet
ist.
5. Sicherstellen, dass die verwendete
Steckdose geerdet ist.
6. Netzstecker in die Steckdose
stecken.
9 Bedienung
Raum entfeuchten
HINWEIS: Den Luftentfeuchter vor der
Inbetriebnahme, nach dem Transport
und nach längerer Lagerung ca. 15
Minuten in seiner endgültigen Position
ruhen lassen.
Vorgehensweise
1. Sicherstellen, dass das Kondensat-
Wasser über einen Ablaufschlauch
abfließen kann.
2. Hygrostat von „0“ in Richtung Cont“
drehen. Die gewünschte Feuchte
am Hygrostat einstellen. Der Luft-
entfeuchter startet nur, wenn die Ist-
Raumfeuchte höher als die Soll-
Raumfeuchte ist.
Die Leuchte leuchtet. Der Luft-
entfeuchter läuft für mindestens 10
Minuten. Sobald die Soll-Raumfeuchte
erreicht ist, läuft der Ventilator 30
Minuten nach. Steigt die Ist-Raum-
feuchte während der Nachlaufzeit um
5%, blinkt die Leuchte und der
Kompressor startet nach Ablauf der Zeit
neu. Falls der Hygrostat auf „Cont“
steht, läuft der Luftentfeuchter im
Dauerbetrieb.
Ausschalten
Vorgehensweise
1. Hygrostat auf „0“ stellen.
10 Wartung und Pflege
WARNUNG! Gesundheitsschäden
durch Staub!
Reinigung des Luftentfeuchters mit
Druckluft nur in offener Umgebung
durchführen.
Schutzmaske und Schutzbrille
tragen.
WARNUNG! Verletzungsgefahr durch
rotierenden Ventilator.
Vor dem Öffnen der Gehäusever-
kleidung:
Netzstecker ziehen und mindestens
15 s warten.
Sicherstellen, dass der Ventilator
gestoppt hat.
9
VORSICHT! Verbrennungsgefahr
durch heiße Leitungen!
Einige Leitungen im Gehäuseinneren
können heiß werden und zu leichten
Verbrennungen führen.
Leitungen ausreichend abkühlen
lassen.
ACHTUNG! Sachschaden!
Putzmittel können Oberflächen
schädigen. Nur milde Reinigungs-
mittel verwenden.
Nur zugelassene Original-Ersatz-
teile verwenden.
Reinigung und Inspektion
Vorgehensweise
1. Luftentfeuchter ausschalten.
2. Netzstecker ziehen.
3. Luftfilter entnehmen und reinigen
(z.B. mit Staubsauger) bzw. er-
neuern.
4. Ablaufstutzen und Ablaufschlauch
kontrollieren.
5. Neuen bzw. gereinigten Filter ein-
setzen. Nur Original-Filter ver-
wenden.
6. Schrauben der Gehäuseseitenteile
und des Deckels lösen und Ge-
häuseverkleidung entfernen.
7. Schrauben der Abdeckung Wärme-
tauscher lösen und Abdeckung
entfernen.
8. Abtropfwanne (Pos. 1) ein Stück
herausziehen und mit einem Tuch
abwischen.
9. Abtropfwanne wieder zurück-
schieben.
10. WARNUNG! Stromschlag durch
auslaufendes Kondenswasser!
Nach Reinigung der Abtropfwanne
sicherstellen, dass der Abtropf-
schlauch (Pos. 2) in der Öffnung
der Pumpe steckt.
11. Gerät vorsichtig mit Druckluft
ausblasen. Darauf achten, dass alle
Komponenten gereinigt werden.
12. Abdeckung Wärmetauscher
montieren.
13. Gehäuseverkleidung montieren.
14. Netzkabel einstecken.
Ersatzteile und Kundendienst
Bei Fragen zum Luftentfeuchter oder
falls Ersatzteile benötigt werden,
Vertragshändler oder AERIAL-Service
kontaktieren.
11 Störungsbehebung
Bei Störungen die folgenden Punkte
prüfen. Bei Bedarf AERIAL-Service
kontaktieren.
WARNUNG! Vergiftungen durch Kälte-
mittel, Verbrennungen, Quetschen oder
Stromschlag während Wartungs-
arbeiten!
Reparaturen oder Instandsetzungs-
arbeiten nur durch den Hersteller
2
1
10
oder autorisiertes Personal
durchführen lassen.
Bei Funktionsstörungen den Luft-
entfeuchter abschalten und gegen
Wiedereinschalten sichern.
Vor Arbeiten an heißen Bauteilen
diese ausreichend abkühlen lassen.
Fehlermeldungen
Display-Anzeige
Mögliche Ursache
Abhilfe
Außentemperatur
<1°C oder > 34 °C
Gerät startet selbsttätig neu,
sobald Temperatur wieder
>5°C oder <30°C.
Fehler des
Kühlsystems
AERIAL-Service kontaktieren.
Störungen
Problem
Mögliche Ursache
Abhilfe
Der Luftentfeuchter
weist eine schlechte
bzw. keine
Entfeuchtungsleistung
auf.
Luftfilter ist
verschmutzt. Der
Luftentfeuchter
bekommt zu wenig
Luft. Verschmutzte
Filter können auf
Dauer zu Schäden
am Gerät führen.
Filter reinigen bzw. bei Bedarf
erneuern.
Der Luftentfeuchter ist
außer Betrieb/
Ventilator und
Kompressor arbeiten
nicht.
Luftentfeuchter ist
ausgeschaltet.
Luftentfeuchter einschalten.
Luftentfeuchter ist
ohne
Stromversorgung.
Stromversorgung prüfen.
Pumpenstörung
Pumpe ist blockiert,
z.B. weil das Wasser
über den
Ablaufschlauch nicht
ablaufen kann.
Ablaufschlauch kontrollieren.
Pumpe defekt.
AERIAL-Service kontaktieren.
Error E1
<Room temp>
Error E2
<cooling system>
11
12 Außerbetriebnahme, Lagerung und Entsorgung
Außerbetriebnahme
Vorgehensweise
1. Luftentfeuchter ausschalten.
2. Netzstecker ziehen.
3. Luftentfeuchter zum Schutz vor
Staub mit einem Tuch abdecken.
Lagerung
VORSICHT! Verletzung!
Nicht mehr als zwei Luftentfeuchter
übereinanderstapeln.
Luftentfeuchter gegen Kippen
sichern.
Vorgehensweise
1. Luftentfeuchter bei 0 °C bis +40 °C
lagern.
Entsorgung
ACHTUNG! Gefährdung durch
Materialien und Substanzen
Materialien sortenrein trennen und
entsprechend örtlicher Vorschriften
der Wiederverwertung zuführen.
Zur Entsorgung von Hilfs- und
Betriebsstoffen die örtlichen
Vorschriften und Angaben aus den
Sicherheitsdatenblättern beachten.
Den Luftentfeuchter nicht
dem Hausmüll zuführen,
sondern entsprechend den
gesetzlichen
Bestimmungen entsorgen.
13 EG-Konformitätserklärung
EG-Konformitätserklärung im Sinne der Maschinenrichtlinie 2006/42/EG
Anhang II 1.A
Hersteller: Dantherm GmbH Oststraße 148 22844 Norderstedt
Produkt: Luftentfeuchter
Produkt-Nr: AD110
Funktionsbeschreibung: Der Luftentfeuchter dient dem Entfeuchten der Luft
bei Atmosphärendruck in geschlossenen Räumen.
Es wird ausdrücklich erklärt, dass das Produkt den einschlägigen Bestimmungen
der folgenden Richtlinien entspricht:
2006/42/EG Maschinenrichtlinie
2014/30/EU Richtlinie über die elektromagnetische Verträglichkeit (EMV)
Folgende harmonisierte Normen wurden angewandt:
EN 60335-2-40:2003
EN 60204-1:2006
EN 378-2:2016
EN ISO 12100:2010
EN ISO 13857:2008
EN ISO 14120:2015
Für die Zusammenstellung der technischen Dokumentation bevollmächtigte
Person: Manfred Föhlisch - Oststraße 148 - 22844 Norderstedt
Norderstedt den 30.03.2020
12
II. EN - OPERATING INSTRUCTIONS
1 Product overview ................................................................................. 12
2 Overview of control panel ................................................................... 14
3 Overview of wall attachment .............................................................. 15
4 About these operating instructions ................................................... 15
5 Product description ............................................................................. 15
6 Safety .................................................................................................... 15
7 Unpacking ............................................................................................ 16
8 Transport and connection .................................................................. 17
9 Operation .............................................................................................. 18
10 Maintenance and care ......................................................................... 18
11 Troubleshooting .................................................................................. 19
12 Decommissioning, storage and disposal .......................................... 20
13 EC Declaration of Conformity ............................................................. 21
1 Product overview
Fig. 1: Front view
1
Air intake area with filter
2
Control panel
3
Air outlet
1
3
2
13
Fig 2: Back view
1
Bracket for wall mount
2
Discharge nozzle for discharge
hose
3
Mains plug
4
Discharge hose
Fig. 3: Inside view
1
Heat exchanger cover
2
Pump
3
Fan
4
Compressor
1
3
2
1
2
3
4
4
14
2 Overview of control panel
Fig. 4: Overview of control panel
1
Humidity switch:
0 = off
Cont. = continuous operation
4
Operating hours
2
Signal lights
5
Operating state/
Target room humidity
3
Actual room temperature/
Actual room humidity
Signal light
State
Meaning
Illuminated
Target room humidity reached
Illuminated
Dehumidifying room
Illuminated
Outside temperature <1°C or
> 34 °C
Illuminated
Fault
Flashing
Pump fault. The pump will start
up again automatically once the
fault has been repaired.
1
2
3
4
5
15
3 Overview of wall attachment
Measurements in cm
Fig 5: Overview of wall attachment
1
Wall mount
3
Top edge of wall mount
2
Drilled hole Ø = 8 mm (2x)
4 About these operating
instructions
These operating instructions must not
be reproduced, duplicated or distributed
without the written consent of the
manufacturer.
Important: Read carefully before use.
Keep for later reference.
5 Product description
The dehumidifier controls the air
humidity in the room. The condensate
water which is produced is pumped
away via a discharge hose. The
dehumidifier has an automatic defrost
function. The dehumidifier is designed to
be wall-mounted.
Package contents
Dehumidifier
Operating instructions
Wall mount
Universal installation kit for wall
attachment
Discharge hose 12 x 2 mm with
hose clamp
Identification plate
The identification plate is on the housing.
6 Safety
Intended use and conditions of use
The dehumidifier is used to remove
humidity from the air where there is
atmospheric pressure in closed indoor
rooms, such as basements, garages or
1
2
3
16
warehouses, and is designed to be wall
mounted.
The dehumidifier must only be mounted,
used and stored in rooms larger than
4 m2.
The dehumidifier must only be used in
compliance with the Technical Data (see
last page).
Persons with physical, sensory or mental
restrictions and children are not
permitted to use the dehumidifier.
Every user must have read and
understood the operating instructions.
Foreseeable misuse
The dehumidifier must not be used:
In rooms with potentially explosive
atmospheres.
In rooms with an aggressive
atmosphere (e.g. caused by
chemicals).
In rooms with water with a pH value
below 7.0 or above 7.4.
In rooms with salt or liquids with a
salt content > 1 %, e.g. brine baths.
In rooms with ozone-treated air,
high solvent concentrations or high
dust pollution.
General safety information
WARNING! Risk of explosion, burns
and poisoning from refrigerants!
The appliance contains an odourless,
flammable refrigerant which, if handled
incorrectly, could result in explosions
and fire as well as injuries and burns.
The refrigerant circuit is pressurised.
Do not use any objects to accelerate
the thawing process.
Do not store the dehumidifier in
rooms with permanent sources of
ignition, such as open flames,
operational gas appliances or
electric heaters.
Do not drill open or ignite
dehumidifiers.
Only operate the appliance in an
adequately ventilated room larger
than 4 m2.
Any work to the refrigerant circuit
must be performed by the
manufacturer or the manufacturer’s
authorised technical personnel.
Before working on the refrigerant
circuit, it must be depressurised
using the designated mechanisms.
Observe the national regulations for
gas installations.
Do not dump refrigerants or dispose
of them as household waste.
Avoid coming into contact with the
refrigerant.
WARNING! Electrocution!
Working on live components or water on
live components can cause life-
threatening electrocution.
Avoid contact between water and
live components.
Always switch off and unplug the
dehumidifier before moving it to
another location.
Only allow the manufacturer or
authorised personnel to carry out
work on electric components.
7 Unpacking
Procedure
1. Check that the package contents
are complete. Contact your stockist
in the event of damage or missing
contents.
2. Remove the packaging and
dispose of it in accordance with
local regulations.
17
8 Transport and connection
Transport
WARNING! Crushing as a result of
instability!
Transport the dehumidifier in an
upright position and secure it so that
it cannot tip over or slip.
Position the dehumidifier on a
stable, even surface.
WARNING! Risk of cuts and crushing
from incorrect handling during
transport
Do not reach into openings such as
air filters.
The dehumidifier must be
transported by two people using
appropriate lifting and transport
equipment.
Procedure
1. Make sure that the discharge hose
and the mains cable have been
disconnected from the appliance.
2. Transport the dehumidifier to where
it is going to be used.
Installing the dehumidifier
WARNING! Risk of dehumidifier
falling as a result of incorrect
assembly!
Only use the wall mount provided
and universal installation kit.
The dehumidifier must be installed
by two people.
Make sure that the wall is sound and
capable of bearing the load.
Requirements
The air must circulate freely. Do not
cover the air openings. There must be a
clearance of at least 100 cm in front of
the air outlet and the air filter.
There must be at least 10 cm between
the top of the wall mount and the nearest
object to allow the device to be mounted.
There must be at least 60 cm between
the bottom of the wall mount and the
nearest object.
Procedure
1. Remove and set aside the two
screws used to pre-assemble the
wall mount to the dehumidifier.
2. Use a spirit level to position the
wall mount horizontally and fix to
the wall using the universal
installation kit as shown in fig. 5.
Drilled hole Ø = 8 mm.
3. Hang the dehumidifier on the
bracket of the wall mount.
4. Screw the dehumidifier to the wall
mount using the two screws from
step 1 to secure the device so that it
does not fall.
Connecting the discharge hose
ATTENTION! Inadequate appliance
output!
Do not bend the discharge hose.
Do not place any objects on the
hose.
Procedure
1. Attach the discharge hose on the
back of the device to the discharge
nozzle and secure with the hose
clamp.
2. Run the discharge hose away from
the dehumidifier to a drain
(maximum height difference: 3 m).
Electrical connection
Procedure
1. Make sure that the supply voltage is
the same as the connection voltage
in the technical data.
2. Provide an adequate fuse for the
socket and the power supply.
3. Install an earth leakage circuit
breaker in damp rooms and building
sites.
18
4. Make sure that the mains plug is
suitable for the socket of the
building.
5. Make sure that the socket used is
earthed.
6. Plug the mains plug into the socket.
9 Operation
Dehumidifying the room
NOTE: Allow the dehumidifier to rest in
its final position for approx. 15 minutes
before starting up, after transport and
after prolonged storage.
Procedure
1. Make sure that the condensate
water can drain off through a
discharge hose
2. Turn the humidity switch from “0” to
“Cont”. Set the desired humidity at
the humidity switch. The
dehumidifier will only start if the
actual room humidity is higher than
the target room humidity.
Light illuminates. The dehumidifier
will start operating. The dehumidifier
runs for at least 10 minutes. Once the
target room humidity has been reached,
the fan continues to run for 30 minutes.
If the actual room humidity increases by
5% during the cool-down period, the
light flashes and the compressor
restarts when the time is up. If the
humidity switch is at “Cont”, the
dehumidifier will run continuously.
Switching off
Procedure
1. Set humidity switch to “0”.
10 Maintenance and care
WARNING! Damage to health from
dust!
Only clean the dehumidifier with
compressed air in open spaces.
Wear a protective mask and
goggles.
WARNING! Risk of injury from
rotating fan.
Before opening the bezel:
Disconnect the mains plug and wait
at least 15 s.
Make sure that the fan has stopped.
CAUTION! Risk of burning from hot
cables!
Some cables inside the housing can get
hot and cause slight burns.
Allow the cables to cool down
sufficiently.
ATTENTION! Damage to property!
Cleaning agents can damage
surfaces. Only use mild detergents.
Only use approved original spare
parts.
Cleaning and inspection
Procedure
1. Switch off the dehumidifier.
2. Unplug the mains plug.
3. Remove and clean the air filter (e.g.
with vacuum cleaner) or replace it.
4. Check the discharge nozzle and
hose, if connected.
5. Insert a new or clean filter. Only use
an original filter.
6. Undo the screws on the side panels
and the lid and remove the bezel.
19
7. Undo the screws on the heat
exchanger cover and remove the
lid.
8. Pull out the drip tray slightly (Pos. 1)
and wipe with a cloth.
9. Push the drip tray back in again.
10. WARNING! Risk of electrocution
from leaking condensate water!
After cleaning the drip tray, make
sure that the drain hose (Pos. 2) is
inserted in the pump opening.
11. Carefully blow off the device with
compressed air. Make sure that all
of the components have been
cleaned.
12. Fit the heat exchanger cover.
13. Fit the bezel.
14. Plug in the mains cable.
Spare parts and customer service
If you have any questions about the
dehumidifier or require spare parts,
contact your authorised dealer or
AERIAL Service.
11 Troubleshooting
Please check the following points in the
event of a fault. If necessary contact
AERIAL Service.
WARNING! Poisoning from refrigerant,
burns, crushing or electrocution during
maintenance work!
Only allow the manufacturer or
authorised personnel to carry out
repairs and maintenance work.
In the event of malfunctions, switch
off the dehumidifier and secure it so
that it cannot be switched back on
again.
Allow any hot components to cool
sufficiently before working on them.
Error messages
Display message
Possible cause
Remedial action
Outside temperature
< 1°C or > 34°C
Appliance will automatically
restart as soon as the
temperature is > 5°C or< 30°C.
Cooling system fault
Contact AERIAL Service.
Error E1
<Room temp>
Error E2
<cooling system>
1
2
20
Faults
Problem
Possible cause
Remedial action
The dehumidifier is
not performing
well/removing
moisture.
Air filter is dirty. The
dehumidifier is not
getting enough air.
Dirty filters can
damage the
appliance in the long
term.
Clean the filter or replace if
necessary.
The dehumidifier is
out of operation / fan
and compressor are
not working.
Dehumidifier is
switched off.
Switch on the dehumidifier.
There is no power
supply to the
dehumidifier.
Check the power supply.
Pump fault
Pump is blocked, e.g.
water cannot drain
out of the discharge
hose.
Check the discharge hose, if
connected.
Pump faulty.
Contact AERIAL Service.
12 Decommissioning, storage and disposal
Decommissioning
Procedure
1. Switch off the dehumidifier.
2. Unplug the mains plug.
3. Cover the dehumidifier with a cloth
to protect it from dust.
Storage
CAUTION! Injury!
Do not stack more than two
dehumidifiers on top of each other.
Secure the dehumidifiers so that
they do not fall over.
Procedure
1. Store the dehumidifier between 0°C
and +40°C.
Disposal
ATTENTION! Risk from materials and
substances
Sort materials according to type and
recycle in accordance with local
regulations.
When disposing of auxiliary and
operating materials, observe the
local regulations and information on
the safety data sheets.
Do not dispose of the
dehumidifier as household
waste but rather in
accordance with the legal
regulations.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128

Aerial AD 110 Condensation Dehumidifier Manuel utilisateur

Taper
Manuel utilisateur
Ce manuel convient également à