Supermicro SSE-G3632SR Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 1
SSE-G3632S
SSE-G3632SR
Switch Installation Guide
Revision 1.0
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 2
The information in this Installation Manual has been carefully reviewed and is believed to be accurate. The vendor assumes no responsibility for
any inaccuracies that may be contained in this document, makes no commitment to update or to keep current the information in this manual, or to
notify any person or organization of the updates. Please Note: For the most up-to-date version of this manual, please see our web site at
www.supermicro.com.
Super Micro Computer, Inc. (“Supermicro”) reserves the right to make changes to the product described in this manual at any time and without
notice. This product, including software, if any, and documentation may not, in whole or in part, be copied, photocopied, reproduced, translated or
reduced to any medium or machine without prior written consent.
IN NO EVENT WILL SUPERMICRO BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, SPECULATIVE OR CONSEQUENTIAL
DAMAGES ARISING FROM THE USE OR INABILITY TO USE THIS PRODUCT OR DOCUMENTATION, EVEN IF ADVISED OF THE
POSSIBILITY OF SUCH DAMAGES. IN PARTICULAR, SUPERMICRO SHALL NOT HAVE LIABILITY FOR ANY HARDWARE, SOFTWARE, OR
DATA STORED OR USED WITH THE PRODUCT, INCLUDING THE COSTS OF REPAIRING, REPLACING, INTEGRATING, INSTALLING OR
RECOVERING SUCH HARDWARE, SOFTWARE, OR DATA.
Any disputes arising between manufacturer and customer shall be governed by the laws of Santa Clara County in the State of California, USA.
The State of California, County of Santa Clara shall be the exclusive venue for the resolution of any such disputes. Super Micro's total liability for
all claims will not exceed the price paid for the hardware product.
FCC Statement: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
manufacturer’s instruction manual, may cause harmful interference with radio communications. Operation of this equipment in a residential area
is likely to cause harmful interference, in which case you will be required to correct the interference at your own expense.
California Best Management Practices Regulations for Perchlorate Materials: This Perchlorate warning applies only to products containing CR
(Manganese Dioxide) Lithium coin cells. Perchlorate Material-special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate for
further details.
WARNING: HANDLING OF LEAD SOLDER MATERIALS USED IN THIS PRODUCT MAY EXPOSE YOU TO LEAD, A CHEMICAL KNOWN TO
THE STATE OF CALIFORNIA TO CAUSE BIRTH DEFECTS AND OTHER REPRODUCTIVE HARM.
Manual Revision 1.0
Release Date: April 5, 2017 3:47 PM
Unless you request and receive written permission from Super Micro Computer, Inc., you may not copy any part of this document.
Information in this document is subject to change without notice. Other products and companies referred to herein are trademarks or registered
trademarks of their respective companies or mark holders.
Copyright © 2017 by Super Micro Computer, Inc.
All rights reserved.
Printed in the United States of America
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 3
Preface
About this Manual
This manual is written for professional system integrators, Information Technology professionals,
service personnel, technicians and network administrators who are responsible for installing and setting
up network equipment; consequently, it assumes a basic working knowledge of LANs (Local Area
Networks). It provides information for the installation and use of the Supermicro's SSE-G3632R and
SSE-G3632SR switches. Installation and maintenance should be performed by experienced
professionals only.
Manual Organization
Chapter 1: Introduction
The first chapter provides an introduction to the switch.
Chapter 2: Safety
The second chapter provides important safety information for the switch.
Chapter 3: Installation Requirements
This chapter covers installation requirements, notices and security warnings for the switches.
Chapter 3 Device Installation
Use this chapter for installation of the switches and connecting them to your systems.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 4
Table of Contents
Introduction .............................................................................................................................. 6
1.1 Overview ....................................................................................................................................................... 6
1.2 Features and Benefits ................................................................................................................................... 7
Various Interfaces ........................................................................................................................................... 7
Supports 100Gbs Ethernet .............................................................................................................................. 7
Different Airflow Options ................................................................................................................................ 7
1.3 Hardware ...................................................................................................................................................... 8
Front Panel ...................................................................................................................................................... 8
Back Panel ....................................................................................................................................................... 9
1.4 Status LEDs .................................................................................................................................................... 9
1.5 Port Description .......................................................................................................................................... 10
1.6 Power Supply Module ................................................................................................................................. 11
800W Power Module .................................................................................................................................... 11
1.7 Fan Module ................................................................................................................................................. 11
1.8 System Specifications .................................................................................................................................. 12
Standardized Warning Statements .......................................................................................... 13
2.1 About Standardized Warning Statements ............................................................................................. 13
Installation Notices ................................................................................................................. 25
3.1 Environmental Requirements ...................................................................................................................... 25
Dust and Particles ......................................................................................................................................... 25
Temperature and Humidity ........................................................................................................................... 26
Power Supply ................................................................................................................................................ 27
Preventing Electrostatic Discharge Damage ................................................................................................. 27
Anti-interference .......................................................................................................................................... 27
Rack Configuration ........................................................................................................................................ 28
3.2 Installation Notice ....................................................................................................................................... 28
3.3 Security Warnings ....................................................................................................................................... 29
Device Installation................................................................................................................... 30
4.1 Installation Preparation .............................................................................................................................. 30
Verify the Package Contents ......................................................................................................................... 30
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 5
Required Tools and Utilities .......................................................................................................................... 30
4.2 Device Installation ................................................................................................................................. 31
Installing the Switch ...................................................................................................................................... 31
Installation with Mounting Rails ................................................................................................................... 32
Installing the Power Supply Module ............................................................................................................. 33
Installing the Fan ........................................................................................................................................... 34
Connecting the Console ................................................................................................................................ 35
QSFP28 Transceiver Installation .................................................................................................................... 36
Copper Cable/Fiber Cable Connection ......................................................................................................... 36
AC Power Supply Connection ....................................................................................................................... 38
Grounding Cable Connection ........................................................................................................................ 39
Checking the Switch ...................................................................................................................................... 40
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 6
Introduction
1.1 Overview
The Supermicro SSE-C3632S and SSE-C3632SRS switches are at the top of the Supermicro bare
metal switch line. A new generation of 100G Ethernet routing switches, they enable a robust layer-3 IP
fabric with a flexible layer-2 overlay in an optimized Ethernet architecture. They are well-suited to
function as the high-speed spine layer, giving scalable bi-sectional fabric bandwidth for leaf layer
switches like the SSE-X3648S or even the SSE-G3648B. The ability to configure the individual physical
Ethernet QSFP28 ports as either 40Gbps or 100Gbps, gives optimum flexibility for high-speed physical
connectivity between the spine and leaf layers in the data center Ethernet fabric.
These switches incorporate 100GE switching technology and are particularly appropriate for use in
large-scale data centers to provide 100GE server connectivity as well as high-bandwidth connectivity
to other Ethernet switching products. Redundant hot-swappable power supplies (standard) are but one
of the many features making them attractive for use in the modern data center. They are ideal as a
distribution layer switch for campus networks, enterprise networks and High Performance Computing
(HPC) networks; as well as a core layer switch for small to medium-sized networks. Preloaded with
Open Networking Installation Environment (ONIE) they are optimized for use in an Open Networking
environment.
Figure 1-1. SSE-C3632S and SSE-C3632SR Switches
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 7
1.2 Features and Benefits
Various Interfaces
The SSE-C3632S and SSE-C3632SR switches provide thirty-two 100Gbs QSFP28 ports. Each
QSFP28 port can be split into four 25Gbs SFP28 ports. Each QSFP28 port can alternatively be
configured at 40Gbps which in turn can be split into four 10Gbps SFP+ ports.
Supports 100Gbs Ethernet
100Gbs Ethernet is a big leap in the evolution of Ethernet. 100Gbs Ethernet can be deployed in leaf-
and-spine topologies. With 100Gbs Ethernet, the SSE-C3632S and SSE-C3632SR switches provide
high bandwidth and powerful processing capacity. Using SSE-C3632S and SSE-C3632SR switches,
users can simplify network structures and reduce the cost of network construction.
Different Airflow Options
The SSE-C3632S provides “front-to-back” air flow (port-side to power-supply side) for cooling
sometimes called “normal air flow”. The SSE-C3632SR provides air flow in the opposite direction
(“reverse air flow”). Reverse air flow is particularly useful in data centers with alternating “hot” and
“cold” aisles because it allows the switch to be installed in the rear of a rack facing the “hot” aisle. This
is the side of the rack where networking cables are typically attached to servers.
Figure 1-2. Regular Air Flow
Figure 1-3. Reverse Air Flow
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 8
1.3 Hardware
Front Panel
The front panel descriptions of SSE-C3632S and SSE-C3632SR switches are given in the following
table.
Panel Descriptions of the SSE-C3632S/SR Switches
Type
QSFP28
Port
10/100/1000Base-T
ETHERNET Port
Console
Port
USB 2.0
Interface
SSE-C3632S and
SSE-C3632SR
32
1
1
1
The front panel of the SSE-C3632S/R is shown below:
Figure 1-4. Front Panel View
Caution: The USB port only supports data transmission, it does not supply USB power.
Console Description
SSE-C3632S and SSE-C3632SR switches provide an RJ-45 serial console port. Users can perform
local and telnet configuration through this port.
The console port supports asynchronous mode: set the data bit as 8, the stop bit as 1, the parity bit as
none. The default baud rate is 115200bps.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 9
Back Panel
The back panel of the SSE-C3632S/R includes two (redundant) alternating current power modules and
five fans.
Fig 1-5. Back Panel View
1.4 Status LEDs
The front panel of the SSE-C3632S/R has 128 QSFP28 port indicator lights, two power supply indicator
lights and system automatic diagnostic LEDs. They are shown below and described in the following
tables.
Indicator Lights on the Front Panel of the SSE-C3632S/R Switches
Indicator Light
Front Panel Sign
Meaning
Power supply
indicator light
P-1/P-2
Power supply module is operating normally.
No power supply or power fault.
System status
indicate LED
START
The system is powered on and operating normally.
The system is powered off.
Indicator Lights on the Rear Panel of the SSE-C3632S/R
Indicator Light
Rear Panel Sign
State
Meanings
Fan Module
Indicator Light
FAN1/FAN2/
FAN3/FAN4/ FAN5
Green light always on
Fan module is operating normally.
Red light always on
No fan module or fan speed is 0.
Out
Fan module is powered off.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 10
Port Indicator Lights on the Front Panel of the SSE-C3632S/R
Indicator Light
Panel Sign
State
ETHERNET Port Link
Light (Left)
Green light wink
The port is transmitting data.
Out
There is no data transmitting on the port.
ETHERNET Port
Activity Light (Right)
Yellow light always on
The port is configured at 10Mbps/100Mbps speed
Green light always on
The port is configured at 1000Mbps speed
Out
No connection or failure to connect.
Indicator Light of
QSFP28 Port
Green light always on
The port is connecting at 100Gbps.
Amber light always on
The port is connecting at 4x25G.bps
Wink
The port is transmitting data.
Red light always on
There is a fault on the port.
Out
No connection or failure to connect.
1.5 Port Description
The SSE-C3632S/R provides 32 100Gb QSFP28 ports. Each is described below:
SSE-C3632S/R Port Description
Port mode
Specification
RJ-45 port
10/100/1000Mbps auto negotiation
MDI/MDI-X cable mode auto negotiation
QSFP28
100GBASE-CR4 transceiver, Copper, 5m
100GBASE-SR4 transceiver, 850nm, MMF, OM3/OM4, 100m
The SSE-C3632S/R provides 32 QSFP28 ports and supports use of a QSFP28 cable. It enhances the
flexibility of the network.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 11
1.6 Power Supply Module
800W Power Module
The Power Supply Module (PSM) of the SSE-C3632S/R is shown in the sketch below:
Fig 1-6. Sketch of SSE-C3632S/R Power Supply Module
SSE-C3632S and SSE-C3632SR switches have two PSMs for redundancy. There are two airflow
options - front to back (SSE-C3632S) and back to front (SSE-C3632SR).
The maximum power is 800W. The input is 100VAC~240VAC and the output is 12V +/- 5%. There is a
handle for installing or removing the module on the back of the power supply. The power supply module
supports hot plug.
Caution: Different airflow power modules can not be mixed.
1.7 Fan Module
The fan module of the SSE-C3632S/R is shown in the sketch below:
Fig 1-7. Fan module
SSE-C3632S and SSE-C3632SR switches have 5 Fan modules in the standard configuration. The
rotation speed of the fan(s) self-adjusts to adapt to the system temperature.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 12
Caution: Different airflow fan modules can not be mixed in the same switch unit. Power Supply
Modules must have the same airflow as the fan modules.
1.8 System Specifications
System Specifications of the SSE-C3632S/R
Type
Attribute
SSE-C3632S/R
Dimension(W * H * D) (mm)
433.8 * 44 * 520
Weight
10.18kg(with 2 PSU)
Fixed Port
32 QSFP28 ports
Management Port
1 RJ-45 serial console port
Power Input
100~240VAC(50~60Hz)
System Consumption
<657W
Operating Temperature
(airflow front to back)
0°C~45°C
Operating Temperature
(airflow back to front)
0°C~40°C
Storage Temperature
-40°C~75°C
Operating Relative Humidity
10%~90%, non-condensing
Storage Relative Humidity
5%~95%, non-condensing
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 13
Standardized Warning
Statements
2.1 About Standardized Warning Statements
The following statements are industry standard warnings, provided to warn the user of situations
which have the potential for bodily injury. Should you have questions or experience difficulty, contact
Supermicro's Technical Support department for assistance. Only certified technicians should attempt
to install or configure components.
Read this appendix in its entirety before installing or configuring components in the Supermicro
chassis
These warnings may also be found on our web site at
http://www.supermicro.com/about/policies/safety_information.cfm
Warning Definition
Warning!
This warning symbol means danger. You are in a situation that could cause bodily injury. Before you
work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with
standard practices for preventing accidents.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 14
此警告符号代表危险。
您正处于可能受到严重伤害的工作环境中。在您使用设备开始工作之前,必须充分意识到触电的危险,
并熟练掌握防止事故发生的标准工作程序。请根据每项警告结尾的声明号码找到此设备的安全性警告说
明的翻译文本。
此警告符號代表危險。
您正處於可能身體可能會受損傷的工作環境中。在您使用任何設備之前,請注意觸電的危險,並且要熟
悉預防事故發生的標準工作程序。請依照每一注意事項後的號碼找到相關的翻譯說明內容。
Warnung
WICHTIGE SICHERHEITSHINWEISE
Dieses Warnsymbol bedeutet Gefahr. Sie befinden sich in einer Situation, die zu Verletzungen führen
kann. Machen Sie sich vor der Arbeit mit Geräten mit den Gefahren elektrischer Schaltungen und den
üblichen Verfahren zur Vorbeugung vor Unfällen vertraut. Suchen Sie mit der am Ende jeder Warnung
angegebenen Anweisungsnummer nach der jeweiligen Übersetzung in den übersetzten
Sicherheitshinweisen, die zusammen mit diesem Gerät ausgeliefert wurden.
BEWAHREN SIE DIESE HINWEISE GUT AUF.
INSTRUCCIONES IMPORTANTES DE SEGURIDAD
Este símbolo de aviso indica peligro. Existe riesgo para su integridad física. Antes de manipular
cualquier equipo, considere los riesgos de la corriente eléctrica y familiarícese con los procedimientos
estándar de prevención de accidentes. Al final de cada advertencia encontrará el número que le
ayudará a encontrar el texto traducido en el apartado de traducciones que acompaña a este
dispositivo.
GUARDE ESTAS INSTRUCCIONES.
IMPORTANTES INFORMATIONS DE SÉCURITÉ
Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une situation pouvant
entraîner des blessures ou des dommages corporels. Avant de travailler sur un équipement, soyez
conscient des dangers liés aux circuits électriques et familiarisez-vous avec les procédures
couramment utilisées pour éviter les accidents. Pour prendre connaissance des traductions des
avertissements figurant dans les consignes de sécurité traduites qui accompagnent cet appareil,
référez-vous au numéro de l'instruction situé à la fin de chaque avertissement.
CONSERVEZ CES INFORMATIONS
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 15
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Dit waarschuwings symbool betekent gevaar. U verkeert in een situatie die lichamelijk letsel kan
veroorzaken. Voordat u aan enige apparatuur gaat werken, dient u zich bewust te zijn van de bij een
elektrische installatie betrokken risico's en dient u op de hoogte te zijn van de standaard procedures
om ongelukken te voorkomen. Gebruik de nummers aan het eind van elke waarschuwing om deze te
herleiden naar de desbetreffende locatie.
BEWAAR DEZE INSTRUCTIES
INSTRUCCIONES IMPORTANTES DE SEGURIDAD
Este símbolo de aviso indica peligro. Existe riesgo para su integridad física. Antes de manipular
cualquier equipo, considere los riesgos de la corriente eléctrica y familiarícese con los procedimientos
estándar de prevención de accidentes. Al final de cada advertencia encontrará el número que le
ayudará a encontrar el texto traducido en el apartado de traducciones que acompaña a este
dispositivo.
GUARDE ESTAS INSTRUCCIONES.
IMPORTANTES INFORMATIONS DE SÉCURITÉ
Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une situation pouvant
entraîner des blessures ou des dommages corporels. Avant de travailler sur un équipement, soyez
conscient des dangers liés aux circuits électriques et familiarisez-vous avec les procédures
couramment utilisées pour éviter les accidents. Pour prendre connaissance des traductions des
avertissements figurant dans les consignes de sécurité traduites qui accompagnent cet appareil,
référez-vous au numéro de l'instruction situé à la fin de chaque avertissement.
CONSERVEZ CES INFORMATIONS
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 16
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Dit waarschuwings symbool betekent gevaar. U verkeert in een situatie die lichamelijk letsel kan
veroorzaken. Voordat u aan enige apparatuur gaat werken, dient u zich bewust te zijn van de bij een
elektrische installatie betrokken risico's en dient u op de hoogte te zijn van de standaard procedures
om ongelukken te voorkomen. Gebruik de nummers aan het eind van elke waarschuwing om deze te
herleiden naar de desbetreffende locatie.
BEWAAR DEZE INSTRUCTIES
Installation Instructions
Warning!
Read the installation instructions before connecting the system to the power source.
警告
将此系统连接电源前,请先阅读安装说明。
警告
將系統與電源連接前,請先閱讀安裝說明。
Warnung
Vor dem Anschließen des Systems an die Stromquelle die Installationsanweisungen lesen.
¡Advertencia!
Lea las instrucciones de instalación antes de conectar el sistema a la red de alimentación.
Attention
Avant de brancher le système sur la source d'alimentation, consulter les directives d'installation.
Waarschuwing
Raadpleeg de installatie-instructies voordat u het systeem op de voedingsbron aansluit.
Circuit Breaker
Warning!
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than: 250 V, 20 A
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 17
250 V 20 A
警告
此产品的短路(过载电流)保护由建筑物的供电系统提供,确保短路保护设备的额定电流不大于
250V,20A
警告
此產品的短路(過載電流)保護由建築物的供電系統提供,確保短路保護設備的額定電流不大於 250V,20A
Warnung
Dieses Produkt ist darauf angewiesen, dass im Gebäude ein Kurzschluss- bzw. Überstromschutz
installiert ist. Stellen Sie sicher, dass der Nennwert der Schutzvorrichtung nicht mehr als: 250 V, 20 A
beträgt.
¡Advertencia!
Este equipo utiliza el sistema de protección contra cortocircuitos (o sobrecorrientes) del edificio.
Asegúrese de que el dispositivo de protección no sea superior a: 250 V, 20 A.
Attention
Pour ce qui est de la protection contre les courts-circuits (surtension), ce produit dépend de
l'installation électrique du local. Vérifiez que le courant nominal du dispositif de protection n'est pas
supérieur à :250 V, 20 A.
!
( ) .
250V( ), 20A( ) .
Waarschuwing
Dit product is afhankelijk van de kortsluitbeveiliging (overspanning) van uw electrische installatie.
Controleer of het beveiligde aparaat niet groter gedimensioneerd is dan 220V, 20A.
Power Disconnection Warning
Warning!
The system must be disconnected from all sources of power and the power cord removed from the
power supply module(s) before accessing the chassis interior to install or remove system
components.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 18
警告
在你打开机箱并安装或移除内部器件前,必须将系统完全断电,并移除电源线。
警告
在您打開機殼安裝或移除內部元件前,必須將系統完全斷電,並移除電源線。
Warnung
Das System muss von allen Quellen der Energie und vom Netzanschlusskabel getrennt sein, das von
den Spg.Versorgungsteilmodulen entfernt wird, bevor es auf den Chassisinnenraum zurückgreift, um
Systemsbestandteile anzubringen oder zu entfernen.
¡Advertencia!
El sistema debe ser disconnected de todas las fuentes de energía y del cable eléctrico quitado de los
módulos de fuente de alimentación antes de tener acceso el interior del chasis para instalar o para
quitar componentes de sistema.
Attention
Le système doit être débranché de toutes les sources de puissance ainsi que de son cordon
d'alimentation secteur avant d'accéder à l'intérieur du chassis pour installer ou enlever des
composants de systéme.
Waarschuwing
Voordat u toegang neemt tot het binnenwerk van de behuizing voor het installeren of verwijderen van
systeem onderdelen, dient u alle spanningsbronnen en alle stroomkabels aangesloten op de
voeding(en) van de behuizing te verwijderen.
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 19
Equipment Installation
Warning!
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
警告
只有经过培训且具有资格的人员才能进行此设备的安装、更换和维修。
警告
只有經過受訓且具資格人員才可安裝、更換與維修此設備。
Warnung
Das Installieren, Ersetzen oder Bedienen dieser Ausrüstung sollte nur geschultem, qualifiziertem
Personal gestattet werden.
¡Advertencia!
Solamente el personal calificado debe instalar, reemplazar o utilizar este equipo.
Attention
Il est vivement recommandé de confier l'installation, le remplacement et la maintenance de ces
équipements à des personnels qualifiés et expérimentés.
Waarschuwing
Deze apparatuur mag alleen worden geïnstalleerd, vervangen of hersteld door geschoold en
gekwalificeerd personeel.
Restricted Area
Warning!
This unit is intended for installation in restricted access areas. A restricted access area can be
accessed only through the use of a special tool, lock and key, or other means of security. (This
warning does not apply to workstations).
Supermicro SSE-C3632S/SSE-C3632SR Switch Installation Guide
Page 20
警告
此部件应安装在限制进出的场所,限制进出的场所指只能通过使用特殊工具、锁和钥匙或其它安全手段进出的场所。
警告
此裝置僅限安裝於進出管制區域,進出管制區域係指僅能以特殊工具、鎖頭及鑰匙或其他安全方式才能
進入的區域。
Warnung
Diese Einheit ist zur Installation in Bereichen mit beschränktem Zutritt vorgesehen. Der Zutritt zu
derartigen Bereichen ist nur mit einem Spezialwerkzeug, Schloss und Schlüssel oder einer sonstigen
Sicherheitsvorkehrung möglich.
¡Advertencia!
Esta unidad ha sido diseñada para instalación en áreas de acceso restringido. Sólo puede obtenerse
acceso a una de estas áreas mediante la utilización de una herramienta especial, cerradura con llave
u otro medio de seguridad.
Attention
Cet appareil doit être installée dans des zones d'accès réservés. L'accès à une zone d'accès réservé
n'est possible qu'en utilisant un outil spécial, un mécanisme de verrouillage et une clé, ou tout autre
moyen de sécurité.
Waarschuwing
Dit apparaat is bedoeld voor installatie in gebieden met een beperkte toegang. Toegang tot dergelijke
gebieden kunnen alleen verkregen worden door gebruik te maken van speciaal gereedschap, slot en
sleutel of andere veiligheidsmaatregelen.
Battery Handling
Warning!
There is the danger of explosion if the battery is replaced incorrectly. Replace the battery only with the
same or equivalent type recommended by the manufacturer. Dispose of used batteries according to
the manufacturer's instructions.
警告
电池更换不当会有爆炸危险。请只使用同类电池或制造商推荐的功能相当的电池更换原有电池。请按制造商的说明处理废旧电
池。
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41

Supermicro SSE-G3632SR Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues