Drawing No. LP1120 Effective 03 2020
connects to a current transformer with an output of 100 mA AC
to ensure that proper heater current is present when the control
output is on, and that little or no current is present when the
output is off. This provides immediate warning of a circuit short
or open, instead of waiting for a high or low temperature
shutdown alarm.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
SPECIFICATIONS
1. POWER: Power is supplied by the DA host device. Modules
may be hot-swapped (replaced while powered up) in non-
hazardous locations only.
1PID Max Power: 3.3 W
2PID Max Power: 2.7 W
2. LEDs
*
:
STS – RGB Status LED shows module condition.
OP1, OP2, OP3, OP4 - Indicate status of outputs 1, 2, 3, and 4
ALM, or ALM1 and ALM2 - Alarm LEDs are lit during an
internal alarm condition
*
Default configuration.
3. MEMORY: Non-volatile memory retains all programmable
parameters.
4. INPUTS:
GENERAL:
Sample Time: 50 msec (20 Hz)
Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >50 dB, 50/60 Hz
Temperature Coefficient: 0.01%/
°
C
Step Response Time: 100 msec typ., 200 msec max
THERMOCOUPLE INPUTS:
Types: T, E, J, K, R, S, B, N, C
Input Impedance: 20 M ohm
Lead Resistance Effect: 0.25 µV/ohm
Cold Junction Compensation: Less than ±1 °C typical (±1.5
°C max) over -40 to 75 °C ambient temperature
Resolution: 0.1
°
TYPE
MEASUREMENT
RANGE
WIRE COLOR
ANSI BS 1843
T
-200 to +400 °C
-328 to +752 °F
(+) Blue
(-) Red
(+) White
(-) Blue
E
-200 to +730 °C
-328 to +1346 °F
(+) Violet
(-) Red
(+) Brown
(-) Blue
J
-200 to +760 °C
-328 to +1400 °F
(+) White
(-) Red
(+) Yellow
(-) Blue
K
-200 to +1350 °C
-328 to +2462 °F
(+) Yellow
(-) Red
(+) Brown
(-) Blue
R
0 to +1768 °C
+32 to +3214 °F
No Standard
(+) White
(-) Blue
S
0 to +1768 °C
+32 to +3214 °F
No Standard
(+) White
(-) Blue
B
+149 to +1820 °C
+300 to +3308 °F
No Standard No Standard
N
-200 to +1300 °C
-328 to +2372 °F
(+) Orange
(-) Red
(+) Orange
(-) Blue
C W5/W6
0 to +2315 °C
+32 to +4199 °F
No Standard No Standard
mV 0 mV to 50 mV N/A N/A
RTD INPUTS:
Type: 2 or 3 wire
Excitation: 150 µA
Lead Resistance: 15 ohms Max
Resolution: 1 or 0.1°
TYPE INPUT TYPE RANGE
385 100 ohm platinum, Alpha = .00385
-200 to +600°C
-328 to +1100°F
392 100 ohm platinum, Alpha = .003919
-200 to +600°C
-328 to +1100°F
672 120 ohm nickel, Alpha = .00672
-80 to +215°C
-112 to +419°F
PROCESS INPUT:
INPUT
RANGE
ACCURACY IMPEDANCE
MAX
CONTINUOUS
OVERLOAD
RESOLUTION
10 V 0.1% span 1 M Ohm 50 V 16 bit
20 mA 0.1% span 10 Ohm 100 mA 16 bit
5. PROBE BREAK RESPONSE: Upscale drive, Input Fault Alarm
bit set high, ALx LED illuminates.
6. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span,
+1 °C). Includes NIST conformity, cold junction effect, A/D
conversion errors, temperature coefficient and linearization
conformity at 23 °C after 20 minute warm up.
7. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute
between the following:
OP1
OP2
OP3
OP4
Linear Output (1PID only)
Signal Input 1 and HCM (2PID only)
Signal Input 2 and HCM (2PID only)
Power Supply Input
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l’installation et
l’utilisation de l’appareil.
WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2
AVERTISSEMENT - DANGER D’EXPLOSION - LE
REMPLACEMENT DE COMPOSANTS PEUT NUIRE À
L’APTITUDE À LA CLASSE I, DIVISION 2
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
WARNING - EXPLOSION HAZARD. NOT HOT
SWAPPABLE. DO NOT REMOVE OR REPLACE WHILE
CIRCUIT IS LIVE UNLESS THE AREA IS FREE OF
IGNITIBLE CONCENTRATIONS.
AVERTISSEMENT - RISQUE D’EXPLOSION. NON
ÉCHANGEABLE À CHAUD. NE PAS RETIRER OU
REMPLACER SOUS TENSION SAUF SI LA ZONE EST
EXEMPTE DE CONCENTRATIONS INFLAMMABLES.