9
4.1 Important Safety Warning
Read this manual thoroughly before undertaking any installation and wiring. An authorized Tripp Lite engineer must perform the start-up of the
UPS and a completed start-up form must be returned to Tripp Lite in order to activate the SmartOnline SVX warranty. Please contact your local
supplier or
[email protected] for further details. T
o find your local contact, go to www
.tripplite.com/support/ and click on ‘Service Centers’.
4.2 Transportation
WARNING
The UPS is packed on a pallet suitable for handling with a forklift. If using a forklift or other equipment to move the
UPS, ensure its load bearing capacity is sufficient to support the total packing weight of the UPS.
The UPS is fixed on the pallet with four balance supports. When removing them, pay attention to the movement of the
casters to avoid accidents.
The UPS cabinet may be pushed forward or backwards only; it may not be moved sideways. The cabinet has a high
center of gravity; take care to not tip or overturn the cabinet during transportation.
If moving the UPS over long distance, use appropriate equipment such as a forklift; do not move the UPS cabinet using
its attached casters over long distances, move the UPS cabinet in its original packaging until at the final destination site.
4.3 Delivery
Inspect the packaging materials and UPS cabinet carefully upon delivery. Do not install a damaged UPS, connect it to a battery or to the utility.
The packing box of the UPS is equipped with an anti-tilt device. Confirm the device does not indicate any shock or excess tilt during transit. If the
device indicates there has been excessive shock or tilt, do not install and contact your local Tripp Lite representative.
4.4 Installation Environment
• The UPS is designed for indoor use only. Do not place or install the UPS in an outdoor area.
• When moving the UPS to its installation site, ensure all corridors, doors, gates, elevators, floors, etc. are able to accommodate and bear the
combined weight of the UPS system, any associated battery cabinets and all handling equipment. See Section 13: Technical Specifications
for UPS module combined weights.
• The installation site should have a dedicated AC circuit available, compatible with the UPS system’s input requirements. See Section 13:
Technical Specifications for input specifications.
• Ensure the installation area has sufficient space for maintenance and ventilation of the UPS system.
• Maintain the installation area’s temperature below 30°C and the humidity below 90%. The highest operating altitude is 2000 m above sea
level. Please consider the derating values when operating the UPS over 1000 m. The optimum operating temperature for the batteries is 25°C.
• The UPS should be located in an environment with clean air and adequate ventilation to maintain the ambient temperature within the UPS
operating range.
• The UPS is air-cooled with the aid of internal fans. Do not cover the ventilation openings of the UPS system.
• Install the UPS in an area in which the walls, floors and ceilings are constructed with fireproof materials. The UPS is suitable for mounting on
concrete or other non-combustible surfaces only.
• Install a CO
2
or dry powder extinguisher in the installation area.
• Maintain a clearance of at least 100 cm from the top of the UPS for maintenance, cabling and ventilation.
• Maintain a clearance of at least 120 cm from the rear and front of the UPS for access and ventilation.
4. Positioning and Pre-Installation