Spectrum Controls 1762sc-IF4OF4 Mode d'emploi

Taper
Mode d'emploi
MicroLogix™ Combo Analog Input/Output Module 24
Publication 0100161-01 Rev. B
For Technical Support
USA 440-646-6900
United Kingdom 01908 635230
Australia 1800-809-929
Brazil (55) 11 3618 8800
Europe (49) 2104 960 630
1705 132nd Ave NE
Bellevue, WA 98005 USA
Tel: 425-746-9481
Fax: 425-641-9473
Web: www.spectrumcontrols.com
MicroLogix is a trademark of Rockwell Automation. Belden is a trademark of Belden, Inc.
Publication 1762sc-IF4OF4 Install Guide – February 2009
© 2009 Spectrum Controls, Inc. Printed in the USA.
Installation Guide
MicroLogix
Combo Analog Input Module
(Catalog Number 1762sc-IF4OF4)
Contents
ForMoreInformation...............................................................................2
Description................................................................................................3
Installation................................................................................................4
RemovePower..........................................................................................5
Mounting...................................................................................................5
PowerRequirements................................................................................7
SystemAssembly......................................................................................8
Wiring........................................................................................................9
I/OMemoryMapping.............................................................................12
HazardousLocationConsiderations........................................................21
Environnementsdangereux....................................................................22
MicroLogix™ Combo Analog Input/Output Module 2
Publication 0100161-01 Rev. B
ForMoreInformation
For Refer to this
Document Allen-Bradley
Pub. No.
An overview of the
MicroLogix 1200 system,
including information on
controllers and expansion
I/O.
MicroLogix™ 1200
System Overview 1762-SO001A-
US-P
Information on installing,
wiring, and operating a
MicroLogix 1200
Programmable Controller
MicroLogix 1200
Programmable
Controllers User Manual
1762-UM001B-
US-P
Installation guide for the
MicroLogix 1200
Programmable Controller.
MicroLogix 1200
Programmable
Controllers Installation
Instructions
1762-IN006C-
MU-P
More information on
proper wiring and
grounding techniques.
Industrial Automation
Wiring and Grounding
Guidelines
1770-4.1
If you would like a manual, you can download a free electronic version from the
internet: www.spectrumcontrols.com
MicroLogix™ Combo Analog Input/Output Module 23
Publication 0100161-01 Rev. B
Intentionally Left Blank
MicroLogix™ Combo Analog Input/Output Module 22
Publication 0100161-01 Rev. B
Environnementsdangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
DANGER D’EXPLOSION
La substitution de composants peut rendre
cet équipement impropre à une utilisation en
environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou
déconnecter l'équipement sans s'être assuré
que l'alimentation est coupée.
Ne pas connecter ou déconnecter des
composants sans s'être assuré que
l'alimentation est coupée.
Ce produit doit être installé dans une armoire.
Pour les applications de Classe I, Division 2,
le connecteur de bus doit être correctement
installé et son couvercle enclenché.
Pour les applications de Classe 1, Division 2,
tous les modules doivent être installés en
contact direct les uns avec les autres, comme
indiqué page6. Si on utilise le montage sur rail
DIN, une butée doit être placée à l'avant de
l'automate et après la dernière unité d'E/S
1762.
MicroLogix™ Combo Analog Input/Output Module 3
Publication 0100161-01 Rev. B
Description
MicroLogix™ Combo Analog Input/Output Module 4
Publication 0100161-01 Rev. B
Installation
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2(1)) and to circuits not exceeding
Over Voltage Category II(2) (IEC 60664-1).(3)
Prevent Electrostatic Discharge
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow
these guidelines when you handle the module:
Touch a grounded object to discharge static
potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the
module.
If available, use a static-safe work station.
When not in use, keep the module in its static-
shield box.
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except
that occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level
transient voltages are controlled and do not exceed the impulse voltage capability of the product’s
insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission
(IEC) designations.
MicroLogix™ Combo Analog Input/Output Module 21
Publication 0100161-01 Rev. B
HazardousLocationConsiderations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-
hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
EXPLOSION HAZARD
Substitution of components may impair
suitability for Class I, Division 2.
Do not replace components or disconnect
equipment or change the current switch
selection switch position unless power has been
switched off.
Do not disconnect equipment unless power has
been removed or the area is known to be non-
hazardous.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus
connector must be fully seated and the bus
connector cover must be snapped in place.
In Class I, Division 2 applications, all modules
must be mounted in direct contact with each
other as shown on page 6. If DIN rail mounting
is used, an end stop must be installed ahead of
the controller and after the last 1762 I/O
module.
All wiring must comply with N.E.C. article 501-
4(b).
MicroLogix™ Combo Analog Input/Output Module 20
Publication 0100161-01 Rev. B
Output Specifications
Specification Description
Accuracy - Voltage
Outputs
System accuracy at 25° C: ± 20 mV maximum
System accuracy at -20-60°C: ± 50 mV maximum
Accuracy - Current
Outputs
System accuracy at 25° C: ± 50 uA maximum
System accuracy at -20-60°C: ± 75 uA maximum
Output Resolution
Voltage Output 370µV per bit average when using RAW format in ±10V range and 0-
10V range
185µV per bit average when using RAW format in 0-5 or 1-5V ranges
Current Output 380nA per bit when using RAW format for all current ranges
Differential Nonlinearity 1 LSB (see resolution for LSB size)
Output Ripple <15mV ripple for voltage or current
Output Impedance Current: >1Megohm, Voltage: <1 ohm (MRD)
Output Load Current: 0 ohm min, 500 ohm max,
Voltage: >=1k ohm at 10V output (10 mA), includes wire resistance.
Maximum Output
Inductive and
Capacitive Load
0.1mH
1µF
Output Settling Time <1ms to 63% of full scale
Output Channel glitch Current mode = < ± 1V for 20ms at maximum load
Voltage mode = < ± 0.4V for 20ms and < ±- 1V for 1.5ms with 1k
ohm load
Output Protection ±24V @25˚ C for 1 minute on any channel, with any range and value
Output Short Ckt
Protection
Yes, continuous. (IEC 1131-2 requirement) with any range and value
MicroLogix™ Combo Analog Input/Output Module 5
Publication 0100161-01 Rev. B
RemovePower
Remove power before removing or installing this module.
When you remove or install a module with power applied, an
electrical arc may occur. An electrical arc can cause personal
injury or property damage by:
sending an erroneous signal to your system’s field
devices, causing unintended machine motion
causing an explosion in a hazardous environment
causing permanent damage to the module’s
circuitry
Electrical arcing causes excessive wear to contacts on both
the module and its mating connector. Worn contacts may
create electrical resistance.
Mounting
The 1762sc-IF4OF4 is to be used with the MicroLogix™ 1100, 1200 or 1400
processor.
Do not remove protective debris strip until after the
module and all other equipment near the module is
mounted and wiring is complete. Once wiring is complete
and the module is free of debris, carefully remove protective
debris strip. Failure to remove strip before operating can
cause overheating.
MicroLogix™ Combo Analog Input/Output Module 6
Publication 0100161-01 Rev. B
Minimum Spacing
Maintain spacing
from enclosure walls,
wireways, adjacent
equipment, etc. Allow
50.8 mm (2 in.) of
space on all sides for
adequate ventilation,
as shown
1762 expansion I/O may be mounted horizontally only.
During panel or DIN rail mounting of all devices, be sure
that all debris (metal chips, wire strands, etc.) is kept from
falling into the module. Debris that falls into the module
could cause damage when power is applied to the module.
DINRailMounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50
022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the
DIN rail mounting area of the module against the DIN rail. The latch will
momentarily open and lock into place.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-
EAH35) for environments with vibration or shock concerns.
MicroLogix™ Combo Analog Input/Output Module 19
Publication 0100161-01 Rev. B
Specification Description
Current Inputs System accuracy at 25° C (4 and 17 Hz filters):
± 20 uA maximum for 0-20 mA inputs
± 20 uA maximum for 4-20 mA inputs
System accuracy at -20-60°C (4 and 17 Hz filters):
± 50 uA maximum for 0-20 mA inputs
± 50 uA maximum for 4-20 mA inputs
Input Repeatability (at
25C)
4Hz Filter 17Hz
Filter
62 and 470Hz Filters typical values2
Thermocouples)
Type J ± 0.3 °C ±0.3 °C Not Recommended
Type K ± 0.4 °C ±0.4 °C Not Recommended
Type N ± 0.3 °C ±0.3 °C Not Recommended
Type E ± 0.3 °C ±0.3 °C Not Recommended
Voltage Inputs ± 1 mV ± 2 mV ± 4 mV
Current Inputs ± 2 µA ± 2 µA ± 6 µA
Input Effective
Resolution (25°C)3
±10V 0.48 mV
0-20mA 1 µA
Input CMRR For 4 Hz and 17 Hz Filters: 75 dB from DC up to 10kHz with the
culprit amplitude up to the input voltage range.
Input NMRR 4 Hz Filter 74dB minimum at 50 and 60 Hz
17 Hz Filter 65dB minimum at 50 and 60 Hz
62 Hz Filter First notch at 31Hz, typically 30dB
470 Hz Filter First notch at 237 Hz, typically
35dB
Input Bias/Leakage
Current
±15µA steady state (±500uA peak max, <200µS duration) over
specified voltage span for input range. Applicable for voltage and TC
input configurations only.
Input Impedance -
Current
249.9 (±1%) ohms for current inputs
Input CrossTalk 70dB rejection from 0 to 10 kHz for 4 and 17 Hz filters.
Input Cable Impedance 25 ohms maximum for specified accuracy in voltage, TC modes.
Input voltage range and
protection in voltage
mode
The input voltage on any input pin must be within ±13VDC of the
output return lines for normal operation. The input lines can
withstand up to ±28VDC continuous without damage, but the
leakage bias/leakage current will increase, and input value is
undefined.
Input Protection in
current mode
Max Current input is limited due to input impedance is 42 mA max,
approximately 10.5 VDC.

2These filters do not reject 50/ 60 Hz. Repeatability for these filters is strongly dependent
on how much 50/60Hz noise is in the system.
3 Effective resolution is based on using a 4Hz filter, the proportional counts data format,
and represents the noise free data with a steady input over time, or a statistical equivalent
of the same.
MicroLogix™ Combo Analog Input/Output Module 18
Publication 0100161-01 Rev. B
Specification Description
Hazardous Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T4a
Radiated and
Conducted Emissions
IEC61000-6-4 FCC Part 15B Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity
(IEC61000-4-2)
4 kV contact, 8 kV air
Radiated Immunity
(IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, 900 MHz
& 1890 MHz 100% amplitude modulation
Fast Transient Burst
(IEC61000-4-4)
4 kV
Surge Immunity
(IEC61000-4-5)
2 kV Line - Line, 4 kV Line - Gnd
Conducted Immunity
(IEC61000-4-6)
10V, 0.15 to 80 MHz
Input Specifications
Specification Description
Calibrated Accuracy For all specified input accuracy ranges, the accuracy for the fastest
two filters will be the specified accuracy plus the repeatability for the
particular filter chosen.
Thermocouple Inputs
Linearization per ITS-90
System accuracy at 25°C (4 and 17 Hz filters):
Type J (-180°C to 1200°C): ±1.0 degrees C maximum
Type K (-200°C to 1370°C): ±2.0 degrees C maximum
Type E (-200°C to 1000°C): ±1.0 degrees C maximum
Type T (-190°C to 400°C): ±2.0 degrees C maximum
System accuracy at -20-60 C (4 and 17 Hz filters):
Type J (-180°C to 1200°C): ±5.0 degrees C maximum
Type K (-200°C to 1370°C): ±6.0 degrees C maximum
Type E (-200°C to 1000°C): ±4.5 degrees C maximum
Type T (-190°C to 400°C): ±4.0 degrees C maximum
The above limits do not include the cold junction compensation or
thermocouple sensor errors.
CJC Profile accuracy ± 4.0 degrees C maximum Temperature correlation to target terminal
CJC accuracy (sensor
and measurement)
± 1.0 degrees C maximum Reading/Conversion of the sensor -20 to
80C input values
CJC Resolution ± 0.5 degrees C maximum for -20-80C input values
Voltage Inputs
System accuracy at 25° C (4 and 17 Hz filters):
± 3 mV maximum for 0-5V inputs
± 3 mV maximum for 1-5V inputs
± 10 mV maximum for 0-10V inputs
± 10 mV maximum for ±10V inputs
System accuracy at -20-60° C (4 and 17 Hz filters):
± 6 mV maximum for 0-5V inputs
± 6 mV maximum for 1-5V inputs
± 20 mV maximum for 0-10V inputs
± 20 mV maximum for ±10V inputs
MicroLogix™ Combo Analog Input/Output Module 7
Publication 0100161-01 Rev. B
For environments with extreme vibration and shock
concerns, use the panel mounting method described
below, instead of DIN rail mounting.
PanelMounting
Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6
panhead screws may also be used, but a washer may be needed to ensure a good
mechanical contact. Mounting screws are required on every module.
PowerRequirements
The maximum number of IF4OF4 modules that can be installed in a system
depends on the maximum bus current draw of the module and the maximum bus
current provided by the PLC. The IF4OF4 module has the following power
requirements.
5 VDC 24 VDC
30 mA 3.0 W Max (125mA max at 24V)
Use the table below to determine the maximum number of IF4OF4 modules that
can be installed in a MicroLogix system.
MicroLogix™ Combo Analog Input/Output Module 8
Publication 0100161-01 Rev. B
Controller
Max 5V
Bus Current
(mA)
Max 24V
Bus Current
(mA)
Max # of IF4OF4
Modules
ML1100 800 700 4
ML1200 (24pt.) 400 350 3
ML1200 (40pt.) 600 500 4
ML1400 1500 1500 7
SystemAssembly
The expansion I/O module is attached to the controller or another I/O module by
means of a ribbon cable after mounting as shown below.
Use the pull loop on the connector to disconnect
modules.
Do not pull on the ribbon cable.
EXPLOSION HAZARD
• In Class I, Division 2 applications, the bus connector must
be fully seated and the bus connector cover must be snapped
in place.
• In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page
6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
MicroLogix™ Combo Analog Input/Output Module 17
Publication 0100161-01 Rev. B
Specifications
General Specifications
Specification Description
Isolation Withstand
Channel to Rack 707 VDC for 1 minute (withstand voltage) Optical & magnetic
Input Channel to
Channel
No isolation between channels other than specified in Input
voltage range and protection.
Output channel to
channel
Return lines are connected together. No isolation between
channels.
Output Channel to Input
Channel Crosstalk
The input channel(s) must maintain repeatability specification
while the output channel(s) step change from minimum to
maximum full scale, or from maximum to minimum.
Power Requirements
Internal rack +5V 30 mA maximum
Internal rack +24V 3.0W Max (125mA max at 24V)
Heat Dissipation 3.0W total Max
Maximum number of
modules on the bus
Distance rating of 6. Maximum number of modules by controller
type:
Controller
Max 5V
Bus Current
Max 24V
Bus Current
Max # of
Modules
ML1100 800 700 4
ML1200 (24pt.) 400 350 3
ML1200 (40pt.) 600 500 4
ML1400 1500 1500 7
Fusing None
Wire Size Up to two wires of size #14-#22 AWG (solid) or #16- #22 AWG
(stranded)
Wire Type To ensure proper operation and high immunity to electrical noise,
always use Belden 8761 (shielded, twisted pair) or equivalent wire
for voltage and current sensors or shielded, twisted pair
thermocouple extension lead wire specified by the thermocouple
manufacturer for the thermocouple type you are using. Using the
incorrect thermocouple extension wire type or not following the
correct polarity convention will cause invalid readings.
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)height including
mounting tabs is 110 mm. 3.54 in. (height) x 3.43 in (depth) x 1.58
in (width)height including mounting tabs is 4.33 in.
Storage Temperature -40˚C to +85˚C (-40˚F to 185˚F)
Operating Temperature -20˚C to 60˚C (-4˚F to +140˚F)
Operating Humidity 5% to 95% non-condensing
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. max peak-to-peak
Shock Operating: 30G
Weight, unpackaged 0.187 kg (0.412 lb)
Weight, packaged 0.281 kg (0.619 lb)
Module Identification
Vendor I.D. 58
Product Type 10
Product Code 22
Certifications
Agency Certification C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
MicroLogix™ Combo Analog Input/Output Module 16
Publication 0100161-01 Rev. B
This table describes the channel specific configuration registers that are individually
selectable for channels 6 and 7.
To Select
Make these bit settings
7 6543210
Filter Frequency
(Ignored if Display CJC)
17 Hz 00
4 Hz 01
62 Hz 10
470 Hz 11
Data Format
Engineering Units X1 00
Engineering Units X10 01
Raw/Proportional Data 10
Scaled for PID 11
Input Type
4 to 20 mA 0 0 0 0
0 to 20 mA 0 0 0 1
-10 to 10 V 0 0 1 0
0 to 10 V 0 0 1 1
1 to 5 V 0 1 0 0
0 to 5 V 0 1 0 1
Type J TC 0 1 1 0
Type K TC 0 1 1 1
Type E TC 1 0 0 0
Type T TC 1 0 0 1
Display CJC channel temp 1 0 1 0
Reserved 1 0 1 1
Reserved 1 1 0 0
Reserved 1 1 0 1
Reserved 1 1 1 0
Channel Disabled 1 1 1 1
MicroLogix™ Combo Analog Input/Output Module 9
Publication 0100161-01 Rev. B
Wiring
GroundingtheModule
Grounding for this product is provided by the MicroLogix™ 1100, 1200 or 1400
CPU via the bus ribbon cable. Refer to Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
Consider the following when wiring your system:
The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.
Output channel returns are common
Input channel to channel isolation is limited to ±13 VDC from the output
return voltage.
Use Belden™ 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground) as close to the module as
possible. Keep the shield connection to earth ground as short as possible.
To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the
I/O system as close to your voltage type sensors or actuators as possible.
The 1762sc-IF4OF4 module does not provide loop power for analog
inputs. Use a power supply that matches the input transmitter
specifications.
Digital and analog power must be supplied by an Isolated Secondary
Limited Energy Low Voltage source.
Use supply wires for 20˚ C above surrounding ambient.
MicroLogix™ Combo Analog Input/Output Module 10
Publication 0100161-01 Rev. B
Terminal Block Layout
Grounding the cable shield at the module end only usually
provides sufficient noise immunity. However, for best cable
shield performance, earth ground the shield at both ends, using a
0.01µF capacitor at one end to block AC power ground currents,
if necessary.
Labeling the Terminals
A write-on label is provided with the module. Remove the label from the door,
mark the identification of each terminal with permanent ink, and slide the label
back into the door.
TC/Voltage
Input Path
MicroLogix™ Combo Analog Input/Output Module 15
Publication 0100161-01 Rev. B
To Select
Make these bit settings
76543210
Input Type
4 to 20 mA 00
0 to 20 mA 0 1
Reserved 1 0
Channel Disabled 1 1
Open Circuit
(For Module)1
Upscale 0
Zero 1
Temperature
Scale
(For Module)1
Deg C 0
Deg F 1

1Thisisamodulewidesettingwhichisonlyrecognizedwithinthe
configurationforChannel4.ThecorrespondingbitinChannel5isignored.
MicroLogix™ Combo Analog Input/Output Module 14
Publication 0100161-01 Rev. B
This table describes the channel specific configuration registers that are individually
selectable for output channels 0 through 3.
To Select
Make these bit settings
7 6 543210
Output Type
4 to 20 mA 000
0 to 20 mA 001
-10 to 10 V 010
0 to 10 V 011
1 to 5 V 100
0 to 5 V 101
Reserved 110
Channel Disabled 111
Data Format
Scaled for PID 00
Engineering Units 01
Percent Range 10
Raw/Proportional Data 11
Unused 0 0 0
This section details the channel specific configuration registers that are individually
selectable for channels 4 and 5
To Select
Make these bit settings
7 6 543210
Filter
Frequency
(Ignored if
Display CJC)
17 Hz 00
4 Hz 0 1
62 Hz 1 0
470 Hz 1 1
Data Format
Engineering Units X1 00
Engineering Units X10 0 1
Raw/Proportional
Data 10
Scaled for PID 1 1
MicroLogix™ Combo Analog Input/Output Module 11
Publication 0100161-01 Rev. B
Wiring the Finger-Safe Terminal Block
Be careful when stripping wires. Wire fragments that fall into
a module could cause damage when power is applied. Once
wiring is complete, ensure the module is free of all metal
fragments.
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped
end of the wire or a spade lug. The terminals will accept a 6.35 mm (0.25
in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is 0.904 Nm
(8 in-lbs).
3. After wiring is complete, remove the debris shield.
If you need to remove the finger-safe cover, insert a screw
driver into one of the square wiring holes and gently pry the
cover off. If you wire the terminal block with the finger-safe
cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way
MicroLogix™ Combo Analog Input/Output Module 12
Publication 0100161-01 Rev. B
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Type Wire Size Terminal Screw
Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.904 Nm (8 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.904 Nm (8 in-lbs)
I/OMemoryMapping
Addressing
The addressing scheme for 1762 Expansion I/O is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins
with slot 1.
MicroLogix™ Combo Analog Input/Output Module 13
Publication 0100161-01 Rev. B
Input Data File
For each module, slot x, words 0 through 3 contain module status information.
Words 4 through 7 contain analog input data for channels 4 through 7 respectively.
The table below shows the layout for the input data file.
Input Data File
Register Function
Input File (Module Data)
I:e.0 General Status Word 0
I:e.1 Output Status Word 1
I:e.2 Input Status Word 2
I:e.3 Raw CJC Temperature
I:e.4 Channel 4 Data Word
I:e.5 Channel 5 Data Word
I:e.6 Channel 6 Data Word
I:e.7 Channel 7 Data Word
Configuration Data File
The configuration data file is not used. Instead the output data file is used to
configure the module.
Output Data File
The output data file is used to configure the 1762sc-IF4OF4 module. Take care
when making changes to the configuration (i.e. output data file) while in run mode.
Illegal configurations could fault the controller.
The table below shows the layout for the output data file. Note that words 4
through 7 are used to define the module configuration.
Output Data File
Register Function
Output File (Used for Module Configuration)
O:e.0 Channel 0 Data Word
O:e.1 Channel 1 Data Word
O:e.2 Channel 2 Data Word
O:e.3 Channel 3 Data Word
O:e.4 Low byte: Channel 0 Configuration Register (Output)
High byte: Channel 1 Configuration Register (Output)
O:e.5 Low byte: Channel 2 Configuration Register (Output)
High byte: Channel 3 Configuration Register (Output)
O:e.6 Low byte: Channel 4 Configuration Register (Input)
High byte: Channel 5 Configuration Register (Input)
O:e.7 Low byte: Channel 6 Configuration Register (Input)
High byte: Channel 7 Configuration Register (Input)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Spectrum Controls 1762sc-IF4OF4 Mode d'emploi

Taper
Mode d'emploi

dans d''autres langues