Grundfos KPVS Installation And Operating Instructions Manual

Taper
Installation And Operating Instructions Manual

Ce manuel convient également à

GRUNDFOS INSTRUCTIONS
KP, KPV, KPVS
Split-case centrifugal pumps
Installation and operating instructions
Table of contents
2
KP, KPV, KPVS
English (US)
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Français (CA)
Notice d'installation et de fonctionnement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Español (MX)
Instrucciones de instalación y operación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Annexe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Anexo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
3
English (US)
English (US) Installation and operating instructions
Original installation and operating instructions
These installation and operating instructions describe Grundfos
KP, KPV, KPVS pumps.
Sections 1-6 give the information necessary to be able to unpack,
install and start up the product in a safe way.
Sections 7-11 give important information about the product, as
well as information on service, fault finding and disposal of the
product.
CONTENTS
Page
1. Limited warranty
4
2. General information
4
2.1 Symbols used in this document
4
2.2 Other important notes
5
3. Receiving the product
5
3.1 Unpacking the product
5
3.2 Inspecting the product
6
3.3 Temporary storage after delivery
6
4. Installing the product
7
4.1 Location
7
4.2 Pump foundation
7
4.3 Securing the baseplate
7
4.4 Mechanical installation
8
4.5 Electrical connection
9
4.6 Outlet pipe
10
4.7 Shaft seals
10
4.8 Coupling alignment (KP)
11
5. Starting up the product
12
5.1 Priming
12
5.2 Pre-start checklist
12
5.3 Motor direction of rotation
12
5.4 Starting the pump
13
6. Handling and storing the product
13
7. Product introduction
13
7.1 Applications
13
7.2 Pumped liquids
13
7.3 Pump identification
14
8. Servicing the product
16
8.1 Maintaining the product
16
8.2 Disassembling the pump
18
8.3 Reassembling the pump (KP, KPV, KPVS)
20
8.4 Recommended spare parts
22
8.5 KP, Horizontal, cross-section and parts list
23
8.6 KPV, Vertical, cross-section and parts list
24
8.7 KPVS, Vertical Split Coupling Split Case, cross-section
and parts list
25
8.8 Taking the product out of operation
26
9. Fault finding the product
27
10. Technical data
29
10.1 Operating conditions
29
11. Disposing of the product
29
WARNING
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
WARNING
The use of this product requires experience with and
knowledge of the product. Persons with reduced
physical, sensory or mental capabilities must not use
this product, unless they are under supervision or
have been instructed in the use of the product by a
person responsible for their safety. Children must not
use or play with this product.
CAUTION
Successful operation depends on careful attention to
the procedures described in this manual. Keep this
manual for future use.
English (US)
4
1. Limited warranty
New equipment manufactured by seller or service supplied by
seller is warranted to be free from defects in material and
workmanship under normal use and service for a minimum of
twelve (12) months from date of installation, eighteen (18) months
from date of shipment, unless otherwise stated in product
warranty guide (available upon request). In the case of spare or
replacement parts manufactured by seller, the warranty period
shall be for a period of twelve months from shipment. Seller's
obligation under this warranty is limited to repairing or replacing,
at its option, any part found to its satisfaction to be so defective,
provided that such part is, upon request, returned to seller's
factory from which it was shipped, transportation prepaid. Parts
replaced under warranty shall be warranted for twelve months
from the date of the repair, not to exceed the original warranty
period. This warranty does not cover parts damaged by
decomposition from chemical action or wear caused by abrasive
materials, nor does it cover damage resulting from misuse,
accident, neglect, or from improper operation, maintenance,
installation, modification or adjustment. This warranty does not
cover parts repaired outside seller's factory without prior written
approval. Seller makes no warranty as to starting equipment,
electrical apparatus or other material not of its manufacture. If
purchaser or others repair, replace, or adjust equipment or parts
without seller's prior written approval, seller is relieved of any
further obligation to purchaser under this paragraph with respect
to such equipment or parts, unless such repair, replacement, or
adjustment was made after seller failed to satisfy within a
reasonable time seller's obligations under this paragraph. Seller's
liability for breach of these warranties (or for breach of any other
warranties found by a court of competent jurisdiction to have
been given by seller) shall be limited to: (a) accepting return of
such equipment exw plant of manufacture, and (b) refunding any
amount paid thereon by purchaser (less depreciation at the rate
of 15 % per year if purchaser has used equipment for more than
thirty [30] days), and canceling any balance still owing on the
equipment, or (c) in the case of service, at seller's option, redoing
the service, or refunding the purchase order amount of the
service or portion thereof upon which such liability is based.
These warranties are expressly in lieu of any other warranties,
express or implied, and seller specifically disclaims any implied
warranty of merchantability or fitness for a particular purpose, and
in lieu of any other obligation or liability on the part of the seller
whether a claim is based upon negligence, breach of warranty, or
any other theory or cause of action. In no event shall seller be
liable for any consequential, incidental, indirect, special or
punitive damages of any kind. For purposes of this paragraph, the
equipment warranted shall not include equipment, parts, and
work not manufactured or performed by seller. With respect to
such equipment, parts, or work, seller's only obligation shall be to
assign to purchaser the warranties provided to seller by the
manufacturer or supplier providing such equipment, parts or
work. No equipment furnished by seller shall be deemed to be
defective by reason of normal wear and tear, failure to resist
erosive or corrosive action of any fluid or gas, purchaser's failure
to properly store, install, operate, or maintain the equipment in
accordance with good industry practices or specific
recommendations of seller, including, but not limited to seller's
installation and operation manuals, or purchaser's failure to
provide complete and accurate information to seller concerning
the operational application of the equipment.
2. General information
2.1 Symbols used in this document
The text accompanying the three hazard symbols DANGER,
WARNING and CAUTION will be structured in the following way:
Example
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off
and that it cannot be accidentally switched on.
5
English (US)
2.2 Other important notes
3. Receiving the product
3.1 Unpacking the product
3.1.1 Lifting and handling
Lifting KP (horizontal) pump without motor
1. Before unloading the product, move the shipping container to
an open area equipped with overhead lifting equipment.
2. Install a lifting strap on each side of the bearing housing. See
fig. 1.
Fig. 1 KP bare shaft pumps, correct lifting points
KP (horizontal) pumps, complete with motor
1. Before unloading the product, move the shipping container to
an open area equipped with overhead lifting equipment.
2. Lift complete horizontal KP pump units by fork truck from
beneath the pump's steel base.
Fig. 2 Horizontal KP complete pumps, correct lifting points
A blue or grey circle with a white graphical symbol
indicates that an action must be taken to avoid a
hazard.
A red or grey circle with a diagonal bar, possibly with
a black graphical symbol, indicates that an action
must not be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Notes or instructions that make the work easier and
ensure safe operation.
WARNING
Damage to personnel or product
Death or serious personal injury
- Allow only qualified personnel to handle the
product during receiving, inspecting, and
unpacking.
WARNING
Overhead load
Death or serious personal injury
- Do not lift the product by the lifting lugs or eye
bolts on the motor.
Unload and handle the product with a sling.
- All complete horizontal KP pump units must be
lifted by fork truck from beneath the pump's steel
base.
WARNING
Crushing hazard
Death or serious personal injury
- Always lift the pump with lifting equipment.
- Use the correct lifting points.
Do not use lifting lugs on the pump or eye bolts on
the motor to lift the entire pump assembly.
Lifting equipment is the responsibility of the
customer. The following instructions are suggestions
only.
Before proceeding, read the warnings and
instructions in sections 2. General information
through 8.1 Maintaining the product.
TM04 0380 0608
TM06 8436 0517
English (US)
6
Lifting KPV, KPVS (vertical) pumps
Before unloading the product, move the shipping container to an
open area equipped with an overhead lifting mechanism.
1. Install a lifting strap on each of the pallet's 4 x 4 in. floor
boards. Attach the straps securely at the corners of the pallet
near the top of the pump motor. See fig. 3.
2. Attach the other end of the straps to a lifting hook.
3. Rotate the pump assembly to the vertical position.
4. Remove excess packaging for easier access to the pump
assembly.
5. Position two lifting straps around the motor, below the junction
box and 180 degrees apart. See fig. 4.
6. Tighten the straps securely.
7. Attach the free ends of the lifting straps to a lifting hook.
8. Tie a strap around the upper portion of the motor to hold the
lifting strips tight against the motor. Ensure the straps stay
tight against the motor while moving the pump assembly.
9. Utilize appropriately rated lifting equipment to move the pump
assembly to the installation location.
Fig. 3 KPV, KPVS pumps, correct lifting points for pallet
Fig. 4 KPV, KPVS pumps, correct lifting points
3.2 Inspecting the product
Check that the product received is in accordance with the
order.
Check that the voltage and frequency of the product match the
voltage and frequency of the installation site. See section
7.3 Pump identification.
Check the product for defects and damage immediately upon
arrival. Any accessories ordered will be packed in a separate
container and shipped with the product.
If any equipment is damaged in transit, promptly report this to
the carrier's agent. Make complete notations on the freight bill.
3.3 Temporary storage after delivery
If the product is not to be installed and operated immediately after
receiving it, store it in a clean, dry place at a moderate ambient
temperature. Protect the pump from moisture, dust, dirt and
foreign bodies. Prior to and during storage, we recommend these
precautions:
1. Ensure that the bearings are filled with the recommended
grease to prevent moisture from entering around the shaft.
See section 8.1.2 Lubricating the pump bearings.
2. Ensure that the inlet and outlet ports of the pump and all other
openings are covered with cardboard, wood or masking tape
to prevent foreign objects from entering the pump.
3. Cover the product with a tarpaulin or other suitable covering if
it is to be stored where there is no protective covering.
4. Rotate the shaft 2 turns every 2 weeks to coat the bearings,
stuffing box (packing), and shaft seal faces with lubricant to
impede oxidation and corrosion.
5. This equipment contains vegetable fiber gaskets that can dry
out during long storage periods. To avoid leaks, fill the pump
with water and let stand for 24 hours prior to startup or
pressure testing. Typically, this will allow the dry gaskets to
wick moisture back into themselves, sealing the pump.
6. Split case pumps must be pressurized only with the medium
they are intended to pump. Do not perform any pressurized
"air" test.
TM06 8345 0117 - TM06 8347 0117TM06 8348 0117
Attach lifting
straps to the
pallet
Use lifting
straps to
rotate the
pallet with the
pump
assembly to
vertical
position
Strap
7
English (US)
4. Installing the product
All installations must be performed by personnel experienced with
the placement, connection, and alignment of pumping equipment.
The following instructions are general in nature, and may not deal
with the specifics of your installation. Read these instructions
thoroughly before installing and operating your KP, KPV, or KPVS
pump.
4.1 Location
Locate the pump as close as possible to the liquid supply. Use
the shortest and most direct inlet pipe practical. Refer to
section 4.4.2 Inlet pipe.
Locate the pump below system level wherever possible. This
will facilitate priming, assure a steady liquid flow, and provide
a positive inlet pressure.
The Net Positive Suction Head (NPSH) available must always
be equal to or exceed the required NPSH specified on the
pump performance curve. Make sure that sufficient NPSH is
provided at the inlet.
Always allow sufficient accessibility space for maintenance
and inspection. Provide a clearance of 24 in. (610 mm) with
ample head room for use of overhead lifting equipment strong
enough to lift the product.
Do not expose the product to sub-zero temperatures to
prevent the pumped liquid from freezing. If there is frost during
shutdown periods, see the shutdown information included in
section 8.8 Taking the product out of operation.
4.2 Pump foundation
Install the pump permanently on a firm, raised concrete
foundation of sufficient size to dampen any vibration and prevent
any deflection or shaft misalignment. The foundation may float on
springs or be a raised part of the floor.
Proceed like this:
1. Pour the foundation without interruption to 0.75 - 1.5 in. (20-
35 mm) below the final pump level.
2. Scour and groove the top surface of the foundation before the
concrete sets to provide a suitable bonding surface for the
grout.
3. Place anchor bolts in pipe sleeves for positioning allowance.
See fig. 5 and fig. 6.
4. Allow enough bolt length for grout, base, flange, nuts, and
washers.
5. Allow the foundation to cure several days before proceeding
to install the pump.
Fig. 5 KP anchor bolt installation
Fig. 6 KPV, KPVS anchor bolt installation
4.3 Securing the baseplate
When the raised concrete foundation has been poured and
allowed to set, proceed as follows:
1. Lower the base plate over the anchor bolts and rest it on loose
adjustment wedges or shims placed near each anchor bolt
and at intervals not exceeding 24 in. (610 mm) along each
side.
2. Place the shims or wedges so that they raise the bottom of the
base plate 0.75 in. - 1.25 in. (20-32 mm) above the pad,
allowing clearance for grout.
3. Level the pump shaft, flanges, and base plate using a spirit
level, adjusting the wedges or shims, as required.
4. Make sure that the pipes can be aligned to the pump flanges
without placing any strain on either flange.
5. After pump alignment has been established, put nuts on
anchor bolts and tighten them just enough to keep the base
plate from moving.
6. Construct a formwork around the concrete foundation and
pour grout inside and around the base plate. See fig. 5 for KP
and fig. 6 for KPV, KPVS. The grout will compensate for
uneven foundation, distribute the weight of the pump, and
prevent shifting.
7. Allow at least 24 hours for the grout to set before proceeding
with the pipe connections.
8. After the grout has thoroughly hardened, check the anchor
bolts and tighten them if necessary. Recheck the pump
alignment after tightening the anchor bolts.
TM05 4775 2512
Grout
Base plate
Finished grouting
0.75 to 1.25 in.
(20 to 32 mm)
allowance for
grout
Formwork
Pipe sleeve
Washer
Lug
Top of foundation
Wedges or shims
left in place
0.25
TM06 6124 0816
Place a spirit level on top of the pump to check that it
is level.
Use an approved, non-shrinking grout.
KPV, KPVS
stand
Anchor bolts for
supporting the base
Wedges or shims
(as required)
Grouted pad for
anchoring/
housekeeping
English (US)
8
4.4 Mechanical installation
4.4.1 Piping
Make sure that both the inlet and outlet pipes are
independently supported and properly aligned so that no strain
is transmitted to the pump when the flange bolts are tightened.
Use of expansion joints or vibration pads does not preclude
the need to properly support the pipes. Make sure that the
pipes are as straight as possible, so as to avoid unnecessary
bends and fittings.
KP, KPV, KPVS pumps have 250 lb flanges which are drilled
according to the pump's service. Non-standard hardware may
be required.
Do not apply force to pipes when making connections.
4.4.2 Inlet pipe
Select and install the inlet pipe in a manner that minimizes
pressure loss and permits sufficient liquid flow into the pump
during starting and operation. Many NPSH issues can be traced
to improper selection and installation of the inlet pipe.
Observe the following precautions when installing the inlet pipe:
Run the inlet pipe as straight as possible to avoid unnecessary
bends and fittings. Ideally, make sure that the length is at least
ten times the pipe diameter. A short inlet pipe can be the same
diameter as the inlet port. A long pipe must be one or two
sizes larger than the inlet port, depending on the length, and
with a reducer between the pipe and the inlet port.
Use an eccentric reducer, with the tapered side down. See fig.
7.
If possible, run a horizontal inlet line along an even gradient.
We recommend a gradual upward slope to the pump under
suction lift conditions, and a gradual downward slope under
positive inlet pressure conditions.
Avoid any high points, such as pipe loops (see fig. 8), as this
may create air pockets and throttle the system or cause erratic
pumping.
Install a gate valve in the inlet line to be able to isolate the
pump during shutdown and maintenance, and to facilitate
pump removal. Where two or more pumps are connected to
the same inlet line, install two gate valves to be able to isolate
each pump from the line.
Always install gate valves or butterfly valves in positions that
prevent air pockets.
During pumping operation, the valves on the inlet line must
always be fully open.
Install properly sized pressure gauges to enable the operator
to monitor the pump performance and determine whether the
pump conforms to the parameter of the performance curve. If
cavitation, vapor binding, or other unstable operating
situations occur, the pressure gauges will indicate wide
fluctuation in the inlet and outlet pressures.
Fig. 7 Inlet pipe
Fig. 8 Air pocket prevention
Do not let the pump support the pipes. Use pipe
hangers or other supports at proper intervals to
provide pipe support near the pump.
At no point must the diameter of the inlet pipe be
smaller than that of the pump inlet port.
Do not use globe valves, particularly when NPSH is
critical.
TM05 4773 2512TM 05 4774 2512
Correct
Eccentric
reducer
Taper is down
Air pocket
Wrong
Concentric
reducer
Correct
Air pocket
Wrong
9
English (US)
4.5 Electrical connection
4.5.1 Motors
The motor control circuit must include the following components
in order to comply with the National Electrical Code:
Motor disconnecting device
Install a motor disconnecting device that is capable of
disconnecting both the controller (motor-protective circuit
breaker) and the motor from their source of power.
Locate the disconnecting device in such a way that the
controller (motor-protective circuit breaker) can be seen from
the disconnecting device. In all cases, the distance from the
disconnecting device to the controller must be less than 50 ft
(15.24 m).
In most installations, the disconnecting device will be a circuit
breaker or fusible disconnect switch.
Motor short circuit and ground fault circuit interrupter
A short circuit and ground fault circuit interrupter is usually a
circuit breaker or fusible disconnect switch.
Select the circuit breaker or fuse in accordance with section
430-52 and table 430-152 of the National Electrical Code.
Motor controller with overcurrent protection (magnetic
starter)
Install these components in accordance with applicable local
and state electrical codes in addition to the National Electrical
Code.
The operating voltage and frequency are marked on the motor
nameplate.
Check that the voltage, phase and frequency of the incoming
power source correspond to the voltage, phase and frequency
of the motor(s).
Electrical characteristics must match those specified on the
motor nameplate.
The electrical connections must be carried out as shown on
the motor nameplate or in the wiring diagram on the back of
the terminal box cover. If further information is needed, contact
the motor supplier.
Mount the control panel or the motor-protective circuit
breaker(s) close to the pump to provide convenient control and
easy installation.
Make sure that the starters and overload control devices are
suitable for operating the pump motors on the voltage, phase
and frequency available. Always follow the control
manufacturer's instructions for proper installation and
connection.
Grease-lubricated motors are fully lubricated at the time of
manufacture and do not require further lubrication if prompt
installation follows. If the motor has been in storage for six
months or longer, refer to section 8.1.1 Lubricating the motor
and lubricate it before starting.
DANGER
Electric shock
Death or serious personal injury
- The electrical installation must be carried out by a
qualified electrician in accordance with local
regulations and the manuals provided with the
electrical accessories.
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off
and that it cannot be accidentally switched on.
DANGER
Explosive environment
Death or serious personal injury
- Observe the rules and regulations generally or
specifically imposed by the relevant responsible
authorities or trade organizations in relation to
running powered equipment in an explosive
environment.
English (US)
10
4.5.2 Variable frequency drive operation
In principle, all three-phase motors can be connected to a
variable frequency drive.
However, variable frequency drive operation will often expose
the motor insulation system to a heavier load and cause the
motor to be more noisy than usual due to eddy currents
caused by voltage peaks.
In addition, large motors driven via a variable frequency drive
will be loaded by bearing currents.
When the pump is operated via a variable frequency drive,
check the following operating conditions:
4.6 Outlet pipe
A short outlet pipe can be the same diameter as the pump
outlet port. A long pipe must be one or two sizes larger than
the outlet port, depending on the length.
It is best to use long horizontal outlet pipes.
Install a gate valve near the outlet port to be able to isolate the
pump during shutdown and maintenance, and to facilitate
pump removal.
Any high points in the outlet pipe may entrap air or gas and
thus impede pump operation.
If water hammer occurs, that is if check valves are used, close
the outlet gate valve before pump shutdown.
4.7 Shaft seals
The KP pumps are available with stuffing boxes with packing
rings or mechanical shaft seals.
4.7.1 Stuffing boxes (KP)
The stuffing boxes are normally packed before shipment.
If the pump is installed within 60 days, the packing material will be
in good condition for operation with a sufficient supply of
lubricating liquid.
If the pump is stored for more than 60 days, it may be necessary
to repack the stuffing boxes.
The stuffing box must be supplied at all times with a source of
clean, clear liquid to flush and lubricate the packing rings.
4.7.2 Packing gland adjustment (KP)
Make sure that the flushing fluid lines are connected and their
valves are open.
With the pump running, adjust the packing gland to permit 40 or
60 drops per minute for shaft lubrication.
Tighten the packing gland evenly to provide uniform compression
on the packing material.
Do not operate packing dry, and do not over-tighten the packing
gland to eliminate leaking as this will cause the shaft sleeve to be
damaged.
After initial startup, additional packing and adjustment may be
required.
4.7.3 Mechanical seals
Mechanical shaft seals require no maintenance or adjustment.
KP, KPV, KPVS pumps equipped with mechanical shaft seals are
matched to the operating conditions for which the pump was sold.
Observe the following precautions to avoid shaft seal damage
and to obtain maximum shaft seal life:
Purge all air from the seal chambers and recirculation lines prior
to operating the pump.
Clean and purge the inlet pipe in new installations before
installing and operating the pump. Pipe scale, welding slag
and other abrasives can cause rapid shaft seal failure.
A mechanical shaft seal does not leak at all during normal
operation, therefore if any appreciable leakage occurs, the
seal must be removed, inspected and if necessary replaced.
We recommend keeping a stock of spare parts to reduce
equipment down time.
If in doubt whether the motor supplied can handle
variable frequency drive operation, contact the motor
supplier.
Operating
conditions
Action
2-, 4- and 6-pole
motors of 45 hp
and up
Check to make sure that one of the motor
bearings is electrically isolated. If not,
contact Grundfos.
Noise-critical
applications
Fit a dU/dt filter between the motor and the
variable frequency drive, it reduces the
voltage peaks and thus the noise.
Particularly noise-
critical applications
Fit a sinusoidal filter.
Cable length Fit a cable that meets the specifications
laid down by the variable frequency drive
supplier. The length of the cable between
motor and variable frequency drive affects
the motor load.
Supply voltage up
to 500 V
Check that the motor is suitable for
variable frequency drive operation.
Supply voltage
between 500 V and
690 V
Fit a dU/dt filter, it reduces the voltage
peaks and thus the noise,
or
check that the motor has reinforced
insulation.
Supply voltage of
690 V and upwards
Fit a dU/dt filter, it reduces the voltage
peaks and thus the noise,
and
check that the motor has reinforced
insulation.
Do not run the pump dry or against a closed valve.
Dry operation will cause shaft seal failure within
minutes.
Do not exceed temperature or pressure limitations
for the mechanical seal used.
11
English (US)
4.8 Coupling alignment (KP)
1. If the pump and motor were shipped mounted on a common
base frame as an assembly, remove the coupling guard.
2. Checking parallel and angular alignment
Place a straight edge and feeler gauges or a dial indicator
across both coupling hubs to check for horizontal, vertical,
and angular misalignment of the coupling hubs. See fig. 9.
Coupling alignment is correct when the measurements show
that all points of the coupling faces are within 0.005 in. (0.127
mm) of each other, or when the straight edge contacts both
hubs evenly in both horizontal and vertical positions. If
misalignment is detected, loosen the motor and shift or shim
as necessary to re-align. Then re-tighten the anchor bolts.
Always align the motor to the pump as pipe strain will occur if
the pump is shifted. Never reposition the pump on the base
frame.
3. Check shaft alignment once again after final piping
connections to the pump have been made, motor wiring
checked, correct direction of rotation has been established,
and pipes have been filled with liquid. See figs 10 and 11.
Fig. 9 KP, checking angular or parallel alignment
Fig. 10 KP, plan view clockwise (CW) rotation
Fig. 11 KP, plan view counterclockwise (CCW) rotation
Leave the coupling guards off until the pump priming
procedure has been completed.
Install the coupling guards after installation has been
completed to protect personnel from rotating machinery.
TM 05 4767 2512TM 05 4768 2512
TM05 9288 3173TM05 9289 3173
WARNING
Moving machine parts or blades
Death or serious personal injury
- Ensure an approved coupling guard is in place
before operating the product. Failure to observe
this warning could result in injury to operating
personnel.
Outlet
Inlet
Clockwise (CW) rotation
Outlet
Inlet
Counterclockwise (CCW)
rotation
English (US)
12
5. Starting up the product
5.1 Priming
KP, KPV, KPVS pumps are non-self-priming and must be
completely primed, that is filled with liquid, before starting.
If the pump will be operating with a positive inlet pressure,
prime it by opening the inlet valve and allowing liquid to enter
the pump housing. Open the vents at the top of the upper
pump housing and the top of each inlet dome, and make sure
that all air is forced out of the pump by the liquid before closing
the vents.
IMPORTANT: Rotate the shaft by hand while priming and
venting to free entrapped air from the impeller passageways.
If the pump will be operating with a suction lift, priming must
be accomplished by other methods. Use foot valves, ejectors
or vacuum pumps, or fill the pump housing and inlet line
manually with liquid.
5.2 Pre-start checklist
Make the following inspections before starting your KP, KPV,
KPVS pump.
1. Make sure that the inlet and outlet pipes have been cleaned
and flushed to remove dirt and debris.
2. Make sure that all wiring connections to the motor and starting
device are in accordance with the wiring diagram and produce
proper rotation.
3. If the motor has been in storage for a long time, either before
or after installation, refer to the motor instructions before
starting.
4. Check the voltage, phase, and frequency with the motor
nameplate.
5. Turn the impeller by hand to make sure that it rotates freely.
6. Tighten the plugs in the gauge and drain the holes. If the
pump is fitted with pressure gauges, keep the gauge cocks
closed when they are not in use.
7. Recheck the motor-to-pump alignment per section
4.8 Coupling alignment (KP).
8. Check inlet and outlet pipes for leaks, and make sure that all
flange bolts are securely tightened.
9. If the pump will run on a variable frequency drive, do not ramp
up the pump from reduced speeds. Go directly on-line at full
speed, especially at commissioning so adequate pressure is
generated to flush wear rings and create a hydrostatic bearing
effect.
5.3 Motor direction of rotation
After the unit has been wired and checked to ensure that all
components in the system, such as disconnect devices, magnetic
starters, pilot devices and motors, are properly connected, check
the motor direction of rotation as follows:
Make sure that the coupling is disconnected, then momentarily
energize the motors to ensure that the direction of rotation is
correct as indicated by the arrow cast into the pump housing.
If the direction of rotation is incorrect, interchange the two
wires at the motor-protective circuit breaker terminals T1 and
T2.
For Wye-Delta motors the direction of rotation has to be
verified for both wye and delta connections.
For proper direction of rotation, reference rotation drawing in
section 4.8 Coupling alignment (KP).
Never run the pump dry in the hope that it will prime
itself. The result will be serious damage to the shaft
seals, pump wear rings and shaft sleeves.
Do not operate the product above the range of the
nameplate conditions. This may damage the product.
Never check the motor direction of rotation unless
pump and motor couplings have been disconnected
and physically separated. Failure to follow this
instruction can result in serious damage to the pump
and the motor if the direction of rotation is wrong.
The pumps must not be operated while dry. Use
extreme caution that motors are energized only
momentarily to determine proper direction of rotation.
13
English (US)
5.4 Starting the pump
1. Install a coupling guard.
2. Fully open the gate valve (if any) in the inlet line, and close
the gate valve in the outlet line.
3. If applicable, turn on any external source of cooling or
lubricating fluid to the shaft seals.
4. Fill the inlet line with liquid and completely prime the pump.
5. Start the pump.
6. Immediately make a visual check of the pump and inlet pipe
for pressure leaks.
7. Immediately after the pump has reached full operating speed,
slowly open the outlet gate valve, and open the bleed valves
at system high points. Do not open the outlet gate valve
completely until the system is full of liquid, purged of air and
checked for leaks.
8. After entirely filling the system, fully open the outlet gate valve
and close the system bleed valves.
9. If the pump is fitted with pressure gauges, open the gauge
cocks and record pressure readings for future reference.
Verify that the pump is performing in accordance with the
parameters specified in the performance curves.
10. Check and record voltage, amperage per phase, and
kilowatts, if a wattmeter is available.
6. Handling and storing the product
See section 8.8 Taking the product out of operation.
7. Product introduction
7.1 Applications
We recommend KP, KPV, KPVS pumps for these applications:
circulation in heating and air conditioning systems, water
condensing and boiler feed systems
liquid transfer and pressure boosting in various industrial
systems
water distribution and water treatment in public water systems.
7.2 Pumped liquids
Use clean, thin, non-aggressive liquids, not containing solid
particles or fibers. Do not pump liquids that will attack the pump
materials chemically.
When pumping liquids with a density and/or viscosity higher than
that of water, pressure and flow will be reduced. Alternatively, use
motors with correspondingly higher outputs.
The stuffing box packing rings or the mechanical shaft seal O-
rings chosen must be suitable for the liquid to be pumped.
Special stuffing box packing rings or shaft seal O-rings may be
required if the pump is used for pumping treated water:
at temperatures above 176 °F (80 °C)
containing additives to prevent system corrosion, calcareous
deposits, etc. (this may be the case in heating and ventilating
systems).
When pumping liquids other than water, select an appropriate
stuffing box or shaft seal. For further information, please contact
Grundfos.
WARNING
Moving machine parts
Death or serious personal injury
- Mount an approved coupling guard before
operating the product.
For KPVS pumps, ensure the jacking screw (114) is
firmly seated and sealed by turning it
counterclockwise. This will prevent media leakage
during operation.
The absolute maximum operating temperature for the
pump is 275 °F (135 °C).
English (US)
14
7.3 Pump identification
All PACO pumps are identified by catalog and serial numbers.
These are stamped on the pump nameplate, as shown in fig. 12,
affixed to the pump housing. Refer to these numbers in all
correspondence with Grundfos.
7.3.1 Nameplate
Fig. 12 KP, KPV, KPVS nameplate
7.3.2 KP KPV model number and construction code
7.3.3 Type key
* 2" outlet on pumps with impellers 13"
TM05 7638 1313
Example 29 60123 140001 1852
Product code
Model code
Materials of construction
Motor code
Production code 29
29: Split case (KP, KPV)
31: Split coupled split case (KPVS)
Model code 60 12 3
Pump outlet
20 = 2"*
30 = 3"
40 = 4"
50 = 5"
60 = 6"
80 = 8
10 = 10"
12 = 12"
14 = 14"
16 = 16"
20 = 20"
24 = 24"
Nominal maximum impeller diameter
95 = 9.5"
12 = 12"
13 = 13"
14 = 14"
15 = 15"
19 = 19"
20 = 20"
24 = 24"
25 = 25"
27 = 27"
28 = 28"
Impeller design
Clockwise rotation:
1, 3, 5, 7, 9
Counterclockwise rotation:
0, 2, 4, 6, 8
Materials of construction 1 4 00 0 1
Packing or seal
3 = Standard packing
1 = Type 21, single seal, ceramic seat, Buna
2 = Type 21, single seal, Tungsten carbide seat,
Viton
6 = Type 21, single seal, Ni-Resist seat, Viton
7 = Type 21, single seal, Ni-Resist seat, Buna
8 = Type 1B, single seal, Ni-Resist seat, Buna
9 = Type 21, single seal, Ni Resist seat, Viton
A = Type 1, single seal, ceramic seat, Buna
B = Type 1, single seal, Ni-Resist seat, Viton
C = Type 1, single seal, Tungsten Carbide seat,
Viton
D = Type 1, single seal, Ni Resist seat, Buna
E = Type 1, single seal, ceramic seat, Buna
F = Type 1, single seal, Si Cbrd seat, EPDM
G = Type 8-1, single seal, Si C brd seat, Viton
H = Type 8-1, single seal, ceramic seat, Buna
ID of packing or seal
2 = 1"
3 = 1 - 1/4"
E = 1 - 1/2"
4 = 1 - 3/4"
5 = 2 - 1/4"
6 = 2 - 3/4"
7 = 3"
K = 3 - 1/2"
V = 4"
H = 4.1"
B = 4.7"
N = 5.5"
15
English (US)
** For packed pumps only (packed pumps standard with
distribution ring, recirculation lines, and hardened stainless
steel sleeves).
Materials of construction 1 4 00 0 1
General configuration (Horizontal)
Code no. Item
00 Standard
01 Double wear rings
02 Oil lube bearings
03 (01) + (02)
04 (01) + (05)
05 Recirculation lines
20 Double ext shaft
21 Double wear rings
22 Recirculation lines
24 (21) + (22)
30 Double ext shaft
31 Double wear rings
32 Recirculation lines
34 (31) + (32)
70 250 lb flange
71 Double wear rings
72 (71) + (73)
73 Recirculation lines
90 250 lb flange
91 Double wear rings
General configuration (Vertical)
Code no. Item
50 Standard (Vesconite for KPVS)
51 Double wear rings
52 Sleeve bearing
53 (51) + (52)
80 250 lb flange for 300 psi CWP
81 Double wear rings
82 Sleeve bearing
83 (81) + (82)
92 250 lb flange for 400 psi CWP
93 Double wear rings
94 Sleeve bearing
95 (93) + (94)
Shaft/sleeve metallurgy
0 = Steel/bronze
1 = Steel/stainless steel
3 = Stainless steell/bronze**
6 = Stainless steel/stainless steel or stainless steel/no sleeves
(KPVS)
7 = SS/hardened stainless steel
A = 316 SS/Ni Al Bronze
X = Special
Pump metallurgy
0 = Standard fitted
1 = Bronze fitted
2 = Standard all bronze
5 = All iron
8 = Ductile iron/bronze fitted
E = Ductile iron/stainless steel fitted
X = Special
Motor code 1782
Enclosure
1 = ODP
2 = TEFC
3 = Explosion Proof
Voltage
Hp
1-phase 3-phase
115/230 V 200 V 230/460 V
1/3
1/2
3/4
1
1-1/2
21
29
35
41
47
23
31
37
43
49
24
32
38
44
50
2
3
5
7-1/2
10
53
59
65
71
76
55
61
67
73
77
56
62
68
74
78
15
20
25
30
40
--
--
--
--
--
81
84
01
02
03
82
85
87
88
89
50
60
75
100
125
--
--
--
--
--
04
05
06
07
--
90
91
92
93
94
150
200
250
300
--
--
--
--
--
--
--
--
95
96
97
98
RPM
1 = 3500
2 = 1750
3 = 1150
Materials of construction 1 4 00 0 1
English (US)
16
8. Servicing the product
8.1 Maintaining the product
8.1.1 Lubricating the motor
Always follow the motor manufacturer's lubricating instructions, if
they are available, and periodically check grease fittings and
drain plugs for leaks. If the lubricating instructions are not
available, refer to the table below for recommended lubricating
intervals.
The motor can be lubricated both when it is running or when it
is at rest.
Remove the grease drain plug (if any) and filler plug on the
grease fitting. Grease with clean lubricant until grease
appears at the drain hole or along the motor shaft.
The table below lists the recommended types of grease for motor
lubrication. These types have all been thoroughly tested and
must be used whenever possible.
8.1.2 Lubricating the pump bearings
Regreasable bearings are packed with grease at our factory prior
to shipping. This initial filling of grease is good for one year or
2000 hours of normal operation, whichever occurs first. After one
year or 2000 hours of normal operation, a regular grease
maintenance schedule must be implemented.
8.1.3 Grease replacement (KP, KPV)
1. Remove the four (4) cap screws and remove the bearing
covers (113C and 113D) to allow access to the bearing.
2. Use a clean rag to remove as much old grease as possible
from the bearing.
3. Re-pack the bearing with sufficient grease to completely fill
and cover the balls inside the bearing.
4. Turn the pump shaft to ensure even and complete lubrication.
5. For drive end bearing maintenance, slide the bearing cover
back as far as possible and visually inspect bearing for
grease.
6. Proceed as stated above removing old grease with a clean
rag. If the bearing covers cannot be moved sufficiently to
allow access to bearing, remove the coupling hub.
7. Reinstall the bearing covers when the task is complete.
Bearing manufacturers recommend that you fill the bottom third of
the bearing with grease. After filling the bottom third with grease,
rotate the shaft to cover the balls inside the bearing.
DANGER
Moving machine parts
Death or serious personal injury
- Before any inspection, maintenance, service or
repair of the product, make sure that the motor
controls are in the "OFF" position, locked and
tagged.
Recommended lubricating intervals
Motor rpm Motor hp Operating conditions
1750 and
below
10-40 Standard Severe Extreme
50-150 1-3 years
6 months -
1 year
6 months -
1 year
200 and up 1 year 3 months 6 months
above
1750
All hp
1 year 3 months 6 months
1 year 3 months 3 months
Standard conditions:
Operating 8 hours per day, normal or light load, clean air, 100 °F
(37 °C), maximum ambient temperature.
Severe conditions:
Operating continuously 24-hours, shock loads or vibrations,
poor ventilation, 100-150 °F (37-65 °C), ambient temperature.
Extreme conditions:
Operating continuously, heavy shocks or vibrations, dirt or dust
in the air, extremely high ambient temperature.
Recommended bearing grease for motors
Manufacturer Bearing lubricant
Chevron SRI grease NLGI No. 2
Texaco Polystar RB2 NLGI No. 2
WARNING
Catastrophic failure
Death or serious personal injury
- Maintain proper lubrication schedule
- Do not operate the unit without proper lubrication
as this can result in overheating of the bearings,
bearing failures, pump seizures and actual
breakup of the equipment, exposing operating
personnel to personal injury.
Recommended bearing grease for pumps
Manufacturer Lubricant
Shell Dolium
®
Exxon Polyrex
®
Chevron
SRI Grease NLGI 22
Black Pearl NLGI 2
Phillips Polytrac™
Texaco Polystar RB
Do not over-grease. Too much grease can cause
overheating and premature bearing failure.
17
English (US)
8.1.4 Oil lubrication (KP, KPV)
Follow a regular oil maintenance program. KP, KPV pumps with
oil lubricated bearings are fitted with a transparent reservoir, a
constant-level oiler, that maintains the oil level about the center
line of the lower bearing. See 85 in fig. 13. When necessary,
renew the oil supply in the reservoir of the constant-level oiler. To
refill it, remove the reservoir and fill it with oil. After filling the
reservoir with oil, replace it into operating position.
Fig. 13 Oil lubricated bearing construction
Change the oil after the first 200 hours of operation. To change
the oil, remove the drain plug (16K) at the bottom of the bearing
cover and the filler plug (16B), at the top of the bearing frame.
After draining the oil, replace the fittings and refill the reservoir
with an oil selected from the table List of acceptable oil lubricants
below. After the first oil change, the oil must be changed again at
2000 hours and then at intervals of 8000 hours or once a year
thereafter.
8.1.5 Stuffing box (packing) or shaft seal water lubrication
(KP)
The stuffing (packing) box must be supplied at all times with a
source of clean, clear liquid to flush and lubricate the packing.
Only a sufficient volume of sealing liquid to create a definite
direction of flow from the stuffing box inward to the pump casing
is required. Pipe from the pump outlet dome to the packing box is
supplied when requested.
8.1.6 Maintaining packing (KP)
Pack the stuffing box with fresh packing before initial startup,
after repairs to the pump, and in case of excessive leaks. Any
time the packing is replaced, inspect the shaft sleeves for wear,
roughness or scouring and replace with new ones if necessary.
For instructions on filling the stuffing box see section Replacing
packing, each side. For seal gland adjustment see section
8.2.2 Bearing, seal and packing replacement.
8.1.7 Flexible coupling maintenance (KP, KPV)
The coupling is pre-greased at the factory. After disassembly it
must be greased again. For annual greasing refer to the coupling
manufacturer's instructions.
TM05 8898 2713
List of acceptable oil lubricants
Lubricant
manufacturer
Bearing oil brand name
Aral Refining Co. Aral Oil CMU Aral Oil Tu 518
British Petroleum Co. BP Energol TH 100-HB
Calypsol Oil Co. Calypsol Bison Oil SR 25 or SR 36
Standard Oil Co. Chevron Hydraulic Oil Circulating Oil 45
Esso Corporation Esso-Mar 52 Teresso 47 Esstic 50
Fina Oil Company Fina Hydran 43 Fina Cirkan 32
Gulf Refining Co. Gulf Harmony 47 Gulf Paramount 45
Socony Mobil Oil Co. Vac HLP 25 Mobilux D.T.E. 25
Shell Oil Company Shell Tellus Oil 29
Sundco Oil Company Sunvis 821
Texas Company Texaco Ursa oil P 20
Wisura Rining Co. Wisura Norma/Tempo 25 (36)
English (US)
18
8.2 Disassembling the pump
8.2.1 Preparations before disassembling the pump
KP, KPV, KPVS pumps are designed for ease of maintenance
and, as such, the seals, sleeves, wear rings, clearances and
bearings can be inspected without having to remove the complete
rotating element or having to disconnect the inlet or outlet pipes,
or disturbing the alignment of the pump set.
Work on this equipment is to be performed only by qualified
personnel. Read the following instructions completely before
performing any work on the pump.
Before beginning disassembly of the pump, proceed as follows:
1. Close the inlet and outlet isolation valves.
2. Turn off any external source of cooling or lubricating fluid to
the shaft seals.
3. Drain the pump case by opening the drain plug and vent
plugs.
4. Disconnect and lock off the motor power source.
8.2.2 Bearing, seal and packing replacement
All normally required parts for KP pumps are available in kit form.
Refer to figs. 14 and 15.
Bearing replacement
1. Remove the motor.
2. Remove the coupling half from the pump shaft (51) using a
wheel puller and remove the coupling key (11A).
3. Remove the bearing covers (113C) and (113D).
4. Loosen the set screws in the eccentric locking rings of the
bearings (53 and 54) and turn the rings in the opposite
direction of the direction of rotation to loosen from the shaft, or
remove the retaining snap ring, whichever is applicable.
5. Remove the cap screws from each bearing housing (124) and
slide, with bearing, off its end of the shaft.
6. Remove the bearings (53, 54) from the bearing housings.
7. Install the new seals and seal seats.
8. Reinstall the bearing housings less the bearings, noting that
the slinger (79) is in the correct position. Take care not to
break the seal seats of the seal type pumps by striking them
against the shaft.
9. Clean out the bearing housings and slide the new bearings
over the shaft and into the bearing housings. Press only on
inner race of the bearing. Use a bearing warmer, if available.
10. Turn the eccentric locking rings in the direction of pump
rotation to tighten on the shaft and tighten the set screws, or
replace the spacer and the retaining snap ring, whichever is
applicable.
11. Pack the ball bearings and bearing cover cavities with clean
ball bearing grease. See section 8.1.2 Lubricating the pump
bearings.
12. Replace the bearing covers (113C, 113D).
13. If applicable replace the packing glands after following
packing instructions in section Replacing packing, each side.
14. Gently tap the coupling half on the shaft (51) over the key
(11A). Do not tap it if it can be pushed on. Using too much
force to drive on the coupling half can damage the ball
bearings and/or fracture the seal faces. If there is difficulty
pushing the coupling onto the shaft, heat up the coupling half
to a temperature of not more than 300 °F (148 °C) and then
use protective gloves to slide the coupling half onto the shaft.
15. Replace motor and realign.
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off
and that it cannot be accidentally switched on.
CAUTION
Toxic material
Minor to moderate personal injury.
- Wash down the pump before doing any work on it.
WARNING
Hot, caustic, flammable or toxic materials,
including vapors
Death or serious personal injury
- Be extremely cautious when venting and/or
draining hazardous liquids.
Wear protective clothing when there are caustic,
corrosive, volatile, flammable, or hot liquids.
Do not breathe toxic vapors.
Do not allow sparks, open fire, or hot surfaces
near the equipment.
WARNING
Moving machine parts
Death or serious personal injury.
- Do not insert a screwdriver between the impeller
vanes to prevent rotation.
A clearance of 24 in. (610 mm) on each side of the
pump will allow for maximum access while servicing.
A minimum of 24 in. (610 mm) clearance is required
to remove the upper pump housing when accessing
the rotating element.
Take care to ensure the seal seats in the bearing
housings of seal type pumps are not broken during
housing removal.
On vertically mounted pumps, remove the rotating
assembly in order to replace the lower bearing and
seal assembly.
19
English (US)
Mechanical seal replacement
1. Follow the above steps to remove the bearing housings (124).
2. Remove the old seal head and the seal seat from the shaft
sleeve and bearing housing or seal cap.
3. Inspect the shaft sleeves (116) for scoring or pitting.
4. Replace if the surface is rough to your fingernail.
Proper seal seat installation
1. Clean the seal cap or bearing housing (124).
2. Lightly lubricate the new seat's rubber cap with liquid soap.
3. Press in the seal seat into the seal housing, making sure the
seat is seated squarely and all the way into seal cap or
bearing housing. Do not touch the seal seat or the head faces.
Proper seal head installation
1. Clean and lightly lubricate the shaft sleeves (116) or the shaft
(51). Make sure that there are no sharp edges or corners to
cut the seal's rubber parts.
2. Lightly lubricate the seal face elastomers with liquid soap.
3. Slide the assembly onto the sleeve or shaft until the spring
touches the shoulder. Do not compress the spring. Make sure
that the notches on the carbon ring match the retainer's lugs
and the spring is in position on the seal head.
4. Reinstall the bearing housings (124) with bearings, noting that
slingers (79) are in correct places. Take care not to strike seal
seats against shaft.
5. Follow remaining bearing replacement steps to complete
assembly.
Replacing packing, each side
1. Remove the packing gland.
2. Remove the old packing distribution ring, if any, and use a
packing hook to remove the packing behind the distribution
ring.
3. If the packing retainer comes out, replace it against the
retaining ring.
4. Insert two new packing rings one at a time, staggering the
joints 180 ° and pushing them firmly back against the packing
retaining washer.
5. Insert the distribution ring, if any.
6. Insert three more packing rings (applies to most sizes)
staggering joints 180 °. If no distribution ring is used, one
extra packing ring is required.
7. Replace the packing gland.
8. Adjust the packing gland to permit a leakage of 40 to 60 drops
per minute for shaft lubrication.
9. Never overtighten the packing gland. For suction lift
applications, should it become necessary to overtighten the
packing while starting the pump, make sure to loosen the
packing immediately after the pump is started, allowing a
leakage of a 40 to 60 drops per minute. After initial startup,
additional packing and adjustment may be required.
8.2.3 Bearing and seal replacement for KPVS
1. Remove the coupling guard and the coupling. See section
8.2.2 Bearing, seal and packing replacement.
2. Remove the seal housing cap screws and the seal housing
(124a).
3. Remove the seal head assembly (105) from the shaft (51).
Water-soluble lubricant may be applied to the shaft to ease
the removal of the seal head. Pull the seal head assembly
from the shaft, using a slight twisting motion (as necessary) to
loosen the bellows from the shaft.
4. Discard the seal, the spring and the retainer.
5. Remove and discard the seal seat and gasket from the seal
housing (124a) and thoroughly clean the inside cavity of the
seal housing and flange.
6. The interior surface of the bellows on the new shaft seal is
coated with a bonding agent that adheres to the pump shaft.
When the old shaft seal is removed, the bellows may crack or
split during removal. We recommend that you install a new
mechanical shaft seal if it becomes necessary to remove the
existing shaft seal from the shaft.
7. Clean and lubricate the pump shaft (51) with a water-soluble
lubricant and make sure that no sharp edges exist to cut or
scratch bellows of the new seal.
8. Install the new gasket onto the seal housing.
8.2.4 Disassembling Horizontal pumps (KP)
1. Remove the nuts and bolts that hold the pump housing halves
together (6A, 6B), and remove cap screws holding bearing
housing (124) to pump housing.
2. Remove roll pin (26B) then lift off upper pump housing (6A).
3. Place the gaskets in water to keep them from drying out and
shrinking.
4. Remove shaft assembly from the case.
5. To disassemble rotating assembly, refer to section Bearing
replacement.
6. Unscrew and remove shaft sleeves (116) or impeller locknuts
by turning them in direction of pump rotation. One has RH
(right-hand) threads. The other has LH (left-hand) threads.
Use a strap wrench. Do not place the wrench on the part of
sleeve that comes in contact with the seal or packing.
7. Remove the wear ring retaining parts as necessary, locking
pin (24) and/or rings (65).
8. Slide the wear ring (45) off the impeller.
9. Make an orientation mark for later reference on the impeller
(49) on the coupling side before removing it from the shaft, to
help ensure it will be reassembled identically.
10. Press the impeller (49) from the shaft (51) and the key (11).
It is not necessary to remove the bearings from the
bearing housings. However, we recommend that you
replace the bearings.
English (US)
20
8.2.5 Disassembling Vertical pumps (KPV)
1. Remove the coupling guard and remove the coupling grid.
2. Remove all the cap screws on the bearing housings (124)
except for the two on the lower pump housing (6B) to hold the
rotating assembly in place while removing the upper pump
housing (6A).
3. Remove the roll pin (26B) then lift off the upper pump housing
(6A).
4. Place the gaskets in water to keep them from drying out and
shrinking.
5. Remove the shaft assembly from the pump housing.
6. To disassemble the rotating assembly, refer to section Bearing
replacement.
8.2.6 Inspecting the components
1. While the pump is disassembled, inspect all components for
wear, damage, deterioration or erosion.
2. Inspect the shaft sleeves and replace them if they are worn or
deeply scored.
3. Check the impeller wear ring (if used) and the pump housing
wear ring (45) for erosion or wear and replace them if badly
deteriorated, to renew original pump performance. The design
clearance is 0.018 in. to 0.022 in. (0.457 mm to 0.558 mm)
diametrically. Clearances greater than 0.040 in. (1.016 mm)
will affect pump performance and new wear rings must be
installed.
4. Examine the lapped faces of the mechanical seals for scoring,
heat checking or cracking. Examine mechanical seal
elastomers (rubber components) for deterioration or
hardening. Replace mechanical seals if any damage exists.
5. Check any external source of cooling or lubricating fluid lines,
and/or recirculation lines and ports for clogs, kinks or other
restrictions.
6. Clean machined mating surfaces of all components to remove
grit, grime and/or old sealing material before reassembling
pump.
8.3 Reassembling the pump (KP, KPV, KPVS)
1. Reinstall the impeller (49) and the key (11) on the shaft (51),
centering the impeller on the shaft with respect to the sleeve
or the lock nut threads. Be sure the impeller is installed on the
shaft the same way it came off, with the vane curvature and
per the orientation mark made during disassembly. For proper
rotation, see figs. 10 and 11. Note that:
– The pump will deliver little or no water if the impeller is
installed backwards.
– Be sure a good O-ring gasket is in place on each sleeve, if
the shaft has sleeves. Replace as necessary.
2. Replace the shaft sleeves (116) or nuts, turning them in the
opposite direction of pump rotation. Do not place a wrench on
the part of the sleeve that comes in contact with the seal or
the packing. Tighten evenly so the impeller position will not
shift.
3. Replace the wear ring retaining ring (65) over the wear ring
(45).
4. Slide the wear ring (45) over each impeller hub.
5. Replace the wear rings (45) on the impeller (49). Replace with
new seals or packing. Replace the bearing housing (124) on
the shaft (51) carefully so as not to damage the seal (11B).
Replace the bearing (54) into the outboard housing and
washer and snap ring. Replace the coupling key (11A) with
the coupling half.
6. For packing type pumps, follow the steps in section
8.2.2 Bearing, seal and packing replacement then the steps in
section Replacing packing, each side.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Grundfos KPVS Installation And Operating Instructions Manual

Taper
Installation And Operating Instructions Manual
Ce manuel convient également à

dans d''autres langues