Unitronics IO-PT400 I-O Expansion Modules Mode d'emploi

Taper
Mode d'emploi
Unitronics
1
IO-PT400, IO-PT4K User Guide
I/O Expansion Modules 4 RTD Inputs
IO-PT400 and IO-PT4K are I/O Expansion
Modules that can be used in conjunction with
specific Unitronics OPLC controllers.
This module is offered in two models.
Each module offers 4 RTD inputs for
temperature measurement:
Part No.
RTD Type
I/O-PT400
PT100, NI100, NI1201
I/O-PT4K
PT1000, NI1000
The interface between the module and the
OPLC is provided by an adapter.
The module may either be snap-mounted on
a DIN rail, or screw-mounted onto a
mounting plate.
Component identification*
1
Module-to-module connector
2
Status indicators
3
Input connection points, CH2 & CH3
4
Module-to-module connector port
5
Input connection points, CH0 & CH1
*Note that the model shown represents all models.
Before using this product, it is the responsibility of the user to read and understand this document and
any accompanying documentation.
All examples and diagrams shown herein are intended to aid understanding, and do not guarantee
operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product in accordance with local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
User safety and equipment protection guidelines
This document is intended to aid trained and competent personnel in the installation of this equipment as
defined by the European directives for machinery, low voltage, and EMC. Only a technician or engineer trained
in the local and national electrical standards should perform tasks associated with the device’s electrical wiring.
Symbols are used to highlight
information relating to the user’s
personal safety and equipment
protection throughout this document.
When these symbols appear, the
associated information must be read
carefully and understood fully.
Symbol
Meaning
Description
Danger
The identified danger causes physical
and property damage.
Warning
The identified danger can cause
physical and property damage.
Caution
Caution
Use caution.
Failure to comply with appropriate safety guidelines can result in severe personal injury or
property damage. Always exercise proper caution when working with electrical equipment.
1
Note that the temperature range for NI120 is not standard: -50° to 172°C (-58° to 341°F).
UG_IO-PT400-4K I/O Expansion Modules
2
Unitronics
Check the user program before running it.
Do not attempt to use this device with parameters that exceed permissible levels.
Install an external circuit breaker and take appropriate safety measures against short-circuiting
in external wiring.
To avoid damaging the system, do not connect / disconnect the device when the power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Leave a minimum of 10mm space for ventilation between the top and bottom edges of the
device and the enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Mounting the Module
DIN-rail mounting
Snap the device onto the DIN rail as shown below; the module will be squarely situated on the DIN rail.
60mm
(2.362")
3.5mm
(0.137")
14mm
(0.55")
80mm
(3.15")
93mm
(3.66")
44.5mm
(1.75")
UG_IO-PT400-4K I/O Expansion Modules
Unitronics
3
Screw-Mounting
The figure below is not drawn to scale. It may be used as a guide for screw-mounting the module.
Mounting screw type: either M3 or NC6-32.
4mm
5.8mm
(0.228")
85mm
(3.346")
80mm
(3.15")
68.4mm
(2.693")
93mm
(3.66")
4mm (x2)
(0.16")
(0.16")
UG_IO-PT400-4K I/O Expansion Modules
4
Unitronics
Connecting Expansion Modules
An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to
the adapter or to another module:
1. Push the module-to-module connector into the port located on the right side of the device.
Note that there is a protective cap provided with the adapter. This cap covers the port of the final
I/O module in the system.
To avoid damaging the system, do not connect or disconnect the device when the
power is on.
1 2
Component identification
1
Module-to-module
connector
2
Protective cap
Wiring
Do not touch live wires.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Wiring Procedures
Use crimp terminals for wiring; use 26-14 AWG wire (0.13 mm 23.31 mm2) for all wiring purposes.
1. Strip the wire to a length of 7±0.5mm (0.2500.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure that a proper connection can be made.
4. Tighten enough to keep the wire from pulling free.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
Install at maximum distance from high-voltage cables and power equipment.
UG_IO-PT400-4K I/O Expansion Modules
Unitronics
5
I/O WiringGeneral
Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance. Use wire
that is properly sized for the load.
Analog Inputs
Shields should be connected at the signal source.
PT1000/NI1000*
2 wire connection
4 wire connection
RTD
RTD
3 wire connection
RTD
* RTD input types PT1000/NI1000 support a two-wire connection, because the high resistance (1000 ohm)
of the sensor element compensates for voltage drop.
IO-PT400, IO-PT4K Technical Specifications
Max. current consumption
35mA maximum from the adapter’s 5VDC
UG_IO-PT400-4K I/O Expansion Modules
6
Unitronics
Typical power consumption
0.09W @ 5VDC
Status indicator
(RUN)
Green LED:
Lit when a communication link is established between module and OPLC.
Blinks when the communication link fails.
Analog Inputs
Number of inputs
4
Model number
I/O-PT400
I/O-PT4K
RTD type
PT100, NI100, NI120
PT1000, NI1000
Temperature coefficient
PT: 385/392, NI100: 618, NI120: 672
PT: 385/392, NI: 618
See Note 1
Temperature unit
°C and °F
Temperature range
PT100/1000
-50° to 460°C (-58° to 860°F)
NI100/1000
-50° to 232°C (-58° to 449°F)
NI120
-50° to 172°C (-58° to 341°F)
Isolation
None
Resolution
12-bit (4096 units)
Measurement resolution
±0.1°C (0.1°F). See Note 2.
Conversion method
Successive approximation
Conversion time
40msec
Input impedance
10MΩ minimum
Auxiliary current
PT100/NI100/NI120
1.9mA
PT1000/NI1000
0.19mA
Linearity error
I/O-PT400
I/O-PT4K
±0.3°C (0.6°F) (±0.05%)
±0.4°C (0.8°F) (±0.06%)
Temperature accuracy
±0.4°C (0.8°F)
Status indicators
(OUT OF RANGE)
Red LEDsLit when the corresponding input measures an analog value
(temperature) outside of the permissible range. See Note 3.
Connection options
2, 3 or 4 wires
Environmental
IP20 / NEMA1
Operating temperature
0 to 50C (32 to 122° F)
Storage temperature
-20 to 60C (-4 to 14F)
Relative Humidity (RH)
10% to 95% (non-condensing)
Dimensions (WxHxD)
80 x 93 x 60mm (3.15 x 3.66 x 2.362”)
Weight
140.3g (4.94oz.)
Mounting
Either onto a 35mm DIN-rail or screw-mounted.
UG_IO-PT400-4K I/O Expansion Modules
Unitronics
7
Notes:
1. Alpha () type is selected in software. The PT default setting is 385.
2. The input analog value represents the temperature value as follows:
Analog value-262 Actual measured temperature: 26.2C
3. The temperature values can also indicate certain faults as shown in the following table.
Value
Possible Cause
-10000 (-1000°)
Input temperature is out of the permissible range
(under -50°C)
-I signal is not connected
Sensor is short-circuited
10000 (1000°)
Input temperature is out of the permissible range
(PT: over 460°C) (NI: over 232° C) (NI120: over 172C)
Sensor is not connected to input
+I or +V signals are not connected
-I and V signals are not connected
Addressing I/Os on Expansion Modules
Inputs and outputs located on I/O expansion modules that are connected to an OPLC are assigned
addresses that comprise a letter and a number. The letter indicates whether the I/O is an input (I) or an
output (O). The number indicates the I/O’s location in the system. This number relates to both the position
of the expansion module in the system, and to the position of the I/O on that module.
Expansion modules are numbered from 0-72 as shown in the figure below.
0 1 2 3 4 5 6 7 Expansion module
identification number
Adapter
The formula below is used to assign addresses for I/O modules used in conjunction with the OPLC.
X is the number representing a specific module’s location (0-7). Y is the number of the input or output on that
specific module (0-15).
The number that represents the I/O’s location is equal to:
32 + x • 16 + y
Examples
Input #3, located on expansion module #2 in the system, will be addressed as I 67,
67 = 32 + 2 • 16 + 3
Output #4, located on expansion module #3 in the system, will be addressed as O 84,
84 = 32 + 3 • 16 + 4.
UG_IO-PT400-4K I/O Expansion Modules
8
Unitronics
UL Compliance
The products listed above may be used with compatible Unitronics PLCs.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, and
additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: IO-AI4-AO2, IO-AO6X, IO-ATC8, IO-DI16, IO-DI16-L, IO-DI8-RO4,
IO-DI8-RO4-L, IO-DI8-TO8, IO-DI8-TO8-L, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16,
EX-A2X are UL listed for Hazardous Locations.
The following models: EX-D16A3-RO8, EX-D16A3-RO8L, EX-D16A3-TO16, EX-D16A3-TO16L,
IO-AI1X-AO3X, IO-AI4-AO2, IO-AI4-AO2-B, IO-AI8, IO-AI8Y, IO-AO6X, IO-ATC8, IO-D16A3-RO16,
IO-D16A3-RO16L, IO-D16A3-TO16, IO-D16A3-TO16L, IO-DI16, IO-DI16-L, IO-DI8-RO4,
IO-DI8-RO4-L, IO-DI8-RO8, IO-DI8-RO8-L, IO-DI8-TO8, IO-DI8-TO8-L, IO-DI8ACH, IO-LC1, IO-LC3,
IO-PT4, IO-PT400, IO-PT4K, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16, EX-A2X, EX-RC1 are
UL listed for Ordinary Location.
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that
have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-hazardous
locations only.
Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
WARNINGExplosion Hazardsubstitution of components may impair suitability for Class I,
Division 2.
WARNING EXPLOSION HAZARD Do not connect or disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
WARNING Exposure to some chemicals may degrade the sealing properties of material used in
Relays.
This equipment must be installed using wiring methods as required for Class I, Division 2 as per
the NEC and/or CEC.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Input/Output expansion modules, Models: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L
When these specific products are used in hazardous locations, they are rated at 3A res, when these specific
products are used in non-hazardous environmental conditions, they are rated at 5A res, as given in the
product’s specifications.
Certification UL des automates programmables, pour une utilisation en environnement à
risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés
pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
UG_IO-PT400-4K I/O Expansion Modules
Unitronics
9
Attention
Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend caduque
la certification du produit selon la Classe I, Division 2.
AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue pour
être non dangereuse.
AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés des
matériaux utilisés pour l'étanchéité dans les relais.
Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
Modules d’Extensions d'E/S, modèles: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L.
Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive, lorsque ces produits spécifiques sont utilisés dans un environnement non
dangereux, ils sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de
températures.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice,
to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness
for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be
liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this
information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you
are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
UG_IO-PT400-4K.pdf 11/22
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9

Unitronics IO-PT400 I-O Expansion Modules Mode d'emploi

Taper
Mode d'emploi