Anybus AB7302 Guide d'installation

Catégorie
Passerelles / contrôleurs
Taper
Guide d'installation
1
3
5
2
4
6
Network Status
Device StatusCANopen Subnet Status
LED Ind.
(not used) Module Status
(not used)
DeviceNet
Connector
Baud Rate and
MacID Switches
SP1192, Rev 2.30, AB 7302. www.anybus.com
Module Front
Side View
Bottom View
Accessories Checklist
The following items are required for installaƟ on:
CANopen:
ACM CANopen con guraƟ on tool (available at www.anybus.com)
CANopen adapter for con guraƟ on tool (not included)
CANopen cable (not included)
• EDS le, available at www.anybus.com
DeviceNet Interface:
• DeviceNet con guraƟ on tool (not included)
• DeviceNet cable
EDS File, available at www.anybus.com
Installation and Startup Summary
Select baud rate and an unused node address for the interface.
(Cover the switches with the enclosed switch covers.)
Connect the gateway to the CANopen network.
Install the EDS le in the CANopen con guraƟ on tool.
Power up and (if required) con gure the module.
Restart the module after the CANopen interface has been
configured.
Connect the gateway to the DeviceNet network.
Set the baud rate and MacID switches.
Install the EDS file in the DeviceNet configuration tool.
Power up and (if required) configure the module.
Please note that the module will start up as a CANopen slave. The mod-
ule can be recon gured as a CANopen master during con guraƟ on.
Further informaƟ on and documents about this product can be found at
the product pages on www.anybus.com.
Technical Details
• Power supply:
24 V DC (-10% to +10%).
• Power consumpƟ on:
Maximum power consumpƟ on is 250 mA @ 24 V DC.
Typical power consumpƟ on: 100 mA @ 24 V DC.
• ProtecƟ ve Earth (PE):
Internal connecƟ on to PE via DIN-rail.
Note: Make sure the DIN-rail is properly connected to PE.
LED Indicators
A
B
1
5
6
9
CANopen Connector
Pin no. Description
2 CAN_L
5 Shield
7 CAN_H
3, 6 CAN_GND
1, 4, 8, 9 (not connected)
USB port:
Connect a PC to the
USB port for rm-
ware upgrades.
Power:
A. +24 V DC
B. GND
Address x10
Baud rate
Address x1
Setting Baud Rate (kbit/s)
020
150
2 125
3 250
4 500
5 800
6 1000
7 Auto
8, 9 Not available
Allowed node address range is 1 - 127. Addresses 1
- 99 are available using the address rotary switches.
To set e.g. node address 42, set the leŌ address
switch to 4 and the right address switch to 2. Cover
the switches with the enclosed switch covers to
ensure EMC compliance.
CANopen Support
Technical support regarding the CANopen eldbus system should be
addressed to CAN in AutomaƟ on (CiA), at: www.can-cia.org
DeviceNet Support
Technical support regarding the DeviceNet eldbus system should be
addressed to the ODVA.
Online: www.odva.com
LED no Indication Meaning
1 (Network Status) Off
Green
Flashing green
Red
Flashing red
Alternating red/green
Not online
Link OK, online, connected
Online, not connected
Critical link failure
Connection timeout
Device self-test in progress
2 (Module Status) Off
Green
Red
Flashing Red
Alternating red/green
No power
Normal operation
Unrecoverable fault
Minor fault
Device self-test in progress
3,4 (not used)
5 (CANopen Subnet
Status)1Off
Flickering green/red
Blinking green
Single ash, green
Green
Blinking red
Single ash, red
Double ash, red
Triple ash, red
Quadruple ash, red
Red
Power off
The LSS services are in progress
Pre-operational state
Stopped state
Operational state
Con guration error
Warning limit reached
Error control event
Sync error
Data communication timeout
Bus off
6 (Device Status) Off
Single ash, green
Green
Single ash, red
Double ash, red
Triple ash, red
Quadruple ash, red
Red
Power off
Bootup
Running
Initialization error
Timeout
Hardware failure
General error
Fatal error
1. This LED shows the status of the CANopen subnet that is controlled by the
X-Gateway CANopen.
DeviceNet Baud Rate and MAC ID Settings
Baud Rate Sw. 1 Sw. 2
125 kbps OFF OFF
250 kbps OFF ON
500 kbps ON OFF
(reserved) ON ON
MAC ID Sw. 3 Sw. 4 Sw. 5 Sw. 6 Sw. 7 Sw. 8
0 OFF OFF OFF OFF OFF OFF
1 OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF ON OFF
... ... ... ... ... ... ...
63 ON ON ON ON ON ON
DeviceNet Connector
Pin no Description
1V -
2 CAN L
3 Shield
4 CAN H
5V +
51
For maintenance and support, contact the HMS support department.
Contact informaƟ on is available at the support pages at
www.anybus.com.
HMS Industrial Networks AB
Box 4126
300 04 Halmstad, Sweden
Anybus® X-gatewayTM CANopen® - DeviceNetTM
INSTALLATION SHEET
UL Certi cation
This product is in accordance with the EMC directive 2014/30/EU
through conformance with the following standards:
EN 61000-6-4 (2007)
Emission standard for industrial environment
EN 55016-2-3, Class A (2010)
EN 55022, Class A (2011)
EN 61000-6-2 (2005)
Immunity for industrial environment
EN 61000-4-2 (2009)
EN 61000-4-3 (2006)
EN 61000-4-4 (2012)
EN 61000-4-5 (2014)
EN 61000-4-6 (2014)
EMC Compliance (CE)
Warnings
WARNING - EXPLOSION HAZARD - SUBSTITION OF ANY
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2.
WARNING - EXPLOSION HAZARD - WHEN IN HAZARD-
OUS LOCATIONS, TURN OFF POWER BEFORE REPLAC-
ING OR WIRING MODULES.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT WHILE THE CURCUIT IS LIVE OR UNLESS
THE AREA IS KNOWN TO BE FREE OF IGNITABLE CON-
CENTRATIONS.
WARNING - EXPLOSION HAZARD - THE USB CONNEC-
TOR IS NOT FOR USE IN HAZARDOUS LOCATIONS AND
FOR TEMPORARY CONNECTION ONLY. DO NOT USE,
CONNECT OR DISCONNECT UNLESS THE AREA IS
KNOWN TO BE NONHAZARDOUS. CONNECTION OR DIS-
CONNECTION IN AN EXPLOSIVE ATMOSPHERE COULD
RESULT IN AN EXPLOSION.
WARNING - INSTALL IN AN ENCLOSURE CONSIDERED
REPRESENTATIVE OF THE INTENDED USE.
ATEX Certi cation
1
2
1
2
DIN Rail Mounting
To mount the gateway on a DIN
rail, rst press it downwards (1)
to compress the spring in the rail
mechanism, then push it against
the rail as to make it snap on (2).
To dismount the gateway, push it
downwards (1) and pull it out from
the rail (2).
Further information and documents about this product can be
found at the product pages on www.anybus.com.
HMS Industrial Networks AB
Box 4126
300 04 Halmstad, Sweden
Attention!
ATTENTION – RISQUE D’EXPLOSION – LE
REMPLACEMENT DE TOUT COMPOSANTS INVALIDE LA
CERTIFICATION CLASS I, DIVISION 2.
ATTENTION – RISQUE D’EXPLOSION – EN ZONE
EXPLOSIVE, VEUILLEZ COUPER L’ALIMENTATION
ÉLECTRIQUE AVANT LE REMPLACEMENT OU LE
RACCORDEMENT DES MODULES.
ATTENTION – RISQUE D’EXPLOSION – NE PAS
DÉCONNECTER L’ÉQUIPEMENT TANT QUE
L’ALIMENTATION EST TOUJOURS PRÉSENTE OU QUE LE
PRODUIT EST TOUJOURS EN ZONE
EXPLOSIVE ACTIVE.
ATTENTION – RISQUE D’EXPLOSION – LE CONNECTEUR
USB N’EST PAS FAIT POUR UN USAGE EN MILIEU
EXPLOSIF. NE PAS, BRANCHER ET DEBRANCHER
SANS SAVOIR SI LA ZONE N’EST PAS IDENTIFIEE NON
EXPLOSIVE. BRANCHER OU DEBRANCHER EN ZONE
EXPLOSIVE PEUT ENTRAINER UNE EXPLOSION.
AVERTISSEMENT – INSTALLER DANS UNE ARMOIRE
VERROUILLEE VALIDANT L’ACTE VOLONTAIRE
D’UTILISATION.
Additional Installation and Operating Instructions
This equipment requires a regulated 24 V (21.6 V to 26.4 V) DC
power source
Field wiring terminal markings (wire type (Cu only, 14-30 AWG))
Use 60/75 or 75 °C copper (Cu) wire only.
Terminal tightening torque: 5–7 lb-in (0.5–0.8 Nm)
Use in Overvoltage Category I Pollution Degree 2 Environment
conforming to EN 60664-1.
Operating temperature/Surrounding temperature:
-25 to +55 °C @ 250 mA @ 24 V DC
Maximum surface temperature: 135 °C
Pressure: 850–1050 millibar (85–105 kPa)
This product is designed to safely operate in class I, division 2 Haz-
ardous location according to ANSI/ISA 12.12.01-2013 and category 3,
zone 2 according to EN 60079-0:2012 and EN 60079-15:2010.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C
AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS
LOCATIONS ONLY.
To comply with ATEX directives, the equipment must be installed
within an IP54 enclosure and must be installed with a transient sup-
pressor on the supply that does not exceed 140 % (33.6 V DC) of the
nominal rated supply voltage.
Anybus® X-gatewayTM CANopen®
INSTALLATION SHEET
  • Page 1 1
  • Page 2 2

Anybus AB7302 Guide d'installation

Catégorie
Passerelles / contrôleurs
Taper
Guide d'installation

dans d''autres langues