Tripp Lite SRCOOL2KWM Le manuel du propriétaire

Catégorie
Climatiseurs split-system
Taper
Le manuel du propriétaire
1
Wall-Mount Cabinet Air Conditioning Unit
SRCOOL2KWM (120V, 60 Hz)
Owner’s Manual
Introduction 2
Important Safety Instructions 2
Features 3
Accessories 4
Installation 4
Optional Accessories 8
Operation 9
Maintenance 10
Troubleshooting 11
Storage & Service 12
Warranty & Product Registration 12
Español 13
Français 25
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite.
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
2
Introduction
The self-contained Wall-Mount Cabinet Air Conditioning Unit provides 2,000 BTU of cooling capacity. Designed for IT environments, it’s ideal for
cooling overheated wall-mount rack enclosures and network closets without access to facility air conditioning. It also filters and dehumidifies air
to improve operating conditions and equipment reliability. Condensate is re-evaporated for drip-free operation, so you won’t waste time emptying
water collection tanks. The self-contained design does not require any plumbing or special circuits, so setup is quick and easy. Eco-friendly
R134A refrigerant meets environmental standards.
Recommended Applications:
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation
and storage of this product. Failure to heed these warnings may affect your warranty.
Warnings
The individual user should determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual
applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of this device
for any specific application.
Install the unit indoors, away from extreme temperatures or humidity, direct sunlight, dust and conductive contaminants.
Connect the unit directly to a grounded AC power outlet. Failure to do so may cause an electric shock or fire.
The power source supplying the unit must be rated in accordance with the unit’s nameplate.
Do not modify the plug nor use an adapter that would eliminate the ground connection.
Do not use an extension cord to connect the unit to an AC outlet. Use only the power cord that came with the unit.
Comply with all applicable wiring and safety regulations, such as National Electrical Code (NEC) in the United States.
Do not plug additional equipment into the outlet where the unit is plugged in. Overloading the outlet may cause an electric shock or fire.
Do not attempt to turn the unit on or off by connecting or disconnecting the AC plug. A serious electric shock may occur. Use the ON/OFF
button to turn the unit on or off.
Turn the unit off and unplug it from the AC outlet before performing maintenance.
Before connecting the unit to a dedicated drainage system, turn it off and unplug it. There is a risk of electric shock while the unit is plugged in.
Maintenance should be performed by trained personnel only.
Do not use thinners, alcohol, detergents or abrasive brushes to clean the unit’s cabinet. These items may damage the cabinet.
Do not pour water over the unit. This may cause an electric shock and damage the unit.
Do not operate the unit without the air filter. This may cause dust accumulation that may damage the unit.
Do not attempt to operate the unit in a room with inadequate air circulation. Failure to vent heat properly may cause the unit to malfunction.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended.
Cooling an overheated wall-mount rack enclosure.
A
IH
GF
C
E
A
B
B
B
D
C
I
J
K
D
E
G
H
F
3
Features
Front View
A
Air Filter
B
Front Panel
C
Directional Vent
D
Cool Air Output
E
Control Panel
F
SRCOOLNET2 Slot
G
Warm Air Exhaust
H
Duct Adapter
Rear View
I
AC Power Cord
J
Air Filter
K
Drainage Outlet
Control Panel
A
Numeric Display
B
Operating Mode LEDs
C
Temperature Control Buttons
D
Fan Speed Mode LEDs
E
“FAN SPEED” Button
F
“QUIET” Button
G
“TIMER” Button
H
“FUNCTION” Button
I
“POWER” Button
1
2 3
4
Accessories
Installation
Warning: After removing the unit from the shipping container, check for damage or missing parts (refer to the parts list below).
If you notice a problem, visit www.tripplite.com/support for service. Do not attempt to operate a damaged unit.
Accessory Parts List:
The procedures described in this section are for Tripp Lite wall-mount rack enclosure types and may not be appropriate for all applications. The
user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suitable for your application,
contact Tripp Lite for assistance.
Installation Notes
The SRCOOL2KWM is ideal for enclosures with perforated doors (not for use in enclosures with solid/acrylic glass/glass doors).
If your building’s cooling system has night or weekend thermostat setbacks, has periodic shutdowns, or has limited cooling
capacity, you may need to consider alternatives to the standard installation. This product is meant to be used as a
supplemental cooling device, and cannot make up for significant fluctuations in building temperature or humidity.
Adjustable Exhaust
Panel (2 Sections)
Exhaust Duct
Adapter
M6x16mm (4) M6 Nuts (4) Directional Vent Mounting Brackets (2)
M4x10mm (8) Self-Tapping Screw (4) Magnetic Door Panel (1) Exhaust Duct Extra Drainage Plug
Front Door Facing Installation
1
Attach the two brackets using the supplied
M4 x 10 mm screws.
2
With the unit facing forward, place it on
top of a wall-mount rack. Align the bracket
holes with the mounting holes on top of
the wall-mount rack.
Note: Bracket holes will align with a Tripp Lite
rack. Other rack brands may require new holes
to be drilled into them.
3
Secure unit to wall-mount rack with the
supplied M6 x 16 mm screws and M6
nuts.
Note: If mounting to a rack brand other than
Tripp Lite, user must supply the mounting
hardware.
1
1
2
2
3
5
Installation
Side Panel Facing Installation
1
Attach the two brackets using the supplied
M4 x 10 mm screws.
2
With the unit facing toward either side
panel, place it on top of a wall-mount
rack. Align the bracket holes with the
mounting holes on top of the wall-mount
rack.
Note: Bracket holes will align with a Tripp Lite
rack. Other rack brands may require new holes
to be drilled into them.
3
Secure unit to wall-mount rack with the
supplied M6 x 16 mm screws.
Note: If mounting to a rack brand other than
Tripp Lite, user must supply the mounting
hardware.
1
Ensure the front door to the wall-mount rack is closed.
2
Align the rectangular opening on the directional vent with the
opening on the front of the air conditioner. Push the directional
vent onto the unit. Magnets on the vent surface will hold the vent
onto the unit and wall-mount rack.
Note: Vent will remain attached to the wall-mount rack’s front door when
it’s opened.
Directional Vent Installation
Note: The illustrations below show a front door facing installation.
1
2
1
1
2
2
A
A
B
B
Self-Tapping Screw
Vertical
Window
Opening
Horizontal Window
Opening
Ceiling Panel
(From Below)
Ceiling Panel
(From Above)
Exhaust Panel
1 2
3
4
6
Installation
1
Connect the flexible exhaust duct
A
to the warm air exhaust vent
on the top panel of the unit
B
. Align the duct with the circular vent
opening, push the duct inward and turn the duct clockwise until it
screws into the exhaust vent solidly.
2
Connect the other end of the exhaust duct
A
to the exhaust duct
adapter
B
. Align the duct with the circular adapter opening, push
the duct inward and turn the duct clockwise until it screws into the
adapter solidly. If you plan to connect the exhaust duct to a drop
ceiling, proceed to the Drop Ceiling Exhaust Connection section.
If you plan to connect the exhaust duct to a window, proceed to
the Window Exhaust Connection section.
Exhaust Duct Connection (Optional)
Drop Ceiling Exhaust Connection
Warning: Some ceilings may require modified installation procedures. The user must determine the fitness of hardware and
procedures before installing. The procedures described in this manual may not be appropriate for all applications.
1
Choose a removable drop ceiling panel near the unit to provide
the straightest, shortest path available for the flexible exhaust
duct. Measure the width of the ceiling panel, including the portion
that rests on the ceiling grid. Combine the two sections of the
adjustable exhaust panel, then adjust the exhaust panel to match
the width of the ceiling panel. After the exhaust panel is set to
the correct width, use the included self-tapping screw to lock it in
place.
Note: The exhaust panel can adjust from 20.5 to 49.2 inches (52.1 to
104.1 cm). Certain installations may require trimming the exhaust panel for
a proper fit.
2
Insert the exhaust duct adapter into the oblong hole in the
adjustable exhaust panel. The adapter will snap into place.
4
Slide the ceiling panel back into place so that it adjoins the exhaust
panel and closes any gaps in the ceiling. A tight seal will permit
maximum cooling efficiency. If the installation is permanent, trim
the ceiling panel so it doesn’t overlap the ceiling grid.
Note: The flexible exhaust duct can extend to a maximum length of 118
inches (300 cm). Provide the straightest, shortest path available. Excessive
bending or stretching of the duct will reduce cooling efficiency.
3
Slide the ceiling panel out of the way and place the exhaust panel
inside the ceiling space. Allow the exhaust panel to rest on top of
the ceiling grid.
Note: There must be at least 10 inches (25.4 cm) of open space above the
exhaust panel to allow adequate airflow.
Self-Tapping Screw
Vertical
Window
Opening
Horizontal Window
Opening
1
Self-Tapping Screw
Vertical
Window
Opening
Horizontal Window
Opening
Self-Tapping Screw
Vertical
Window
Opening
Horizontal Window
Opening
2
3
TO EXTERNAL
DRAIN
1
2 & 3
7
Installation
Window Exhaust Connection
Warning: Some windows may require modified installation procedures. The user must determine the fitness of hardware and
procedures before installing. The procedures described in this manual may not be appropriate for all applications.
1
Measure the window opening. Combine
the two sections of the adjustable
exhaust panel, then adjust the exhaust
panel to match the width of the window
opening. After the exhaust panel is set to
the correct width, use the included self-
tapping screw to lock it in place.
Note: The exhaust panel can adjust from
20.5 to 49.2 inches (52.1 to 104.1 cm).
It is compatible with vertical and horizontal
mounting.
2
Insert the exhaust duct adapter into the
oblong hole in the adjustable exhaust
panel. The adapter will snap into place.
3
Insert the exhaust panel into the window
opening, then close the window against
the exhaust panel. A tight seal will permit
maximum cooling efficiency. Note: There
must be at least 10 inches (25.4 cm) of
open space behind the exhaust panel to
allow adequate airflow.
Note: The flexible exhaust duct can extend to
a maximum length of 118 inches (300 cm).
Provide the straightest, shortest path available.
Excessive bending or stretching of the duct will
reduce cooling efficiency.
Drainage Plug
Warning: The unit’s built-in re-evaporator will not function unless the drainage plug is installed in the drainage outlet.
The SRCOOL2KWM ships with the drainage plug pre-installed. When the unit cools or dehumidifies, condensation forms. The unit has a built-in
re-evaporator that allows it to expel condensation through the warm air exhaust stream. This feature allows the unit to operate indefinitely without
requiring you to empty a water collection tank.
1
Cooling Mode with Re-Evaporation
The drainage plug must remain installed to enable re-evaporation of condensation.
2
Cooling Mode without Re-Evaporation
To use Cooling mode without re-evaporating condensation, remove the drain plug and route
a user-supplied drain line to external drainage.
3
Dehumidify Mode
When using the unit in Dehumidify mode, you must remove the drain plug and route a user-
supplied drain line to external drainage. This is required because the water removed from
the air would otherwise be evaporated back into the room.
Note: If the drainage system becomes clogged, a small internal reservoir will collect condensation. If the
drainage system is not cleared before the internal reservoir fills, the unit will shut down automatically.
Warning: Before connecting the unit to a dedicated drainage system, turn it off and
unplug it. There is a risk of electric shock while the unit is plugged in.
1 2 3
8
Optional Accessories
Remote Cooling Management
Add remote cooling management to your SRCOOL2KWM with the optional SRCOOLNET2 module. It allows you to communicate with and control
the SRCOOL2KWM as a manageable device on your network and is accessible via Web Browser, Network Management Station or Telnet. With the
SRCOOLNET2 installed, you can:
• Change settings and monitor temperature and humidity from any location
• Receive alerts via e-mail, SMS or SNMP
• Access detailed condition and event logs
Learn more about the SRCOOLNET2 at www.tripplite.com.
Installation
Powering the SRCOOL2KWM
Plug the unit into an appropriate power source.
Low Temperature Operation
The SRCOOL2KWM is a high performance cooler, capable of producing very cold air output. When using the unit in environments that are
already cold (20° C / 68° F or less), Tripp Lite recommends using the Dehumidify Mode only. This will allow the unit to continue to provide the
supplemental cooling while preventing any evaporator icing issues caused by the low room temperature.
Magnetic Door Panel Installation (Optional)
1
Open the rack front door.
2
Cut the magnetic door panel to fit the
shape of the directional vent when it’s
attached to the wall-mount rack front
door.
3
Attach the magnetic door panel to the
inside of the rack front door.
9
Operation
Warning: Install the unit according to the instructions in the “Installation” section before attempting to operate it.
Power
Turn the unit on or off by pressing the “POWER” button.
The unit has a 3.5-minute compressor delay in order to prevent potential circuit overloads at
start up.
Automatic Restart Feature
The unit will turn on and resume operation automatically when power is restored after a power
outage. The unit will use the same settings that it used immediately before the power outage
occurred.
Note: If the power outage is brief, the unit will run the fan alone for 3.5-minutes before resuming normal
operation. The delay allows the compressor to depressurize so the unit will function properly when it enters
Cool mode.
Cool Mode
Pressing the “FUNCTION” button cycles between Cool mode and Dehumidify mode. The
“COOLING” LED remains illuminated when Cool mode is active.
Press the TEMP+ and TEMP- buttons to set the temperature in Cool mode. The selected
temperature is shown on the numeric display. Once set, the desired temperature will blink five
times, after which the display will show the current room temperature.
Press the “FAN SPEED” button to cycle between high, medium and low fan speeds. An LED
illuminates to indicate the selected fan speed. When speed is set on AUTO, the unit will
automatically select a fan speed based on the set and ambient temperatures. If ambient
temperature is lower than the set temperature, the fan will run and the “COOLING” LED will
blink to indicate that the compressor is off. When cooling resumes, the “COOLING” LED will
remain illuminated.
Dehumidify Mode
Pressing the “FUNCTION” button cycles between Cool mode and Dehumidify mode.
The “DEHUMIDIFY” LED illuminates when Dehumidify mode is active. In Dehumidify mode, the
fan runs at a fixed speed and temperature controls are disabled. For optimal performance in
Dehumidify mode, close windows and doors, remove the drain plug and route user-supplied
drain line to external drainage.
Timer
The “TIMER” button allows you to schedule the unit to turn on or off automatically.
Timer On (Note: The unit must be off to activate the Timer On function. Confirm that mode, temperature
and fan speed settings are correct before activating the Timer On function.)
Activate the timer by pressing the “TIMER” button. Pressing or holding down the “TIMER”
button allows you to set the “delayed on” time. The number of hours is shown on the numeric
display. The number will flash on the screen five times, then display the time remaining before
the unit will power on.
Timer Off (Note: The unit must be on to activate the Timer Off function.)
Activate the timer by pressing the “TIMER” button. Pressing or holding down the “TIMER”
button allows you to set the “delayed off” time. The number of hours is shown on the
numeric display. The number will flash on the screen five times before returning to the current
temperature.
Quiet Control Mode
The unit includes a Quiet Control Mode which regulates the cooling via the microprocessor to
achieve quieter operation levels when noise is an issue.
To activate Quiet Control Mode, first set the desired temperature. After the display LED stops
flashing, press the “QUIET” button. The Quiet LED will turn on. The set temperature will
automatically increase by 2° F / 1° C per hour for the next two consecutive hours for a total
gain of +4° F / +2° C after two hours, keeping the setting temperature constant from that
point on.
10
It is important to keep the air filters clean
and free of dust. When the filters are dirty
or clogged with dust, it decreases cooling
efficiency and can threaten air quality.
Tripp Lite recommends cleaning the filters at
least once every two weeks.
Before cleaning the filters, turn
the unit off and unplug it!
There is a risk of electric shock
while the unit is plugged in.
1. Turn the unit off and unplug it.
2. Remove the air filters.
3. Wash the filters with warm water and
a neutral detergent. Do not use harsh
detergents or chemicals. Allow the filters to
air dry completely after washing.
Note: Do not use water hotter than 104° F
(40° C) to clean the filters.
4. Replace the air filters.
5. Plug the unit in and resume normal
operation.
Operation
Maintenance
Periodic maintenance extends the unit’s lifespan and permits maximum operating efficiency.
Cleaning the Air Filters
Changing Degree Units
The unit can display temperatures in both Celsius and Fahrenheit. The default setting for the
SRCOOL2KWM is Fahrenheit.
To toggle between temperature modes, put the unit in standby mode. The air conditioner is in
standby mode when it is plugged into live AC power, but powered off. Then, press and hold the
“FUNCTION” key for 10 seconds. After 10 seconds, the display will flash the temperature in the
new degree units. Power the unit back on to resume operation.
Alarm
If the internal water tank becomes full, the unit will display the “E4” error code on its screen. To
resume normal function, turn the unit off, remove the drainage plug and drain the excess water
from the unit. Replace the plug and turn the unit on to begin cooling.
One possible cause of the “E4” error is an excessively humid operating environment. If the error
occurs regularly, you should check the humidity level of the operating environment. You may
need to add an external drain.
Cleaning the Cabinet
Before cleaning the cabinet, turn the unit off and unplug it!
There is a risk of electric shock while the unit is plugged in.
1. Turn the unit off and unplug it.
2. Wipe the unit with a dry, non-abrasive cloth. Do not use gasoline, benzene, thinners or other harsh chemicals that may damage the surface.
Do not pour water directly over the unit or into the working parts. This causes a risk of electrical shock and deterioration of electrical
components and wiring insulation.
3. In extreme cases, wipe the unit with a damp cloth to remove residue.
Moving the SRCOOL2KWM
1. Turn the unit off and unplug it.
2. Remove the drainage plug and drain any excess water from the unit.
3. Replace the plug.
4. Move the unit to the desired location.
11
Additional Display Codes
Troubleshooting
Review the possible solutions below. If the problem persists, please visit www.tripplite.com/support for service.
Problem Possible Cause Possible Solution
The unit does not function. The unit is turned off.
Turn the unit on. (See Operation section.)
The unit is not plugged in. Plug the unit into a suitable outlet.
Main power is off. Check fuses or circuit breaker.
Cooling performance is unsatisfactory. The air exhaust or intake is blocked. Confirm that all ducts and intakes are clear of obstructions.
The temperature setting is too high. Adjust the temperature setting.
The fan speed setting is too low. Adjust the fan setting.
The air filter is dirty. Clean the air filter.
The wattage of the rack enclosure, the size of
the room or the ambient temperature exceeds
the cooling capacity of a single unit.
Contact Tripp Lite for additional cooling solutions suitable for your application.
The unit leaks water. The drainage plug is not installed.
Insert the drainage plug in the drainage outlet. (See Installation section.)
The unit has ice or frost buildup. The unit is operating in an environment that is
too cool or has excess humidity.
OPTION 1: Turn off the unit, and let the unit defrost. Once defrosted, ensure the unit
is operating with the fan speed set on HIGH.
OPTION 2: Turn off the unit, and let the unit defrost. Once defrosted, operate the unit
in DEHUMIDIFY MODE, or increase the desired temperature setpoint.
Display Code Description
df Unit is in Defrost Mode
Lo Ambient Air Temp. Sensor Error
(Too Low)
Hi Ambient Air Temp. Sensor Error
(Too High)
E1 Indoor Temperature Sensor Error
E2 Internal Temperature Sensor Error
E4 Water Full Error
E5 Evaporator Fan Error
E6 Condenser Fan Error
Defrost Mode
If the “df” code appears, it means the unit detected an icing problem and has started a defrost
cycle. The compressor will stop and the upper motor will continue to run at high speed for
3.5 minutes.
If the icing problem clears up, the unit will return to normal operation. If the code returns,
check the humidity and temperature of the operating environment. An environment that is too
cool or has excessive humidity can cause icing problems. If the operating environment is normal
and you are still getting the “df” code, contact Tripp Lite for further instructions.
Error Codes
The Tripp Lite SRCOOL2KWM has the ability to continually monitor itself. Should an error occur,
the display will show one of 7 error codes to the left:
Code E4 can be cleared by emptying the water tank. Consult the Alarm entry in the Operation
section for details.
To clear codes Lo, Hi, E1, E2, E5 and E6, follow these steps:
1. Power cycle the unit by unplugging it from the source for 5 minutes.
2. Plug the unit back in.
3. Restart the unit.
If the code remains clear, continue to operate the unit as normal. If the code returns, please
contact Tripp Lite for further instructions.
12
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
1-YEAR LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 1 year from the
date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service
under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL
60609 USA. Seller will pay return shipping charges.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES
OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL
WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES
ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have
other rights which vary from jurisdiction to jurisdiction).
WARNING: The individual user should determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to
great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of this device for any specific application.
PRODUCT REGISTRATION
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You’ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. Open to U.S. residents only. See www.tripplite.com for details.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found
on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series
number. The series number should not be confused with the marketing name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment
from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Tripp Lite has a policy of continuous improvement. Product specifications are subject to change without notice.
Warranty and Product Registration
Storage and Service
Storage
Before storing the unit, confirm that the ducts and vents are secured or removed and cared for properly. Also confirm that the unit is drained of
condensation.
Service
Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs are also
available from Tripp Lite. For more information on service, visit www.tripplite.com/support. Before returning your product for service, follow these
steps:
1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading of the
instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Request Return (RMA) link. From here you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial numbers,
along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you. Any damages (direct,
indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered
under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the
RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your sales receipt. Return the
product for service using an insured carrier to the address given to you when you request the RMA.
13
Unidad de Aire Acondicionado para
Gabinetes Instalados en la Pared
SRCOOL2KWM (120V, 60 Hz)
Manual del Propietario
Introducción 14
Instruccione de Seguridad 14
Importantes
Características 15
Accesorios 16
Instalación 16
Accesorios Opcionales 20
Operación 21
Mantenimiento 22
Solución de Problemas 23
Almacenamiento y Servicio 24
Garantía 24
English 1
Français 25
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • www.tripplite.com/support
Copyright © 2017 Tripp Lite.
14
Introducción
La unidad autónoma de Aire Acondicionado para Gabinetes Instalados en la Pared proporciona 2,000 BTU de capacidad de enfriamiento.
Diseñada para entornos de TI, es ideal para enfriar gabinetes instalados en la pared y gabinetes de cableado de redes sobrecalentados
sin acceso al aire acondicionado de las instalaciones. Además filtra y deshumidifica el aire para mejorar las condiciones de operación y
confiabilidad del equipo. La condensación es re-evaporada para una operación libre de goteos, de modo que usted no gaste tiempo vaciando
tanques recolectores de agua. El diseño autónomo no requiere de plomería o circuitos eléctricos, de modo que el arranque es rápido y fácil. El
refrigerante R134A amigable con el ambiente cumple con los estándares ambientales.
Aplicaciones Recomendadas:
Instrucciones de Seguridad Importantes
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante la instalación, operación y
almacenamiento de este producto. La omisión en la observancia de estas advertencias puede afectar su garantía.
Advertencias
Antes de usarlo, cada usuario debe determinar si este dispositivo es adecuado o seguro para el uso previsto. Ya que las aplicaciones individuales
están sujetas a gran variación, el fabricante no garantiza la adecuación de este dispositivo para alguna aplicación específica.
Instale la unidad en interiores, alejada de temperaturas o humedad extremas, luz solar y contaminantes conductores.
Conecte la unidad directamente a un tomacorriente de CA conectado a tierra. La omisión puede causar una descarga eléctrica o un incendio.
La fuente de energía que alimente la unidad debe estar especificada de acuerdo con la placa de identificación de la unidad.
No modifique la clavija ni use un adaptador que pueda eliminar la conexión a tierra.
No use un cable de extensión para conectar la unidad a un tomacorriente de CA. Use solamente el cable de alimentación que viene con la unidad.
Cumpla con todos los reglamentos de cableado y seguridad aplicables, como el Código Eléctrico Nacional (NEC) en los Estados Unidos.
No enchufe equipo adicional en el tomacorriente en que se conecte la unidad. La sobrecarga del tomacorriente puede causar una descarga
eléctrica o incendio.
No intente encender o apagar la unidad conectando y desconectando la clavija de CA. Puede causar una descarga eléctrica severa. Use el botón
ON/OFF para encender o apagar la unidad.
Apague la unidad y desconéctela del tomacorrientes de CA antes de llevar a cabo el mantenimiento.
Antes de conectar la unidad a un sistema de drenaje dedicado, apáguela y desconéctela. Existe un riesgo de descarga eléctrica cuando la unidad
está enchufada.
El mantenimiento lo debe realizar sólo personal capacitado.
No use solventes, alcohol, detergentes, o cepillos abrasivos para limpiar el gabinete de la unidad. Estos artículos pueden dañar el gabinete.
No vierta agua sobre la unidad. Puede causar una descarga eléctrica y dañar la unidad.
No opere la unidad sin el filtro de aire. Esto puede causar acumulación de polvo que puede dañar la unidad.
No intente operar la unidad en un cuarto con circulación de aire inadecuada. Si no ventila adecuadamente el calor la unidad puede funcionar mal.
No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda razonablemente causar la falla
del equipo de soporte de vida o afectar significativamente su seguridad o efectividad.
Enfriamiento de un gabinete instalado en la pared sobrecalentado.
A
IH
GF
C
E
A
B
B
B
D
C
I
J
K
D
E
G
H
F
15
Características
Vista Frontal
A
Filtro de Aire
B
Panel Frontal
C
Ventila Direccional
D
Salida de Aire Frío
E
Panel de Control
F
Ranura para SRCOOLNET2
G
Descarga de Aire
Caliente
H
Adaptadores para
Conducto
Vista Posterior
I
Cable de alimentación
de CA
J
Filtro de Aire
K
Salida del Drenaje
Panel de Control
A
Pantalla Numérica
B
LEDs de Modo de Operación
C
Botones de Control de
Temperatura
D
LEDs de Modo de Velocidad
del Ventilador
E
Botón “FAN SPEED”
[Velocidad del ventilador]
F
Botón “QUIET” [Silencio]
G
Botón “TIMER” [Temporizador]
H
Botón “FUNCTION” [Función]
I
Botón "POWER" [Encendido]
1
2 3
16
Accesorios
Instalación
Advertencia: después de retirar la unidad del contenedor de embarque, revise para detectar daños o partes faltantes (Consulte la lista
de partes siguiente). Si nota algún problema, visite www.tripplite.com/support para servicio. No intente operar una unidad dañada.
Lista de Partes:
Los procedimientos descritos en esta sección son para gabinetes para instalación en la pared y pueden no ser apropiados para todas las
aplicaciones. Antes de la instalación, el usuario debe determinar la adecuación de los accesorios y procedimientos. Si los accesorios y
procedimientos no son adecuados para su aplicación, póngase en contacto con Tripp Lite para solicitar apoyo.
Notas para Instalación
El SRCOOL2KWM es ideal para gabinetes con puertas perforadas (no es para uso en gabinetes con puertas sólidas / vidrio acrílico / vidrio).
Si el sistema de enfriamiento de su edificio tiene configuraciones de termostato nocturnas o de fin de semana, tiene apagados periódicos
o capacidad de enfriamiento limitada, usted puede necesitar considerar alternativas a la instalación estándar. Este producto está pensado
para usarse como un dispositivo complementario de enfriamiento y no puede corregir fluctuaciones significativas de la humedad o
temperatura del edificio.
Panel de Escape
Ajustable (2 Secciones)
Adaptador para
Conducto de Escape
M6x16 mm (4) Tuercas M6 (4) Ventila Direccional Soportes de montaje (2)
M4x10 mm (8) Tornillo Autorroscante (4) Panel Magnético de Puerta (1) Conducto de Escape Tapón del Drenaje Adicional
Instalación Hacia Puerta Delantera
1
Coloque los dos soportes usando los
tornillos M4 x 10 mm suministrados.
2
Con la unidad apuntando al frente,
colóquelo sobre la parte superior de un
rack para instalación en pared. Alinee los
orificios del soporte con los orificios de
instalación en la parte superior del rack
para instalación en pared.
Nota: Los orificios del soporte se alinearán
con un rack de Tripp Lite. Otras marcas de rack
pueden requerir perforar nuevos orificios en
ellos.
3
Fije la unidad al rack para instalación
en pared con los tornillos M6 x 16 mm
suministrados y tuercas de M6.
Nota: Si se instala a una marca de rack que no
sea Tripp Lite, el usuario debe suministrar los
accesorios de instalación.
1
1
2
2
3
17
Instalación
Instalación Hacia el Panel Lateral
1
Coloque los dos soportes usando los
tornillos M4 x 10 mm suministrados.
2
Con la unidad hacia cualquier panel
lateral, colóquelo sobre la parte superior
de un rack para instalación en pared.
Alinee los orificios del soporte con los
orificios de instalación en la parte superior
del rack para instalación en pared.
Nota: Los orificios del soporte se alinearán
con un rack de Tripp Lite. Otras marcas de rack
pueden requerir perforar nuevos orificios en
ellos.
3
Fije la unidad al rack para instalación
en pared con los tornillos M6 x 16 mm
suministrados.
Nota: Si se instala a una marca de rack que no
sea Tripp Lite, el usuario debe suministrar los
accesorios de instalación.
1
Asegure que esté cerrada la puerta al rack para instalación en
pared.
2
Alinee la abertura rectangular de la rejilla de ventilación direccional
con la abertura en la parte frontal del aire acondicionado. Empuje
la ventila direccional en la unidad. Los imanes en la superficie
de la ventila sostendrán la ventila en la unidad y en el rack para
instalación en pared.
Nota: La ventila permanecerá fija en la puerta frontal del rack para
instalación en pared cuando ésta se abra.
Instalación de la Ventila Direccional
Nota: Las ilustraciones de abajo muestran una instalación hacia la puerta frontal.
1
2
1
1
2
2
A
A
B
B
Tornillo Autoroscante
Abertura
Vertical de
Ventana
Abertura Horizontal
de Ventana
Panel de Techo
(Desde Abajo)
Panel de Techo
(Desde Arriba)
Panel de Escape
1 2
3
4
18
Instalación
1
Conecte el conducto de escape flexible
A
a la ventila de salida
del aire caliente en el panel superior de la unidad
B
. Alinee el
conducto con la abertura circular de la ventila, empuje el conducto
hacia adentro y gire el conducto en sentido de las manecillas del
reloj hasta que se atornille sólidamente en la ventila de escape.
2
Conecte el otro extremo del conducto de escape
A
al adaptador
del conducto de escape
B
. Alinee el conducto con la abertura
circular del adaptador, empuje el conducto hacia adentro y gire el
conducto en sentido de las manecillas del reloj hasta que se atornillo
sólidamente en el adaptador. Si va a conectarse el conducto de
escape a un techo falso, diríjase a la sección Conexión del Escape
en Techo Falso. Si va a conectarse el conducto de escape a una
ventana, diríjase a la sección Conexión del Escape en la Ventana.
Conexión del Conducto de Escape (Opcional)
Conexión del Escape en Techo Falso
Advertencia: es posible que para algunos techos se requieran otros procedimientos de instalación. Antes de la instalación, el usuario debe
determinar que los accesorios y procedimientos sean los adecuados. Es posible que los procedimientos descritos en este manual no sean
adecuados para todas las aplicaciones.
1
Elija un panel de techo falso removible cerca de la unidad para
que el tendido del conducto flexible de escape sea lo más corto
y directo posible. Mida el ancho del panel del techo, incluyendo
la porción que descansa en la rejilla de techo. Combine las dos
secciones del panel de escape ajustable, a continuación, ajuste
el panel de escape para que coincida con el ancho del panel de
techo. Después que el panel de escape se ajuste al ancho correcto,
use el tornillo autorroscante incluido para asegurarlo en su sitio.
Nota: el panel de descarga se puede ajustar entre 52.1 y 125 cm [20.5" y
49.2"]. Algunas instalaciones pueden requerir recortar el panel de escape
para un ajuste apropiado.
2
Inserte el adaptador del conducto de escape en el orificio alargado
en el panel de escape. El adaptador encajará en su lugar.
4
Deslice el panel de techo en su lugar de modo que quede junto al
panel de escape y cierre cualquier hueco en el techo. Un sellado
hermético garantizará una refrigeración altamente eficiente. Si la
instalación es definitiva, recorte el panel del techo para que no se
superponga sobre la rejilla.
Nota: El conducto de escape flexible se puede extender hasta una longitud
máxima de 300 cm [118"]. Busque el tendido más corto y directo posible.
Excesiva flexión o estiramiento del conducto reducirá la eficiencia de
enfriamiento.
3
Deslice el panel de techo fuera de su lugar y coloque el panel
de descarga en ese espacio del techo. Permita que el panel de
descarga se apoye encima de la rejilla del techo.
Nota: Debe haber al menos 25.4 cm [10"] de espacio libre por encima del
panel de descarga para permitir una circulación de aire adecuada.
Tornillo Autoroscante
Abertura
Vertical de
Ventana
Abertura Horizontal
de Ventana
1
Tornillo Autoroscante
Abertura
Vertical de
Ventana
Abertura Horizontal
de Ventana
Tornillo Autoroscante
Abertura
Vertical de
Ventana
Abertura Horizontal
de Ventana
2
3
AL DRENAJE
EXTERNO
1
2 y 3
19
Instalación
Conexión del Escape en la Ventana
Advertencia: es posible que para algunas ventanas se requieran otros procedimientos de instalación. Antes de la instalación, el usuario debe
determinar que los accesorios y procedimientos sean los adecuados. Es posible que los procedimientos descritos en este manual no sean
adecuados para todas las aplicaciones.
1
Mida la abertura de la ventana. Combine
las dos secciones del panel de escape
ajustable, a continuación, ajuste el panel
de escape para que coincida con el ancho
de la abertura de la ventana. Después
que el panel de escape se ajuste al ancho
correcto, use el tornillo autorroscante
incluido para asegurarlo en su sitio.
Nota: el panel de descarga se puede ajustar
entre 52.1 y 125 cm [20.5" y 49.2"]. Es
compatible con instalación vertical y horizontal.
2
Inserte el adaptador del conducto de
escape en el orificio alargado en el panel
de escape. El adaptador encajará en su
lugar.
3
Inserte el panel de escape de la abertura
de la ventana, a continuación, cierre
la ventana contra el panel de escape.
Un sellado hermético garantizará una
refrigeración altamente eficiente. Nota:
Debe quedar al menos 25.4 cm [10"]
de espacio libre por detrás del panel de
descarga para permitir una circulación de
aire adecuada.
Nota: El conducto flexible de escape se puede
extender hasta una longitud máxima de 300 cm
[118"]. Busque el tendido más corto y directo
posible. Excesiva flexión o estiramiento del
conducto reducirá la eficiencia de enfriamiento.
Tapón del Drenaje
Advertencia: El evaporador incorporado en la unidad no funcionará a menos que el tapón del drenaje esté instalado en la salida del
drenaje.
El SRCOOL2KWM se embarca con el tapón del drenaje preinstalado. Cuando la unidad enfría o deshidrata, se forma condensación. La
unidad tiene un re-evaporador integrado que le permite expulsar la condensación a través de la corriente de descarga de aire caliente. Esta
característica permite a la unidad operar en forma indefinida sin necesidad de vaciar un tanque recolector de agua,
1
Modo de Enfriamiento con Re-Evaporación
El tapón del drenaje debe permanecer instalado para permitir la re-evaporación de la
condensación.
2
Modo de Enfriamiento sin Re-Evaporación
Para usar el modo de enfriamiento sin re-evaporar la condensación, retire el tapón del
drenaje y conduzca una tubería de drenaje suministrada por el usuario al drenaje externo.
3
Modo de Deshumidificado
Cuando se use la unidad en modo de Deshumidificado, debe retirar el tapón del drenaje
y conducir una tubería de drenaje suministrada por el usuario al drenaje externo. Esto es
necesario porque el agua retirada del aire de lo contrario será evaporada nuevamente en el
cuarto.
Nota: Si el sistema de drenaje se obstruye, un pequeño recipiente interno recolectará la condensación.
Si el sistema de drenaje no es despejado antes que se llene el recipiente interno, la unidad se apagará
automáticamente.
Advertencia: Antes de conectar la unidad a un sistema de drenaje dedicado, apáguela y
desconéctela. Existe un riesgo de descarga eléctrica cuando la unidad está enchufada.
1 2 3
20
Accesorios Opcionales
Administración Remota del Enfriamiento
Agregue administración remota de enfriamiento a su SRCOOL2KWM con el módulo opcional SRCOOLNET2. Permite comunicarse con
el SRCOOL2KWM y controlarlo como un dispositivo administrable en su red y es accesible mediante navegador de Internet, Estación de
Administración de Red o Telnet. Con el SRCOOLNET2 instalado, usted puede:
• Cambiar parámetros y monitorear la temperatura y humedad desde cualquier ubicación
• Recibir alertas a través de correo electrónico, SMS o SNMP
• Acceder a registros detallados de condición y eventos
Conozca más acerca del SRCOOLNET2 en www.tripplite.com.
Instalación
Encendido del SRCOOL2KWM
Enchufe la unidad en una fuente de alimentación apropiada.
Operación a Baja Temperatura
El SRCOOL2KWM es un enfriador de alto rendimiento, capaz de producir una salida de aire muy frío. Al usar la unidad en ambientes que ya
están fríos (20 °C [68 °F] o menos), Tripp Lite recomienda usar solamente el modo de deshumidificado. Esto permitirá a la unidad continuar
proporcionando enfriamiento suplementario mientras evita cualquier problema de formación de hielo del evaporador causado por la baja
temperatura de la sala.
Instalación del Panel Magnético de la Puerta (Opcional)
1
Abra la puerta delantera del rack.
2
Corte el panel magnético de la puerta
para que ajuste a la forma de la ventila
direccional cuando se fije a la puerta
frontal del rack para instalación en pared.
3
Coloque el panel magnético de la puerta
en el interior de la puerta delantera del
rack.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Tripp Lite SRCOOL2KWM Le manuel du propriétaire

Catégorie
Climatiseurs split-system
Taper
Le manuel du propriétaire