Allen-Bradley FLEX I/O 1794-APBDPV1 Guide d'installation

Taper
Guide d'installation
Publication 1794-IN114A-EN-P - July 2008
Installation Instructions
FLEX I/O PROFIBUS Communications
Adapter
1794-APBDPV1
European Hazardous Location Approval
The following modules are European Zone 2 approved: 1794-APBDPV1
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.literature.rockwellautomation.com) describes
some important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or
death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding
of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions
help you:
identify a hazard
avoid a hazard
recognize the consequence
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without
derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate precautions,
there may be potential difficulties ensuring electromagnetic compatibility
in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted
within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed
to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information regarding
specific enclosure type ratings that are required to comply with certain
product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for
additional installation requirements, Allen-Bradley publication
1770-4.1.
NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.
ATTENTION
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The use
of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
Store the equipment in appropriate static-safe packaging when not
in use.
European Zone 2 Certification (The following applies when the product bears the
Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15.
IMPORTANT
Observe the following additional Zone 2 certification requirements:
This equipment is not resistant to sunlight or other sources of UV
radiation.
This equipment must be installed in an enclosure providing at least
IP54 protection when applied in Class I, Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in
Class I, Zone 2 environments.
Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided
with this product.
Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
2 FLEX I/O PROFIBUS Communications Adapter
Publication 1794-IN114A-EN-P - July 2008
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
1794-APBDPV1.
FLEX I/O PROFIBUS Adapter 1794-APBDPV1
Install Your Adapter Module
Mounting on a DIN rail before installing the Terminal Base Units
1. Position the adapter module (A) on a 35 x 7.5 mm (3 x 0.3 in.) DIN rail (B)
at a slight angle.
2. Hook the lip on the rear of the adapter onto the top of the DIN rail, and
rotate the adapter module onto the rail.
3. Press the adapter module down onto the DIN rail until flush. Locking tab
C will snap into position and lock the adapter module to the DIN rail.
4. If the adapter module does not lock in place, use a screwdriver or similar
device to move the locking tab down while pressing the adapter module
flush onto the DIN rail, and release the locking tab to lock the adapter
module in place. If necessary, push up on the locking tab to lock.
5. Connect the adapter wiring as shown under “Connect Wiring for your
Module ”.
Remove the debris wrapper before applying power to the module.
Panel/Wall Mounting
If mounting this adapter to a panel or wall, refer to publication 1794-5.13, “Panel
Mounting Kit, Cat. No. 1794-NM1.”
Mount (or Replace) the Adapter on an Existing System
1. Remove the PROFIBUS connector from the front of the adapter.
The following information applies
when operating this equipment in
hazardous locations:
Informations sur l’utilisation de cet
équipement en environnements dangereux :
Products marked “CL I, DIV 2, GP A, B, C, D”
are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining
products within a system, the most adverse
temperature code (lowest “T” number) may
be used to help determine the overall
temperature code of the system.
Combinations of equipment in your system
are subject to investigation by the local
Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D"
ne conviennent qu’à une utilisation en
environnements de Classe I Division 2 Groupes
A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa
plaque d’identification qui indiquent le code de
température pour les environnements
dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de
température le plus défavorable (code de
température le plus faible) peut être utilisé pour
déterminer le code de température global du
système. Les combinaisons d’équipements dans
le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l’installation.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless
power has been removed or the area
is known to be nonhazardous.
Do not disconnect connections to
this equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
Substitution of components may
impair suitability for Class I,
Division 2.
If this product contains batteries,
they must only be changed in an area
known to be nonhazardous.
AVERTISSEMENT
RISQUE D’EXPLOSION
Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher l'équipement.
Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.
S’assurer que l’environnement est
classé non dangereux avant de changer
les piles.
WARNING
If you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this equipment must
be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION
To comply with UL restrictions, this equipment must be powered from a
source compliant with the following:
Class 2 or Limited Voltage/Current.
Description Description
1 Flexbus connector 4 Node address thumbwheel switches
2 24V common connections 5 PROFIBUS connector
3 24V DC connections 6 Status indicators
ATTENTION
During mounting of all devices, be sure that all debris (such as metal chips
and wire stands) is kept from falling into the module. Debris that falls into
the module could cause damage on power up.
6
5
4
3
2
1
44553
B
C
A
44554
FLEX I/O PROFIBUS Communications Adapter 3
Publication 1794-IN114A-EN-P - July 2008
2. Disconnect any wiring jumpered to the adjacent terminal base.
3. Open the module latching mechanism and remove the module from the
base unit to which the adapter will be attached.
4. Push the flexbus connector toward the right side of the terminal base to
unplug the backplane connection.
5. Release the locking tab (C) and remove the adapter module.
6. Before installing the new adapter, notice the notch on the right rear of the
adapter. This notch accepts the hook on the terminal base unit. The notch
is open at the bottom. The hook and adjacent connection point keep the
terminal base and the adapter tight together, reducing the possibility of a
break in communication over the backplane.
7. Complete the adapter mounting as follows.
a. Push down and in at the same time to lock the adapter to the DIN rail.
If the adapter does not lock in place, use a screwdriver or similar
device to move the locking tab down while pressing the adapter flush
onto the DIN rail, and release the locking tab to lock the adapter
module in place. If necessary, push up on the locking tab to lock.
b. When the adapter is locked onto the DIN rail, gently push the flexbus
connector into the adapter to complete the backplane.
8. Reinstall the module in the adjacent terminal base unit.
Connect Wiring for your Module
1. Connect the PROFIBUS drop cable to the 9-pin D-shell connector
according to the following pin assignments.
2. Connect the cable shield to pin 1.
The shield is connected to earth ground.
3. Connect the data signal pins on both ends (signal + pin 3 and signal -
pin 8).
4. Insert the wired connector into the mating connector on the adapter.
5. Connect +V DC power to the left side of the lower connector, terminal E.
6. Connect -V common to the left side of the upper connector, terminal D.
WARNING
If you connect or disconnect the PROFIBUS cable with power applied to this
module or any device on the network, an electrical arc can occur. This could
cause an explosion in hazardous location installations. Be sure that power
is removed or the area is nonhazardous before proceeding.
C
Flexbus connector
44555
44556
C
44557
WARNING
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
PIN RS-485 Reference Signal Description
1 Shield Shield, RC to earth ground
2 RP Not used
3 B/B’ RXD/TXD-P Receive/transmit data - P
4 CTNR-P Not used
5 C/C’ DGND Data ground
6 VP Voltage plus (+5V)
7 RP Not used
8 A/A RXD/TXD-N Receive/transmit data - N
9 CTNR-N Not used
Metal shell Earth ground
ATTENTION
Total power connection wire length must be less than 10 m (32.8 ft).
1
.
.
Data Ground
Shield
Pin #1
5
RCV/ Xmit Data +
9
6
.
.
DROP CABLE
PROFIBUS
ADAPTER
Signal + Pin #3
Pin #5
+5V Pin #6
Signal - Pin #8
Earth Ground
RCV/ Xmit Data -
.
*
Pins #5 and #6 can be used to supply an external Profibus terminator.
*
44558
G
E
24V
COM
PROFIBUS Connector
D
F
44559
4 FLEX I/O PROFIBUS Communications Adapter
Publication 1794-IN114A-EN-P - July 2008
7. Connections G and F are used to pass +V DC power (G) and -V common
(F) to the next module in the series (if required).
Node Address
Set the node address using the thumbwheel switches on the front of the adapter.
Valid settings range from 00...99. Use the + or - buttons to set the node address.
Set the thumbwheel switches to 00 to allow node addressing by software
configuration tool to set the range from 1 to 125. Address changes take effect only
after cycling power.
GSD Requirements
8. Current functionality of PROFIBUS adapters requires GSD files. These
files are easy to install and are available online at:
www.ab.com/networks/gsd.
Indicators
ATTENTION
When connecting wiring, torque terminal screws D, E, F, and G to 0.8 Nm
(7 lb-in).
ATTENTION
Do not wire more than 2 conductors on any single terminal.
99
44560
Thumbwheel switches
for setting the node
address
Status Indicators
Indication Status
Off No power
Solid green Normal operation
Flashing red/OFF Recoverable fault
- FLEX K/O module defective
- Incorrect module installed
- Node address changed since powerup
Solid red Unrecoverable fault
- Major hardware failure
PROFIBUS Indicators
Indication Status
Off No power or no communication
Solid green Data is being transmitted and received
Flashing red/OFF Recoverable fault
- Invalid Send parameter data
- Invalid Check Configuration data
Solid red Unrecoverable fault
- Unable to communicate
99
44561
STATUS Indicator
(green/red)
PROFIBUS Indicator
(green/red)
Publication 1794-IN114A-EN-P - July 2008 5 PN 20760
Copyright © 2008 Rockwell Automation, Inc. All rights reserved.
Mounting Dimensions
Specifications - Flex I/O PROFIBUS 1794-APBDPV1
Environmental Specifications
Certifications
Specification Description
I/O capacity 8 modules
Input voltage rating 24V DC nom
19.2V...31.2 V DC (includes 5% AC ripple)
Input current 450 mA max, 330 mA at 24V dc
Inrush current 23 A for 2 ms
Communication rate All rates up to 12.0 Mbits/s
Indicators Status- red/green
PROFIBUS- red/green
Flexbus output current 640 mA max
Isolation voltage 50V (continuous), Basic Insulation Type
Profibus to Flex backplane to power
Routine tested at 850V DC for 1 s, Profibus to Backplane to Power
Type tested at 850V AC for 60 s, Profibus to Backplane to Power
Power dissipation 7.68 W max @ 19.2V dc
Thermal dissipation Max 26 BTU/hr @ 19.2V dc
Dimensions
(HxWxD)
87 x 69 x 69mm
3.4 x 2.7 x 2.7 in.
Wire size
Power
0.34... 2.5 mm
2
(22...12 AWG) solid or stranded copper wire rated at 75 °C
(167 °F ) or greater 1.2 mm (3/64 in.) insulation max
Wire category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
1 on power ports
2 on communications ports
North American temp code T4
IEC temp code T4
PROFIBUS CABLE Standard drop cable
PROFIBUS connector plug 9-pin D-shell
(Inches)
Millimeters
(3.4)
87
(3.2)
80
(2.7)
68
(0.83) 21
1794-APBDPV1
(3.4H x 2.7W x 2.7D)
87H x 68W x 69D
(1.4)
35
A
(2.3)
59
B
(2.0)
50
(1.2)
28
C
44561
A = Mounting hole dimensions for optional mounting kit
B = DIN rail
C = Secure DIN rail approximately every 200mm (7.87 in.)
Module 1794-APBDPV1
Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40…85 °C (–40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30 g
Nonoperating 50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2500 MHz
3V/m with 1 kHz sine-wave 80% AM from 2500…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth (CM) on communications ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 10 kHz…80 MHz
Emclosure type rating None (open-style)
Certifications (when product is marked)
(1)
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (Zone
2)