CD Automation CD3000S 2PH Manuel utilisateur

Taper
Manuel utilisateur
USER’S MANUAL
Rev. 03/2023
2PH
From 10 to 90A
004
M-3000S2-10-90
CD3000S
CD Automation S.r.l.
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: inf[email protected] - Web: www.cdautomation.com
Declaration of conformity
Declaration of conformity - Dichiarazione di Conformità
PRODUCT MANUFACTURER / PRODUTTORE:
CD Automation S.R.L.
Controllers, Drives & Automation
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: inf[email protected] - Web: www.cdautomation.com
Declare that the product / Dichiara che il prodotto:
CD3000S 2PH 10-90A
PRODUCT DESCRIPTION: Electric power control
SCOPE OF APPLICATION: Thermal control process
DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica
UTILIZZO: Controllo processi termici
FULFILS THE REQUIREMENTS OF THE STANDARD:
Electrical safety Standard EN60947-1: 2007 + A1 2011, A2 2014
EN60947-4-3: 2014
Generic Emission standard EN60947-4-3: 2014 Group 1 Class A emissions
Generic Immunity standard EN60947-4-3: 2014 Industrial Immunity
SODDISFA I REQUISITI DELLA NORMA:
Specica di sicurezza EN60947-1: 2007 + A1 2011, A2 2014
EN60947-4-3: 2014
Specica sulle emissioni EN60947-4-3: 2014 gruppo 1 emissioni classe A
Specica sulle Immunità EN60947-4-3: 2014 Immunità industriale
CDAutomation declares that the products above mentioned are conforming to the directive
CDAutomation dichiara che i prodotti sopra menzionati sono conformi alla direttiva
Bassa Tensione (low Voltage) EMC directive updated 2014/30/EU,
Low Voltage Directive updated 2014/35/EU
Issued on: 20/03/2017
Data di emissione: 20/03/2017
Amministratore Unico e
Legale Rappresentante
Simone Brizzi
Declaration of conformity
Declaration of conformity - Dichiarazione di Conformità
PRODUCT MANUFACTURER / PRODUTTORE:
CD Automation S.R.L.
Controllers, Drives & Automation
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: inf[email protected] - Web: www.cdautomation.com
Declare that the product / Dichiara che il prodotto:
CD3000S 2PH 10-90A
PRODUCT DESCRIPTION: Electric power control
SCOPE OF APPLICATION: Thermal control process
DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica
UTILIZZO: Controllo processi termici
FULFILS THE REQUIREMENTS OF THE STANDARD:
Electrical safety Standard EN60947-1: 2007 + A1 2011, A2 2014
EN60947-4-3: 2014
Generic Emission standard EN60947-4-3: 2014 Group 1 Class A emissions
Generic Immunity standard EN60947-4-3: 2014 Industrial Immunity
SODDISFA I REQUISITI DELLA NORMA:
Specica di sicurezza EN60947-1: 2007 + A1 2011, A2 2014
EN60947-4-3: 2014
Specica sulle emissioni EN60947-4-3: 2014 gruppo 1 emissioni classe A
Specica sulle Immunità EN60947-4-3: 2014 Immunità industriale
CDAutomation declares that the products above mentioned are conforming to the directive
CDAutomation dichiara che i prodotti sopra menzionati sono conformi alla direttiva
Bassa Tensione (low Voltage) EMC directive updated 2014/30/EU,
Low Voltage Directive updated 2014/35/EU
Issued on: 07/03/2022
Data di emissione: 07/03/2022
Amministratore Unico e
Legale Rappresentante
Simone Brizzi
4
CD3000S 2PH from 10A to 90A User’s manual
Important warnings for safety
This chapter contains important information for the safety. The not observance of these instructions may result
in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components
system included.
The installation should be performed by qualied persons.
In the manual are used symbols to give more evidence at the notes of safety and operativity for the attention
for the user:
This icon is present in all the operational procedures where the Improper
operation may result in serious personal injury or death by Electrical Shock
Hazard Symbol (a lightning bolt in a triangle) precedes an electric shock hazard
CAUTION or WARNING safety statement.
Warning or Hazard that needs further explanation than the label on unit can
provide. Consult User’s Guide for further information.
Unit is compliant with European Union directives.
See Declaration of Conformity for further details on Directives and Standards
used for Compliance.
If available, unit is a Listed device per Underwriters Laboratories. It has been
investigated to ANSI/UL® 508 standards for Industrial Control Switches and
equivalent to CSA C22.2 #14.
For more detail search for File E231578 on www.ul.com
ESD Sensitive product, use proper grounding and handling techniques when
installing or servicing product.
Do not throw in trash, use proper recycling techniques or consult manufacturer
for proper disposal.
A “NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your equipment and
performance. Be especially careful to read and follow all cautions that apply to your application.
A “WARNING” safety alert appears with information that is important for protecting you, others and equipment
from damage. Pay very close attention to all warnings that apply to your application.
Safety notes
WARNING! To avoid damage to property and equipment, injury and loss of life, adhere to applicable
electrical codes and standard wiring practices when installing and operating this product. Failure to do
so could result in damage, injury and death.
AVERTISSEMENT! Pour éviter d’endommager la propriété et l’équipement, les blessures et la perte
de vie, respecter les codes électriques en vigueur et les pratiques de câblage standard au moment
de l’installation et de l’utilisation de ce produit. Dans le cas contraire, cela peut entraîner la mort, des
blessures graves ou des dommages.
UL
CD3000S 2PH from 10A to 90A User’s manual
5
WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse
or other user serviceable component replacement must be performed only by properly qualied
personnel. Service personnel must read this manual before proceeding with work. While service is
being performed unqualied personnel should not work on the unit or be allowed in the immediate
vicinity.
AVERTISSEMENT! Tous les services, y compris l’inspection, l’installation, le câblage, l’entretien, le
dépannage, le remplacement de fusibles ou d’autres composants pouvant être réparés par l’utilisateur,
doivent être eectués uniquement par un personnel diment qualié. Le personnel de service doit lire ce
manuel avant d’eectuer tout travail. Pendant que l’entretien est exécuté, tout personnel non qualié ne
doit eectuer de travail sur l’appareil ni se trouver a proximité.
WARNING! When in use the power controller is connected to dangerous voltages. Do not remove the
protective covers without rst disconnecting and preventing power from being restored while servicing
the unit.
AVERTISSEMENT! Au moment de l’utilisation, le régulateur de puissance est connecté a des tensions
dangereuses. Ne retirer aucun couvercle de protection sans d’abord débrancher l’appareil et ainsi
empêcher l’alimentation d’être rétablie pendant l’entretien.
WARNING! Do not use in aerospace or nuclear applications.
AVERTISSEMENT! Ne pas utiliser pour les applications aérospatiales ou nucléaires.
WARNING! The units are not developed to manage capacitive and inductive loads.
AVERTISSEMENT! Les unités ne sont pas développées pour la conduite de charges capacitives et
inductives.
WARNING! The power controller’s protection rating is IP20 with all covers installed and closed. It must
be installed in an enclosure that provides all the necessary additional protections appropriate for the
environment and application.
AVERTISSEMENT! L’indice de protection du régulateur de puissance est de IP20 lorsque les couvercles
sont installés et fermés. L’appareil doit être installé dans une enceinte qui assure toute la protection
supplémentaire nécessaire pour l’environnement et l’application.
WARNING! Ground the power controller via the provided protective earth grounding terminal. Verify
ground is within impedance specications. This should be veried periodically.
AVERTISSEMENT! Mise a la terre du régulateur de puissance par le biais de la borne de prise de terre
de protection fournie. Vérier que la prise de terre est conforme aux spécications de l’impédance. Cela
doit être vérié périodiquement.
WARNING! Electric Shock Hazard: when the power controller has been energized, after shutting othe
power, wait at least one minute for internal capacitors to discharge before commencing work that brings
you in to contact with power connections or internal components.
AVERTISSEMENT! Risque de décharges électriques: lorsque le régulateur de puissance est mis sous
tension, après avoir été éteint, attendre au moins une minute pour que les condensateurs internes se
déchargent avant de commencer tout travail incluant le contact avec les connexions électriques ou les
composants internes.
WARNING! The installation must be protected by electromagnetic circuit breakers or by fuses. The
semiconductor fuses located inside the power controller are classied for UL as supplementary
protection for semiconductor devices. They are not approved for branch circuit protection.
AVERTISSEMENT! L’installation doit être protégée par des disjoncteurs électromagnétiques ou des
fusibles. Les fusibles pour semi-conducteurs situés a l’intérieur du régulateur de puissance sont classés
UL comme protection supplémentaire pour les dispositifs pour semi-conducteurs. Ils ne sont pas
approuvés pour la protection des circuits de dérivation.
WARNING! When making live voltage or current measurements, use proper personal protective
equipment for the voltages and arc-ash potentials involved.
6
CD3000S 2PH from 10A to 90A User’s manual
AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un
équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique
concernés.
WARNING! Verify the voltage and current ratings of the power controller are correct for the application.
AVERTISSEMENT! Vérier que les valeurs de tension et de courant du régulateur de puissance sont
correctes pour l’application.
CAUTION: To avoid compromising the insulation, do not bend wire or other components beyond their
bend radius specications.
ATTENTION: Pour éviter de compromettre l’isolation, ne pas plier le l ou tout autre composant au-delà
de ses spécications en matière de rayon de courbure.
CAUTION: Protect the power controller from high temperature, humidity and vibrations.
ATTENTION: Protéger le régulateur de puissance contre les températures élevées, l’humidité et les
vibrations.
CAUTION: The power controller warranty is void if the tested and approved fuses are not used.
ATTENTION: La garantie du régulateur de puissance est nulle si aucun fusible testé et approuvé n’est
utilisé.
CAUTION: Only trained and authorized personnel should access and handle the internal electronics
and they must follow proper electro-static prevention procedures.
ATTENTION: Seul le personnel formé et autorisé peut accéder aux composants électroniques internes
et les gérer, et il doit se conformer a des procédures de prévention électrostatique appropriées.
CAUTION: Install an appropriately sized RC lter across contactor coils, relays and other inductive
loads.
ATTENTION: Installer un ltre RC de dimensions appropriées sur les bobines du contacteur, les relais et
autres charges par induction.
CAUTION: The thyristor units here described have been designed for use with sinusoidal networks with
nominal frequency 50-60 Hz. Any application with NON-SINUSOIDAL, distorted or disturbed networks
could compromise the correct operation of the unit.
ATTENTION: Les unités de thyristors décrites ici ont été conçues pour être utilisées avec des réseaux
sinusoïdaux d’une fréquence nominale de 50 à 60 Hz. Toute application utilisant des réseaux NON
SINUSOÏDAUX, déformés ou perturbés peut compromettre le bon fonctionnement de l’appareil.
NOTE: Provide a local disconnect to isolate the power controller for servicing.
REMARQUE: Fournir une déconnexion locale an d’isoler le régulateur de puissance pour l’entretien.
NOTE: The nominal current is specied for ambient temperatures at or below 40° C. Ensure the application
design allows for adequate cooling of each power controller. The power controller must be mounted
vertically. The cooling design must prevent air heated by one power controller from causing power
controllers mounted above to exceed the ambient operating temperature limit. When power controllers
are mounted side by side allow a minimum spacing of 15mm between them.
REMARQUE: Le courant nominal est précisé pour des températures ambiantes égales ou inférieures
a 40°C. S’assurer que la conception de l’application permette le refroidissement adéquat de chaque
régulateur de puissance. Le régulateur de puissance doit être monté verticalement. La conception de
refroidissement doit empêcher l’air chaué par le régulateur de puissance de dépasser la limite de
température de fonctionnement ambiante de la part des régulateurs de puissance montés au-dessus.
Lorsque les régulateurs de puissance sont montés côte a côte, il faut conserver un espacement minimal
de 15 mm entre les deux.
NOTE: Use only copper cables and wires rated for use at 75°C or greater.
REMARQUE: N’utiliser que des cables et des ls en cuivre pour l’utilisation a 75°C ou plus.
CD3000S 2PH from 10A to 90A User’s manual
7
Maintenance
In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the fans. The
frequency of this servicing depends on environmental pollution.
Also check periodically if the screw for the power cables and safety earth are tightened correctly
(See Connection Diagram)
Warranty condition
Producer gives a 12 months warranty to its products.
The warranty is limited to repairing and parts substitution in our factory and does
exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty
product should be shipped to Producer at customer’s cost and our Service will
evaluate if product is under warranty terms.
Substituted parts remain of Producer property.
Return Material Authorization (RMA)
Customers wishing to return any items, whether they are incorrectly supplied, faulty or damaged in transit,
must rst complete a Return Material Authorisation (RMA) form to obtain an RMA number from the Service
Department.
A full repair service is available for customers. Prior to submitting the RMA form and returning products,
customers are recommended to contact the technical support team to determine whether the issue can be
resolved with telephone support.
How the RMA service works
The RMA form and details are availableon our web sites:
https://www.cdautomation.com/rma-english-version/
When completing the RMA form, please be as specic as possible about the problem, including any pertinent
application details. The more information given, the more quickly and more thoroughly the problem can be
solved. The minimum information required is:
1. The Full Model Number
2. Quantity of units being returned
3. The units Serial Number(s)
4. A description of the problem (“faulty” or “unknown is not sucient)
CD Automation srl assumes no liability for any damage to persons or property deriving from tampering, from
incorrect or improper use, or from any use not conforming to the characteristics of the controller and to the
instructions in this User Manual.
8
CD3000S 2PH from 10A to 90A User’s manual
Declaration of conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Important warnings for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1.1 Standard version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 Analog Input and/or HB Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Basic Connections and sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Identication and Order Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3.1 Identication of the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Order Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Technical Specication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1 General features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 Input features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Power output features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.4 Environmental installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5 Derating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.6 Led Status and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.1 Dimensions and xing holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wiring instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.1 Diagram of control connection - Standard Version . . . . . . . . . . . . . . . . . . . . 18
6.2 Diagram of control connection - Analog Input and/or Heater Break Options . . . 21
Heater break alarm and SCR short circuit . . . . . . . . . . . . . . . . . . . . . .22
7.1 HB alarm contact (only with the HB option) . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.2 Heater break Calibration procedure (only with the HB option). . . . . . . . . . . . . 23
Firing Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
8.1 Firing Setting with Analog Input Option . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.2 Firing Setting with Heater Break Option . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Input Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
9.1 Input Setting with Analog Input Option . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.2 Input Calibration procedure (only with Analog Input Option) . . . . . . . . . . . . . 26
Fuses and Fuse holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
1
2
3
4
5
6
7
8
9
10
Summary
CD3000S 2PH from 10A to 90A User’s manual
9
Quick Start
1.1 Standard version
Attention: this procedure must be carried out by skilled people only.
If the Order Code of the Thyristor unit is in line with what you really need, then CD3000S has been already
congured in Factory and you just need to do the following steps:
1. Verify CD3000S Sizing. Be sure that:
The load current is equal or less than the Max current of CD3000S.
The load voltage is equal or less than the Max voltage of CD3000S
2. Verify the Order Code
3. Verify the Installation
4. Verify the Diagram of control connection:
verify that there isn’t a short circuit on the load
5. Supply the Power unit
The CD3000S is ready to start
1.2 Analog Input and/or HB Option
Attention: this procedure must be carried out by skilled people only.
If the Order Code of the Thyristor unit is in line with what you really need, then CD3000S has been already
congured in Factory and you just need to do the following steps:
1. Verify CD3000S Sizing. Be sure that:
The load current is equal or less than the Max current of CD3000S.
The load voltage is equal or less than the Max voltage of CD3000S
2. Verify the Order Code
3. Verify the Installation
4. Verify the Diagram of control connection:
all auxiliary connections must be done in line with wirings on this manual
verify that there isn’t a short circuit on the load
5. Supply the auxiliary voltage of the unit (see Order Code)
6. Supply the Power unit
7. If you have HB option makes Calibration procedure
The CD3000S with Analog Input and/or Heater Break Option is ready to start
1
10
CD3000S 2PH from 10A to 90A User’s manual
Basic Connections and sizing
Wiring with resistive Load
Delta wiring
V = Nominal load voltage phase to phase
I = Nominal load current
P = Nominal load power
Star wiring
2
V
V
I= P
1,73V
CD3000S 2PH from 10A to 90A User’s manual
11
Identification and Order Code
3.1 Identication of the Unit
Caution: Before to install, make sure that the Thyristor unit have not damages. If the product
has a fault, please contact the dealer from which you purchased the product.
The identication label give all the information regarding the factory settings of the Thyristor unit, this label is
on the unit, like represented in gure.
Verify that the product is the same thing as ordered.
3
12
CD3000S 2PH from 10A to 90A User’s manual
3.2 Order Code
CURRENT (A) 4 5 6
description Code OLD code Note
10A 010 10A 1
15A 0 1 5 15A
25A 0 2 5 25A
35A 0 3 5 35A
45A 0 4 5 45A
75A 0 7 5 75A
90A 0 9 0 90A 1
OPERATING VOLTAGE (V) -
description Code OLD code Note
From 24V to Max Load Voltage
not in the code
_ _ _V
MAX LOAD VOLTAGE (V) 7
description Code OLD code Note
480V 4
600V 6
AUXILIARY VOLTAGE (V) 8
description Code OLD code Note
NO Auxiliary Voltage supply 0 NO /
12÷24V with analog input / HB Alarm 4 12:24 / 2,3
INPUT 9
description Code OLD code Note
SSR from 4 to 30Vdc S SSR /
Analog Input10V V0÷10V / 3,5
Analog Input 4
÷20mA
A4
÷20mA /
3,5
FIRING 10
description Code OLD code Note
Zero Crossing with SSR Input Z ZC /
4 cycles on + 4 o with Analog Input 4BF004 /
8 cycles on + 8 o with Analog Input 8BF008 /
16 cycles on + 16 o with Analog Input 6BF016 /
CONTROL MODE 11
description Code OLD code Note
Open loop 0
not in the code
FUSES & OPTION 12
description Code OLD code Note
No Fuse / No Option 0 NF / -
No Fuse / HB Option for SSR input 1 NF / HB 5
No Fuse / HB Option for analog input 1 5
External Fuse & Fuse Holder / No Option F EF / -
External Fuse & Fuse Holder / HB Option
for SSR input 2EF / HB 5
External Fuse & Fuse Holder / HB Option
for analog input 2EF / HB 5
FAN VOLTAGE 13
description Code OLD code Note
No Fan for unit <75A 0 - /
Fan 110V Option - for 75A and 90A units 1 110VFAN/
Fan 220V Standard - for 75A and 90A units 2
not in the code
APPROVALS 14
description Code OLD code Note
CE EMC for European Market 0 - /
CE EMC + cUL us listed L UL /
MANUAL 15
description Code OLD code Note
None 0
NM
Italian 1
IM
English 2
EM
German 3GM
French 4FM
IP PROTECTION 16
description Code OLD code Note
Standard IP20
(all unit excluded 45A, 75A, 90A) 0- /
External IP20 protection for size S7/S8
(45A, 75A, 90A) PEP /
(1) For 10A 600V and for 90A cUL us not available
(2) Necessary with 0÷10V - 4÷20mA or HB alarm
(3) Option available from 45 to 90A
(4) IP20 is standard on all units with exception of S7 and S8 size (45-75-90A).
To complain IP20 use “P” option at digit 16
(5) HB option not available with UL approval
New Code (example):
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CD3000S 2PH D S 2 0 7 5 - 4 4 V 8 0 1 2 0 2 P
Old Code (example):
Model Current
(A)
Operating
Voltage
(V)
Max Load
Voltage
(V)
Aux
Voltage
(V) Input Firing Fuses HB
Option EP
Option Approvals Manual
CD3000S 2PH / 75A / 400V / 480V / 12:24V / 4-20mA / BF008 / EF / HB / EP / - / EM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CD3000S 2PH DS2___-__________
CD3000S 2PH from 10A to 90A User’s manual
13
Technical Specification
4.1 General features
Cover and Socket material: PolymericV2
Heat-sink: Anodized aluminum
Delay switch ON time: 0.5 period Max
Delay switch OFF time: 0.5 period Max
Auxiliary Voltage: 12÷24V dc/ac (max 70mA)
Fan Voltage 220Vac ± 15%
(only for Size S8) (110 Vac option)
4.2 Input features
Analog Input: 4 - 20mA
(Loop Powered) (6,5Vdc Min)
Logic input SSR: 4 - 30Vdc 20mA Max
(Standard for size S0-S1) (ON ≥ 4Vdc - OFF < 1Vdc)
Logic input SSR: 4 - 30Vdc 15mA Max
(Standard for size S4-S7-S8) (ON ≥ 4Vdc - OFF < 1Vdc)
Logic input SSR: 5 - 30Vdc 12mA Max
(low current) (ON ≥ 5Vdc - OFF < 1Vdc)
Version with Analog Input Option:
Analog Input:
(Standard) 0 ÷ 10Vdc (15 kΩ)
Analog Input: 4 ÷ 20mA (100 Ω)
Heater Break Alarm (Optional):
Is a microprocessor based circuit to diagnose partial or total load failure and short circuit on SCR and fuses
failure. Discrimination better than 20%. Latching alarm.
Relay Output: 0.5A at 125VAC
4.3 Power output features
Size Voltage
range
Repetitive peak
reverse
Voltage
Latching
current
Max peak
one cycle
Leakage
current
I2t value
thyristor
Frequency
range
Power
loss
Isolation
Voltage
(A) (V) 480V 600V (mAe) (10ms) (A) (mAe) tp=10msec (Hz) I=Inom
(W) Vac
10A (S0) 24÷480 1200 1200 150 230 15 610 47÷70 20 2500
15A (S1) 24÷480 1200 1200 150 230 15 610 47÷70 36 2500
25A (S1) 24÷480 1200 1200 150 230 15 610 47÷70 60 2500
35A (S4) 24÷600 1200 1600 250 600 15 1800 47÷70 88 2500
45A (S7) 24÷600 1200 1600 450 1000 15 4750 47÷70 108 2500
75A (S8) 24÷600 1200 1600 450 1350 15 8830 47÷70 180 2500
90A (S8) 24÷600 1200 1600 450 2000 15 19100 47÷70 240 2500
4
14
CD3000S 2PH from 10A to 90A User’s manual
4.4 Environmental installation conditions
Ambient temperature 0-40°C (32-104°F) at nominal current.
Over 40°C use the derating curve (max 50°C).
Storage temperature -25°C to 70°C, -13°F to 158°F
Installation place Don’t install at direct sun light,
where there are conductive dust, corrosive gas,
vibration or water and also in salty environmental.
Altitude Up to 1000 meter over sea level.
For higher altitude reduce the nominal current
of 2% for each 100m over 1000m
Humidity From 5 to 95% without condense and ice
Pollution Level Up to 2nd Level ref. IEC 60947-1 6.1.3.2
4.5 Derating curve
l max = l nominal x K
1
15 20 25 30 35 40 45 50 55
1,2
1
0,8
0,6
0,4
0,2
0
1 1 1 1
0,9
0,8
K
CABINET TEMPERATURE °C
Derating
For higher cabinet
temperature
(more than 50°C)
contact the producer
of the unit
4.6 Led Status and Alarms
Only with Options Analog Input and/or Heater Break
The following events and alerts don’t stop the unit:
SCR Short circuit (only with the HB option)
Heater Break (only with the HB option)
When one of these alarms is active, the HB Relay change status.
LED STATUS DESCRIPTION
ON Load IS NOT powered
Load IS powered
SC SCR OK
SCR Short Circuit
HB Load OK
Load Fault
CD3000S 2PH from 10A to 90A User’s manual
15
Installation
Before to install, make sure that the Thyristor unit have not
damages.
If the product has a fault, please contact the dealer from which
you purchased the product. Verify that the product is the same
thing as ordered.
The Thyristor unit must be always mounted in vertical position
to improve air cooling on heat-sink.
Maintain the minimum distances in vertical and in horizontal as
represented.
When more unit has mounted inside the cabinet maintain the air
circulation like represented in gure.
Sometimes is necessary installing a fan to have better air
circulation.
5
≥5 cm
≥15 cm
≥2 cm
AIR
AIR
5.1 Dimensions and xing holes
Size: S0 Size: S1
120 mm
Ø 4,5 mm
30 mm
120 mm
110 mm
Ø 4,5 mm
30
60 mm
120 mm
110 mm
16
CD3000S 2PH from 10A to 90A User’s manual
Size: S4
Size: S7
Size: S8
159 mm
Ø 4,5 mm
117 mm
65 mm
120 mm
110 mm
123 mm
Ø 4,5 mm
117 mm
120 mm
65 mm
110 mm
159 mm
Ø 4,5 mm
117 mm
65 mm
138 mm
110 mm
CD3000S 2PH from 10A to 90A User’s manual
17
Wiring instructions
CD3000S unit has isolated heatsink. For safety connect the heatsink to earth using its terminal with earth
symbol.
CD3000S can be susceptible to airborne interferences from near equipment or from interferences on main
supply, so a number of precautions must be taken.
Contactors coils and chokes must have in parallel a RC lter and must be supplied with a dierent voltage
line.
All input/output signals must use screened bilar wires.
Signal input and output must not route in same cable try and must not be parallel.
Local regulations regarding electrical installation should be rigidly observed
Use copper cables and wires rated for use at 75 °C only.
Use wire terminal UL Listed (ZMVV).
Power cable torque (suggested)
Current Connector Type Torque Lb-in (N-m) Wire Range
AWG/kcmil
Wire Terminal
UL listed (ZMVV)
10A, 15A, 25A, 35A M5 Screw 26.6 (3.0) 8 Wire Pin
45A, 75A, 90A M6 Screw 70.8 (8.0) 1 Fork/Spade terminal
Copper Tube Crimp. Lug
Cable dimensions (suggested)
Current
Supply Load Earth Auxiliary Supply
Cable Screw
M
Cable Screw
M
Cable Screw
M
Cable
mm2AWG mm2AWG mm2AWG mm2AWG
10A (S0) 4 12 M5 4 12 M5 4 12 M5 0,50 18
15A (S1) 4 12 M5 4 12 M5 4 12 M5 0,50 18
25A (S1) 6 10 M5 6 10 M5 6 10 M5 0,50 18
35A (S4) 10 8 M5 10 8 M5 6 10 M5 0,50 18
45A (S7) 10 8 M6 10 8 M6 6 10 M5 0,50 18
75A (S8) 25 4 M6 25 4 M6 6 10 M5 0,50 18
90A (S8) 35 3 M6 35 3 M6 6 10 M5 0,50 18
6
18
CD3000S 2PH from 10A to 90A User’s manual
6.1 Diagram of control connection - Standard Version
Size S0 - Standard version 10A
Note:
The user installation must be protected by electromagnetic circuit breaker or by fuse isolator.
L2
L1
L2
L3 L3
L1
SSR
L1 T1
L2 T2
LOAD
Input:
CD3000S 2PH from 10A to 90A User’s manual
19
Size S1 - Standard version 15A-25A
Note:
The user installation must be protected by electromagnetic circuit breaker or by fuse isolator.
L2
L1
L2
L3 L3
L1
SSR
T1
A2+
L1
A1-
POWER UNIT
T2
A2+
L2
A1-
POWER UNIT
LOAD
Input:
20
CD3000S 2PH from 10A to 90A User’s manual
Size S4 - Standard version 35A
Size S7 - Standard version 45A
Size S8 - Standard version 75A, 90A
Note:
The user installation must be protected by electromagnetic circuit breaker or by fuse isolator.
L2
L1
L2
L3 L3
L1
SSR
T1
L2
FAN
T3T2
A1-A2+
L3L1
POWER UNIT
LOAD
Input:
Fan Power
Supply
(for size S8)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29

CD Automation CD3000S 2PH Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues