Allen-Bradley ControlLogix Installation Instructions Manual

Catégorie
Blocs d'alimentation
Taper
Installation Instructions Manual
Installation Instructions
Original Instructions
ControlLogix Redundant Power Supply
Catalog Numbers
1756-PA75R, 1756-PB75R, 1756-PSCA2, 1756-PBXTR, 1756-PSCA2XT, 1756-PAXTR, 1756-PA75RK, 1756-PB75RK, 1756-PSCA2K
The redundant power supply system provides additional uptime protection for chassis that are used in critical applications. The two remotely
mounted supplies are designed to share the current required by the chassis. Two supplies are available in AC (catalog number 1756-PA75R/A or
1756-PAXTR) and DC (catalog number 1756-PB75R/A or 1756-PBXTR) versions that can be mixed or matched when used in tandem.
If one power supply fails, the remaining supply accommodates the entire load of the chassis without disruption to chassis activity.
The ControlLogix® redundant power supply system is designed to account for operational anomalies in only the power supply
(the chassis adapter and power supply cables are excluded).
The 1756-PSCA2 chassis adapter is a passive device. The chassis adapter funnels power from one or two ControlLogix redundant power supplies to
the single power connector on the ControlLogix chassis backplane.
Redundant Power Supply and Chassis Compatibility
Your chassis series determines the redundant power supply that you can use. This table lists the chassis that can be installed with each redundant
power supply.
Topic Page
Summary of Changes 5
Components of the Redundant System 5
Tools Required 6
Parts Required 6
Install the Chassis Adapter 6
Install the Redundant Power Supplies 6
Connect the Power 7
Remove the Protective Label 9
Troubleshoot the Redundant Power Supplies 10
Remove or Replace a Redundant Power Supply 11
Remove or Replace a Chassis Adapter 11
Specifications 12
Additional Resources 13
Power Supply Cat. No. Chassis Cat. No.
1756-PA75R 1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B
1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C
1756-PB75R
1756-PAXTR
(1)
(1) The 1756-PAXTR and 1756-PBXTR redundant power supplies are only rated from 0…60 °C (32…140 °F) when used in non-XT chassis.
1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B, 1756-A4LXT/B, 1756-A5XT/B, 1756-A7LXT/B, 1756-A7XT/B
1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C, 1756-A7XT/C
1756-PBXTR
(1)
2 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or
maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code
of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
⌘᜿˖൘ᆹ㻵ǃ䝽㖞ǃ᫽֌઼㔤ᣔᵜӗ૱ࡽˈ䈧䰵䈫ᵜ᮷ẓԕ৺ Ā ަԆ䍴Ⓚ ā 䜘࠶ࡇࠪⲴᴹޣ䇮༷ᆹ㻵ǃ䝽㖞઼᫽֌Ⲵ⴨ᓄ᮷ẓDŽ䲔Ҷᡰᴹ䘲⭘㿴㤳ǃ⌅
ᖻ઼ḷ߶Ⲵ⴨ޣ㾱≲ѻཆˈ⭘ᡧ䘈ᗵ享⟏ᚹᆹ㻵઼᧕㓯䈤᰾DŽ
ᆹ㻵ǃ䈳ᮤǃᣅ䘀ǃ֯⭘ǃ㓴㻵ǃ᣶ন઼㔤ᣔㅹ਴亩᫽֌ᗵ享⭡㓿䗷䘲ᖃ䇝㓳ⲴуъӪઈ᤹➗䘲⭘Ⲵ᫽֌㿴㤳ᇎᯭDŽ
ྲ᷌ᵚ᤹➗ࡦ䙐୶ᤷᇊⲴᯩᔿ֯⭘䈕䇮༷ˈࡉਟ㜭Պᦏᇣ䇮༷ᨀ׋Ⲵ؍ᣔDŽ
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la
instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de
práctica aplicable.
Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os
usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o
código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе
«Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по
установке и прокладке соединений, а также с требованиями всех применимых норм, законов и стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с
применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
ὀព ᮏ〇ရࢆタ⨨ࠊᵓᡂࠊ✌ືࡲࡓࡣಖᏲࡍࡿ๓࡟ࠊᮏ᭩࠾ࡼࡧᮏᶵჾࡢタ⨨ࠊタᐃࠊ᧯స࡟ࡘ࠸࡚ࡢཧ⪃㈨ᩱࡢヱᙜ⟠ᡤ࡟グ㍕ࡉࢀ࡚࠸ࡿᩥ᭩࡟┠
ࢆ㏻ࡋ࡚ࡃࡔࡉ࠸ࠋ࣮ࣘࢨࡣࠊࡍ࡭࡚ࡢヱᙜࡍࡿ᮲౛ࠊἲᚊࠊつ᱁ࡢせ௳࡟ຍ࠼࡚ࠊタ⨨࠾ࡼࡧ㓄⥺ࡢᡭ㡰࡟⩦⇍ࡋ࡚࠸ࡿᚲせࡀ࠶ࡾࡲࡍࠋ
タ⨨ㄪᩚࠊ㐠㌿ࡢ㛤ጞࠊ౑⏝ࠊ⤌❧࡚ࠊゎయࠊಖᏲࢆྵࡴㅖసᴗࡣࠊヱᙜࡍࡿᐇ᪋つ๎࡟ᚑࡗ࡚カ⦎ࢆཷࡅࡓ㐺ษ࡞సᴗဨࡀᐇ⾜ࡍࡿᚲせࡀ࠶ࡾࡲࡍࠋ
ᮏᶵჾࡀ〇㐀࣓࣮࢝࡟ࡼࡾᣦᐃࡉࢀ࡚࠸࡞࠸᪉ἲ࡛౑⏝ࡉࢀ࡚࠸ࡿሙྜࠊᶵჾ࡟ࡼࡾᥦ౪ࡉࢀ࡚࠸ࡿಖㆤࡀᦆ࡞ࢃࢀࡿᜍࢀࡀ࠶ࡾࡲࡍࠋ
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten,
bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den
Installations- und Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit
den anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer,
configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
㭒㦮 a ⽎G㩲䛞G㍺䂮 SG㍺㩫 SG㧧☯G⡦⓪G㥶㰖G⽊㑮䞮₆G㩚㠦G⽎Gⶎ㍲⯒G䙂䞾䞮㡂G㍺䂮 SG㍺㩫G⹥G㧧☯㠦Gὖ䞲G㺎ἶG㧦⬢G㎏㎮㦮Gⶎ㍲✺㦚G⹮✲㔲G㧓ἶG㑯㰖䞮
㕃㔲㡺 UG㌂㣿㧦⓪G⳾✶Gὖ⩾G′㩫 SG⻫′G⹥G䚲㭖㠦㍲G㣪ῂ䞮⓪G㌂䟃㠦G╖䟊G⹮✲㔲G㍺䂮G⹥G⺆㍶G㰖䂾㦚G㑯㰖䟊㟒G䞿┞┺ U
㍺䂮 SG㫆㩫 SGṖ☯ SG㌂㣿 SG㫆Ⱃ SG⿚䟊 SG㥶㰖⽊㑮G❇G⳾✶G㧧㠛㦖Gὖ⩾G′㩫㠦G➆⧒G㩗㩞䞲Gᾦ㥷㦚G⹱㦖G㌂㣿㧦⯒G䐋䟊㍲ⰢG㑮䟟䟊㟒G䞿┞┺ U
⽎G㧻゚⯒G㩲㫆㌂ṖGⳛ㔲䞮㰖G㞠㦖G⹿⻫㦒⪲G㌂㣿䞮ⳊG㧻゚㦮G⽊䢎G₆⓻㧊G㏦㌗♶G㑮G㧞㔋┞┺ U
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”,
riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi,
codici e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun
şekilde yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
⌘᜿һ丵˖൘ᆹ㼍ǃ䁝ᇊǃ᫽֌ᡆ㏝䆧ᵜ⭒૱ࡽˈ䃻ݸ䯡䆰↔᮷Ԧԕ৺ࡇᯬ NjަԆ䋷Ⓚnjㄐㇰѝᴹ䰌ᆹ㼍ǃ䁝ᇊ㠷᫽֌↔䁝ۉⲴ᮷ԦDŽ֯⭘㘵ᗵ丸⟏ᚹᆹ㼍
઼䝽㐊ᤷ⽪ˈіㅖਸᡰᴹ⌅㾿ǃ⌅ᖻ઼⁉Ⓠ㾱≲DŽ
वᤜᆹ㼍ǃ䃯ᮤǃӔԈ֯⭘ǃ֯⭘ǃ㍴㼍ǃ᣶ন઼㏝䆧ㅹअ֌䜭ᗵ丸Ӕ⭡ᐢ㏃䙾䚙⮦䁃㐤ⲴӪ଑䙢㹼ˈԕㅖਸ䚙⭘Ⲵሖ֌⌅㾿DŽ
ྲ᷌ሷ䁝ۉ⭘ᯬ䶎㼭䙐୶ᤷᇊⲴ⭘䙄ᱲˈਟ㜭ᴳ䙐ᡀ䁝ۉᡰᨀ׋Ⲵ؍䆧࣏㜭ਇᨽDŽ
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace
a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające
instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi
kodeksami, prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller
utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in
overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 3
ControlLogix Redundant Power Supply
Before You Begin
ATTENTION: Before installing, configuring, operating, or maintaining this product, read this document and the documents listed in the additional resources
section for installing, configuring, or operating equipment. Users should familiarize themselves with installation and wiring instructions in addition to
requirements of all applicable codes, laws, and standards.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with
applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for
repair. Do not dismantle the module.
This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) [PA75R, PB75R, PSCA2] -25…+70 °C
(-13…+158 °F) [PAXTR, PBXTR, PSCA2XT]. The equipment must not be used outside of this range.
Annunciator cable length should be less than 10 m (32.8 ft).
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must
have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the
application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1, for additional installation requirements.
NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous
locations.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous location temperature code. When
combining products within a system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the local Authority Having Jurisdiction
at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de
l'installation.
WARNING: Explosion Hazard
Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has
been removed or the area is known to be nonhazardous. Secure any
external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with this
product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area
known to be nonhazardous.
AVERTISSEMENT: Risque d’Explosion
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs
externes reliés à cet équipement à l'aide de vis, loquets coulissants,
connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une
utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer
les piles.
4 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
European Hazardous Location Approval
The following applies to products marked , , II 3, such modules:
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to
Directive 94/9/EC. See the EC Declaration of Conformity at rok.auto/certifications for details. The type of protection for the 1756-PB75R, 1756-PBXTR, 1756-PSCA2, and 1756-PSCA2XT is “Ex nA IIC T4
Gc” according to EN 60079-15.
May have Catalog numbers followed by a “K” to indicate a conformal coating option.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations
correspond to Zone 2 classification according to ATEX directive 1999/92/EC.
As the 1756-PB75R, 1756-PBXTR, 1756-PSCA2, and 1756-PSCA2XT comply to Standards: EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO13ATEX1325026X.
WARNING: Special Conditions for Safe Use
This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in EN/IEC
60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure
must be accessible only by the use of a tool.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
The instructions in the user manual shall be observed.
IEC Hazardous Location Approval
The following applies to products with IECEx Certification.
Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods.
Such locations correspond to Zone 2 classification to IEC 60079-0.
The type of protection for the 1756-PB75R, 1756-PBXTR, 1756-PSCA2, and 1756-PSCA2XT is “Ex nA IIC T4 Gc” according to IEC 60079-15.
Such modules as the 1756-PB75R, 1756-PBXTR, 1756-PSCA2, and 1756-PSCA2XT comply to Standards IEC 60079-0:2011, IEC 60079-15:2010, reference IECEx certificate number IECExUL14.0008X.
Such modules may have catalog numbers followed by a “K” to indicate a conformal coating option.
ATEX and IECEx Hazardous Location Conformity
Model Protection Type ATEX Certificate IECEx Certificate
1756-PSCA2 Ex nA IIC T4 Gc DEMKO13ATEX1325026X IECEx UL 14.0008X
1756-PSCA2XT Ex nA IIC T4 Gc DEMKO13ATEX1325026X IECEx UL 14.0008X
1756-PAXTR None
1756-PBXTR Ex nA IIC T4 Gc DEMKO13ATEX1325026X IECEx UL 14.0008X
1756-PA75R None
1756-PB75R Ex nA IIC T4 Gc DEMKO13ATEX1325026X IECEx UL 14.0008X
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wrist strap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 5
ControlLogix Redundant Power Supply
Summary of Changes
We updated the torque requirement on pages 7 and 12 for these power supplies.
Components of the Redundant System
The following graphic (series C chassis depicted) shows the components of a redundant system in a typical configuration.
Removable Terminal Blocks (RTBs) for I/O Connections
WARNING: EXPLOSION HAZARD
When you connect or disconnect the removable terminal block (RTB) with field side power applied, an electric arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
IMPORTANT The ControlLogix redundant power supply system is designed to account for operational anomalies in only the power supply. The chassis adapter and power
supply cables are excluded.
Item Description Cat. No.
1 Redundant power supply 1756-PA75R/A and/or 1756-PB75R/A or 1756-PAXTR and/or 1756-PBXTR
2 Redundant power supply cable (Length = 0.91 m [3 ft]) 1756-CPR2
(2)(3)
or 1756-CPR2D
(3)(4)
or 1756-CPR2U
(3)(4)
(2) Cable bend radius is 12.7 cm (5.0 in.).
(3) Cable bend radius can be greater than or less than the minimum mounting clearance of the chassis. Always maintain chassis minimum mounting clearance.
(4) Requires 10.16 cm (4.0 in.) of clearance next to the chassis adapter.
3 Redundant power supply chassis adapter 1756-PSCA2 or 1756-PSCA2XT
4 Annunciator wiring
(1)
(Maximum length = 10 m [32.8 ft])
(1) Optional user-provided annunciator wiring can be connected to the solid-state relay for status and for troubleshooting. See page 8 for more information.
User-supplied
2
3
1
4
6 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
Tools Required
When installing your chassis and power supplies, the following items are required:
Parts Required
Each redundant power supply requires four #10 Phillips screws for installation. Eight #10 Phillips screws are required to install two redundant
power supplies.
Install the Chassis
Install the Chassis Adapter
1. Align the circuit board of the 1756-PSCA2 or 1756-PSCA2XT chassis adapter with the card guides on the left side of the chassis.
2. Slide the adapter back until it is flush with the front of the chassis.
Install the Redundant Power Supplies
Follow these steps to install your redundant power supplies.
1. Drill holes in the back panel of the enclosure for the redundant power supply.
2. Insert the #10 Phillips screws into the top mounting holes, but do not tighten completely.
3. Slide the redundant power supply over the installed screws and tighten the screws.
4. Insert the bottom screws and tighten them.
5. Repeat these steps for additional power supplies.
3.18 mm (0.125 in.) slotted screwdriver Crimper
6.35 mm (0.25 in.) slotted or #2 Phillips screwdriver Wire stripper
Torque screwdriver Drill
Needle-nose pliers
IMPORTANT Install the chassis in the enclosure and make sure that you follow the minimum spacing requirements. See the ControlLogix Chassis Installation Instructions,
publication
1756-IN621 for more information.
WARNING: EXPLOSION HAZARD
If you connect or disconnect the 1756-CPR2 cables while either backplane power source is on, an
electric arc can occur. This could cause an explosion in hazardous location installations. Repeated
electric arcing causes excessive wear to contacts on both the module and its mating connector.
Worn contacts may create electrical resistance that can affect module operation.
Be sure that power is removed or the area is nonhazardous before proceeding.
IMPORTANT Install the redundant power supplies in the enclosure and make sure that you follow the minimum spacing requirements. See the ControlLogix Chassis
Installation Instructions, publication
1756-IN621, for more information.
ATTENTION: Do not drill holes for a redundant power supply above installed equipment. Metal chips from drilling can damage the backplane and cause
intermittent operation.
Card Guide
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 7
ControlLogix Redundant Power Supply
Connect the Power
Use the 1756-CPR2, 1756-CPR2D, or 1756-CPR2U cable to connect your redundant power supply to the 1756-PSCA2 or 1756-PSCA2XT
chassis adapter.
1. Connect the male end of the power cable to the chassis adapter (series C depicted).
2. Connect the female end of the power cable to the redundant power supply.
3. Tighten the screws to hold the cable in place.
Make sure that you tighten the screws securely to hold the cable in place for the
life of the product.
4. Repeat these steps with the second redundant power supply.
Use 2.5 mm (14 AWG) solid or stranded-copper wire that is rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation maximum to connect
power. Tighten the terminals to a torque of 0.565 N•m (5 lb•in).
WARNING: EXPLOSION HAZARD
If you connect or disconnect the 1756-CPR2 cables while either backplane power source is on, an electric arc can occur. This could cause an explosion in hazardous
location installations. Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create
electrical resistance that can affect module operation.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: EXPLOSION HAZARD
If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION: Do not wire more than one conductor on any single terminal.
Use a 15 A time-delay type fuse in all ungrounded power connections.
1756-CPR2
1756-CPR2U
1756-CPR2D
8 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
Connect the power as shown in the following figure.
Connect the Solid-state Relay
A solid-state relay on your redundant power supplies can be connected to any compatible monitoring or signaling device. This connection indicates
if the supplies are functioning properly.
The relays are closed during standard operation. The solid-state relay contacts open if one of these events occurs:
One or more of the supplies fail.
In this case, the contact opens on the failed supply (or supplies), and the input module alerts you to the failure through the controller
program.
The connected redundant power supplies are turned OFF.
When you use the solid-state relay annunciator function, connect a compatible source voltage to a contact terminal. Then connect the other
terminal to the monitoring or signaling device.
IMPORTANT The voltage input connections of the power supplies are auto-sensing.
You do not use a jumper, for example, a 120/240V AC jumper, when connecting external power to the power supply, as shown in the previous figure.
Item Description, 1756-PA75R/A (AC) Description, 1756-PB75R/A (DC)
1 L1 (high side of line power) Not used
2 Not used DC+ (positive supply)
3 L2 (low side of line power) Not used
4 Not used DC- (negative supply return)
5 Protective Earth. Attach to chassis ground lug or ground bus. See the ControlLogix Chassis Installation Instructions,
publication 1756-IN621, for details.
ATTENTION: Annunciator cable length must be less than 10 m (32.8 ft).
The annunciator output is rated only for resistive loads. Do not use it to drive the coil of an electromagnetic relay.
1756-PA75R/A (AC)
1756-PB75R/A (DC)
1
3
2
5
4
1
3
2
5
4
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 9
ControlLogix Redundant Power Supply
Connect the solid-state relay as shown in the following figure.
Solid-state Relay Connection
Remove the Protective Label
Remove the protective label from the top of the power supply.
Item Description
1 Source voltage
2 Annunciator cable to input module
3 0.25…2.5 mm (22…14 AWG) solid or stranded-copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
4 0.25…2.5 mm (22…14 AWG) solid or stranded-copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
5 Plastic barrier
ATTENTION: Make sure the power supply is mounted and all panel fabrication is complete before you remove the protective label. This label protects the power
supply from metal shavings falling inside the power supply and damaging it during operation.
Routing of annunciator cable when annunciator voltage
and input voltage are different.
Routing of annunciator cable when annunciator voltage
and input voltage are the same.
The annunciator wiring must be tucked under the tab at the top of the plastic
barrier and routed separately from the power wires.
1
3
2
5
4
1
4
2
3
Configuration 1
Configuration 2
10 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
Troubleshoot the Redundant Power Supplies
The redundant power supplies have a green status indicator for power and an amber status indicator for non-redundancy.
The
Status Indicators table describes how to use the status indicators to troubleshoot your redundant power supplies.
Chassis Adapter Status Indicator
The chassis adapter has a green power status indicator. When the status indicator is solid green, the chassis is receiving power from the redundant
power supplies. If the indicator is off, the chassis is not receiving power from the redundant power supplies. See the
Status Indicators table to
troubleshoot the redundant power supplies.
Status Indicators
Power Indicator Non-red Indicator Description Take This Action
Solid green Off The power supplies are operating properly. None
Solid green Solid amber This power supply is operating properly, but is the only power
supply providing power to the chassis adapter.
Check the other power supply.
Off Solid amber All possible connections are made, but the power supply is turned
off.
Turn the power supply ON. If the power supply does not turn ON, follow these
steps.
1. Remove the input power from the power supply.
2. Wait 30 seconds.
3. Reconnect the input power.
4. Turn the power supply ON.
If the power supply still does not turn ON, it can require replacement.
Off Off Any of the following conditions can apply: Take the corresponding action:
The supply is turned OFF. Turn the power supply ON.
Line voltage is not within the specified range.
Verify that line power is in the specified range. If the indicators remain OFF,
cycle power.
All connections are made, but input power is not supplied. Verify that input power is supplied and turn the power supply ON.
All connections are made, including input power, but the
output cable (1756-CPR2) is not connected.
Connect the output cable and turn the power supply ON.
The power supply is ON but defective. The power supply can require replacement.
Power
Non-red
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 11
ControlLogix Redundant Power Supply
Remove or Replace a Redundant Power Supply
Remove a Redundant Power Supply
Follow these steps to remove the redundant power supply.
1. Turn the redundant power supply OFF.
2. Disconnect the line power source voltage from the redundant power supply and annunciator.
3. Remove the wiring terminal blocks.
4. Unscrew and disconnect the 1756-CPR2, 1756-CPR2D, or 1756-CPR2U cable at the power supply.
5. Remove the bottom mounting screws.
6. Loosen the top mounting screws and slide the supply up and off the mounting screws.
Replace a Redundant Power Supply
Follow these steps to replace a redundant power supply.
1. Slide the redundant power supply over the top mounting screws and tighten them.
2. Install the bottom mounting screws.
3. Reconnect the 1756-CPR2, 1756-CPR2D, or 1756-CPR2U cable at the power supply.
4. Install the wiring terminal blocks.
5. Connect the line power source voltage to the redundant power supply and annunciator.
6. Turn the redundant power supply ON.
When you turn ON the replacement redundant power supply, the connected chassis automatically draws power from the redundant power
supplies.
Remove or Replace a Chassis Adapter
Use this information to remove or replace a chassis adapter.
Remove a Chassis Adapter
Follow these steps to remove a chassis adapter.
1. Turn the redundant power supplies OFF.
2. Disconnect the power cable at the chassis adapter.
3. Push the top and bottom locking tabs on the chassis adapter to the side and pull the module off the chassis.
Replace a Chassis Adapter
1. Align the circuit board of the adapter with the card guides on the left side of the chassis.
2. Slide the adapter back until it is flush with the front of the chassis.
WARNING: EXPLOSION HAZARD
Remove or replace power supplies only when backplane and power supply power are removed or the area is known to be nonhazardous. Removal or replacement
of a power supply in a hazardous area can cause an electric arc across the contacts if backplane power is still applied.
IMPORTANT You can replace one redundant power supply while the other supply is operating in nonredundant mode without any affect on chassis operation.
If you must only replace a redundant power supply cable, we recommend that you do this replacement when the conditions permit the removal of all
system power.
12 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
Specifications
Attribute
1756-PSCA2/
1756-PSCA2K
1756-PSCA2XT 1756-PAXTR 1756-PBXTR
1756-PA75R/
1756-PA75RK
1756-PB75R/
1756-PB75RK
Voltage and current ratings Input N/A N/A 120/240V AC,
50/60 Hz, 75VA,
65 W
24V DC, 81W 120/240V AC,
50/60 Hz, 120VA,
115 W
24V DC, 110 W
Output (current capacity) 2.8 A, 24V DC;
15.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC
2.8 A, 24V DC;
15.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC
1.75 A, 24V DC;
8.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC;
42 W max,
20 A inrush max
2.1 A, 24V DC;
10.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC;
52 W max,
30 A inrush max
2.8 A, 24V DC;
13.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC;
75 W max,
20 A inrush max
2.8 A, 24V DC;
13.0 A, 5.1V DC;
4.0 A, 3.3V DC;
1.5 A, 1.2V DC;
75 W max,
20 A inrush max
Annunciator N/A N/A 240V AC
50/60 HZ,
240V DC, 50 mA,
resistive only
240V AC
50/60 HZ,
240V DC, 50 mA,
resistive only
90V DC for
ATEX/IECEx
240V AC
50/60 HZ,
240V DC, 50 mA,
resistive only
240V AC
50/60 HZ, 240V DC,
50 mA, resistive
only
90V DC for
ATEX/IECEx
Isolation voltage N/A 250V (continuous), Reinforced Insulation Type, Power Input to Backplane, Power Input to
Annunciator, Annunciator to Backplane
All supply frequencies or frequency ranges, if AC supply is
used
N/A 47…63 Hz N/A 47…63 Hz N/A
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C
(32 °F < Ta <
+140 °F)
-25 °C < Ta < +70 °C (-13°F < Ta < +158 °F) 0°C < Ta < +60 °C
(32 °F < Ta < +140 °F)
Temperature, surrounding air, max 60 °C (140 °F) 70 °C (158 °F) 60 °C (140 °F)
Enclosure type rating None (open-style)
Torque N/A 0.565 N•m (5 lb•in)
Wire size N/A Power: 2.5 mm (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater,
1.2 mm (3/64 in.) insulation max
Annunciator: 0.25…2.5 mm (22…14 AWG) solid or stranded copper wire rated at
90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
Protective earth ground N/A 2.5 mm (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater
Pilot duty rating N/A Annunciator: Not Rated
North American temperature code T5 T4A T3C T4
ATEX temperature code T4 - T4 - T4
IECEx temperature code T4 - T4 - T4
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 13
ControlLogix Redundant Power Supply
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Resource Description
1756 ControlLogix Communication Modules Specifications Technical Data, publication 1756-TD003 Describes Ethernet communication module specifications.
ControlLogix Chassis Installation Instructions, publication 1756-IN621 Provides information on installing ControlLogix chassis.
ControlLogix System User Manual, publication 1756-UM001 Provides instructions for installation and use of ControlLogix Systems, application design, and
other general information for these systems.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website,
http://www.rockwellautomation.com/rockwellautomation/certification/overview.page
Provides declarations of conformity, certificates, and other certification details.
14 Rockwell Automation Publication 1756-IN620D-EN-P - October 2018
ControlLogix Redundant Power Supply
Notes:
Rockwell Automation Publication 1756-IN620D-EN-P - October 2018 15
ControlLogix Redundant Power Supply
Notes:
Allen-Bradley, ControlLogix, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Publication 1756-IN620D-EN-P - October 2018 PN-520118
Supersedes Publication 1756-IN620C-EN-P - February 2017 Copyright © 2018 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at
http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and
Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download
Center (PCDC)
Get help determining how products interact, check
features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Allen-Bradley ControlLogix Installation Instructions Manual

Catégorie
Blocs d'alimentation
Taper
Installation Instructions Manual

dans d''autres langues