Tripp Lite SmartOnline SU1000RTXL2U Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur
Owner’s Manual
1111 W. 35th Street Chicago, IL 60609 USA
Customer Support: (773) 869-1234 • www.tripplite.com
Important Safety Instructions 2
Installation 3
Basic Operation 6
Battery Replacement 12
Storage and Service 14
SmartOnline
Rack/Tower Mount Online UPS Systems
Specifications 14
Español
Français 31
16
Copyright ©2002 Tripp Lite. All rights reserved. SmartOnline is a trademark of Tripp Lite.
Troubleshooting 10
PyccŞèé 46
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 1
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, conductive contaminants,
dust or direct sunlight.
For best performance, keep the indoor temperature between between 32º F and 104º F
(0º C and 40º C).
Leave adequate space around all sides of the UPS for proper ventilation.
UPS Connection Warnings
Connect your UPS directly to a properly grounded AC power outlet. Do not plug the
UPS into itself; this will damage the UPS.
Do not modify the UPS's plug, and do not use an adapter that would eliminate the UPS’s
ground connection.
Do not use extension cords to connect the UPS to an AC outlet. Your warranty will be
voided if anything other than Tripp Lite surge suppressors are used to connect your UPS
to an outlet.
If the UPS receives power from a motor-powered AC generator, the generator must
provide clean, filtered, computer-grade output.
Equipment Connection Warnings
Do not use Tripp Lite UPS Systems for life support applications in which a malfunction
or failure of a Tripp Lite UPS System could cause failure or significantly alter the
performance of a life-support device.
Do not connect surge suppressors or extension cords to the output of your UPS. This
might damage the UPS and will void the surge suppressor and UPS warranties.
Battery Warnings
Your UPS does not require routine maintenance. Do not open your UPS for any reason
except battery replacement. There are no user-serviceable parts inside.
Battery replacement must be performed by qualified service personnel. Because the
batteries present a risk of electrical shock and burn from high short-circuit current,
observe proper precautions. Unplug and turn off the UPS before performing battery
replacement. Use tools with insulated handles, and replace the existing batteries with the
same number and type of new batteries (Sealed Lead-Acid). Do not open the batteries.
Do not short or bridge the battery terminals with any object.
The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in
the USA only call 1-800-SAV-LEAD for recycling information. Do not dispose of the
batteries in a fire.
Only connect Tripp Lite battery packs of the appropriate type and correct voltage to the
external battery connector.
Do not connect or disconnect external batteries while the UPS is operating from battery.
Do not operate your UPS without batteries.
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these
warnings will void your warranty.
2
Important Safety Instructions
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 2
Rackmount
1) Loosen the wingnuts on each of the two UPS
Side Supports; adjust the length of the supports to
match the depth of your rack; tighten wingnuts.
2) Mount both UPS Side Supports in your rack on
the inside surfaces of the rack rails.
Note: Both support ledges should face inward. The side supports’
front and back holes are threaded and do not require nuts to
secure rack bolts.
3) Attach mounting ‘ears’ to the front end of the
UPS’s sides using the screws provided.
4) Lift UPS and slide it onto the UPS Side
Supports within your rack. Mount the UPS by
screwing rack bolts through the UPS mounting
‘ears’, through the rack rails and through the UPS
Side Supports.
Note: The side supports’ front holes are threaded and do not
require nuts to secure rack bolts.
Vertical Tower Mount
1) Cover the rackmount screw holes on the UPS’s
sides with supplied snap-in hole-cover caps.
2) Place the UPS upright in a flat, stable location
with its control panel on the high corner facing
forward. Position stabilizer feet 4 in. from each
end of the UPS.
Mounting
SU2200RTXL2U shown
SU2200RTXL2U shown
3
Installation
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 3
Connection and Start-Up
Plug your UPS’s line cord into an
electrical outlet.
If your model features a detachable line cord,
first plug the female end into your UPS’s AC
Input Receptacle.
Your UPS must be connected to a dedicated
circuit of sufficient amperage—check the
“Recommended Utility Amps” rating of your
model in the specifications. Note, however, that
the select models may be fitted with different
plug types. Refer to the “OP Rating/Plug
Rating” chart printed on the top of your UPS.
Once your UPS is plugged in, the fan and all
Indicator Lights will turn ON. The “LINE” and
“LOAD ACTIVE METER” LEDs will
illuminate and the UPS will emit a beep to
indicate normal operation. However, power is
not supplied to your UPS’s AC outlets until the
UPS is turned on.
Plug your equipment into your UPS.
Your UPS is designed to support computer
equipment only. You will overload your UPS if
you connect household appliances or laser
printers to the UPS's outlets.
Turn your UPS ON:
Press the “ON/TEST” Switch
Hold it for several seconds until you
hear a beep
Release it
Your UPS will begin providing AC power to its outlets.
The “ON LINE” LED will illuminate.
SU2200RTXL2U Plug
(NEMA 5-20) shown
1
1
2
3
2
3
SU2200RTXL2U shown
4
Installation
(continued)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 4
Optional Connections
Your UPS will function properly without these connections.
Serial Port Connection
Using the serial cable provided, connect a serial
port on your computer to the serial port of your
UPS. See Communications in the Basic
Operation section of this manual to determine
how to monitor and manage your UPS using
this port.
External Battery Pack Connection
Check to ensure that the external batteries you
are connecting match the voltage listed on
your UPS’s battery connector. Plug either end
of the battery connection cable (supplied with
the battery pack) into the UPS’s External
Battery Connector and the other end into the
Battery Output Connector on the rear panel of
the external battery pack.
Since your UPS has internal batteries, external
batteries are only needed to extend runtime.
Adding external batteries will increase
recharge time as well as runtime. Make sure
that each end of the cable is fully inserted into
its connector. Several small sparks may result
during battery connection; this is normal.
1
2
48V/26A
1
2
SU2200RTXL2U shown
SU2200RTXL2U shown
5
Installation
(continued)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 5
Front Panel Switches
“ON/TEST” Switch: This switch controls four separate UPS functions:
UPS Power ON
To turn the UPS on, press this switch, hold it for several seconds until
you hear a beep, then release it. The “ON LINE” LED will illuminate.
UPS Self-Test
During normal on-line operation, press this switch and hold it until
you hear a beep. This initiates a 10-second self-test of the battery. The
UPS will shift to battery power (the “ON BATT” and “BATT
ACTIVE METER” LEDs will illuminate) for ten seconds.
Alarm Silence
To silence the UPS “on-battery” alarm, press this switch and hold it
until you hear a beep.
UPS Cold Start
To use your UPS as a stand-alone power source when AC power is
unavailable (i.e. during a blackout), press this switch and hold it until
you hear a beep. The UPS will then provide battery power to its outlets.*
* The “ON BATT” Indicator Light will be illuminated since your UPS will be operating
from battery power.
“OFF” Switch: This switch turns power OFF at the UPS receptacles.
Press this switch, hold it until you hear a beep, then release it. The
UPS will continue charging and the fan will continue to cool internal
components even after you turn the UPS receptacles off. To turn the
UPS OFF completely, including the charger, disconnect the UPS’s
power cord after pressing the “OFF” switch.
“ON LINE” LED: This green light will illuminate constantly to indicate
the UPS is performing normal on-line operation (filtering and
resynthesizing incoming AC line voltage to provide pure sine wave
output). When this light is illuminated, you can monitor the load level
of your UPS on the “LOAD ACTIVE METER” LEDs.
“LINE” LED: This green light will illuminate constantly to indicate
the utility supplied AC line voltage at your wall outlet is nominal. It
will flash if the line voltage is outside the nominal range (either too
low or two high). No action is required on your part when the LED
flashes; the UPS continuously and automatically filters AC line
power to provide your equipment with pure sine wave AC power,
regardless of brownout or overvoltage conditions. If this light is off,
then AC line voltage is not present (blackout) or is at an extremely
high voltage, and the UPS will provide connected equipment with
power from battery.
Front Panel Indicator Lights
6
Basic Operation
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 6
Front Panel Indicator Lights
continued
“BYPASS” LED: This yellow light will illuminate to indicate that
the UPS’s DC/AC inverter is deactivated and the UPS is in the
“Bypass” mode. During normal operation this LED will light briefly
when the unit is plugged in, but if an internal fault or overload occurs
this light will illuminate constantly to show that connected equipment
will receive filtered AC mains power, but will not receive battery
power during a blackout. In this case, contact Tripp Lite for service.
“FAULT” LED: This red light will flash when your UPS detects an
internal fault (overheating, overvoltages, etc.) or when it detects a
wiring fault in your wall outlet (reversed phases, missing ground, etc.)
The UPS will only detect wiring faults when it is plugged into a utility
outlet but not turned ON. If the light persists after restarting the UPS,
contact an electrician to check the AC line. Your UPS will identify the
presence of most (but not all) wiring faults.
“LOAD ACTIVE METER” LED: This green light will illuminate
when your UPS is receiving AC power to indicate that the set of four
dual-function LEDs is displaying the load level of your UPS.
“BATT ACTIVE METER” LED: This green light will illuminate
when your UPS is operating from battery power to indicate that the
set of four dual-function LEDs is displaying the battery charge level
of your UPS. Note: the “ON BATT” LED will also be illuminated.
“OVERLOAD” LED: This red light will illuminate constantly to indicate
that your UPS’s capacity has been exceeded while it is in on-line operation.
The UPS alarm will beep continuously. Immediately remove overload
until light and alarm goes off. If you do not immediately remove the
overload, the UPS will transfer from on-line to bypass operation.
“BATT LOW” LED: This yellow light will illuminate when your UPS’s
battery charge level is low. The UPS alarm will beep until either the
battery charge is depleted or the batteries are adequately recharged.
“ON BATT” LED: This green light will illuminate constantly to
indicate that AC line voltage is not present and your UPS is providing
your equipment with battery power. The UPS will also beep every two
seconds, unless silenced by the “ON/TEST” Switch. When this light
is illuminated, you can monitor the battery charge level of your UPS
on the “BATT ACTIVE METER” LEDs.
7
Basic Operation
(continued)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 7
Rear Panel
“REPLACE BATT” LED: This red light will illuminate constantly
and the UPS alarm will sound three beeps* if your UPS’s
microprocessor detects a battery fault or if your UPS fails the
automatic self-test (after you turn your UPS ON) and the UPS battery
is less than fully charged. Let the UPS system charge for at least 12
hours and perform a self test using the "ON/Test Switch" as described on
page 6. If the light continues to stay on, contact Tripp Lite for service.
*After the initial alarm, the UPS will beep once every hour until the problem is corrected.
Accessory Slot: Remove the small cover panel from this slot to use
optional accessories to remotely monitor and control your UPS.
Contact Tripp Lite Customer Support at (773) 869-1234 for more
information, including a list of available SNMP, network management
and connectivity products.
External Battery Pack Connector: Use to connect optional Tripp Lite
Battery Packs for additional runtime. Contact Tripp Lite Customer
Support at (773) 869-1234 for the appropriate Tripp Lite battery pack
to connect. Refer to instructions available with the Battery Pack for
complete connection information and safety warnings.
Fan: The fan cools the UPS’s internal components. It is always on
when line power is present.
TVSS Cover Plate: Remove this plate to install optional modem/network
surge protection modules, available for purchase by special
arrangement with Tripp Lite.
Input Circuit Breaker Switch: This resettable breaker prevents high
input current from damaging the UPS or the attached load. If this
breaker trips, make sure your UPS is connected to AC power of the
proper voltage before resetting the circuit breaker by pushing the
breaker switch in.
Input Receptacle (Select Models Only): Connect one end of the
detachable line cord into this receptacle and the other into your wall outlet.
Front Panel Indicator Lights
continued
8
Basic Operation
(continued)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 8
Rear Panel
continued
Output Circuit Breakers Switches (Select Models Only): These
resettable circuit breakers protect your UPS from output overload. If
one or both breakers trip, remove some of the load on the circuit(s)
and allow the UPS to cool before pressing the breaker switch(es) in to
reset.
Input Cord (Select Models Only): This permanently attached power
cord connects your UPS to a power outlet.
AC Receptacles (Varied by Model): These 15-, 20- and 30-amp
receptacles provide your connected equipment with pure sine-wave
AC output from the AC line during normal operation and from battery
power during blackouts and severe brownouts. Power provided at
these outlets is filtered to protect connected equipment against
damaging surges and line noise. The receptacles are divided into
numbered load banks, as labelled on the unit. Using PowerAlert
software and cabling, load banks one and two may be individually
turned off and on from a remote location, allowing users to reset or
reboot connected equipment. See Serial Port Connection under
Optional Connections.
“SMART” DB9 Port: Your UPS’s DB9 port can be used to monitor
and control your UPS using either RS-232 or dry contact protocols. It
can also be used to connect an emergency power off (EPO) switch.
RS-232 communications are very complex, but are easy to
implement. The easiest way monitor and control the UPS using RS-
232 is to connect the UPS to a computer with a DB9 cable and install
Tripp Lite’s PowerAlert software on the connected computer.
Dry contact communications are simple, but some knowledge of
electronics is necessary to configure them. The DB9 port’s pin
assignments are shown in the diagram at the left. If the UPS battery is
low, the UPS sends a signal by bridging pin 1 and pin 5. If utility
power fails, the UPS sends a signal by bridging pin 8 and pin 5. To
shut the UPS down remotely, send a 5V to 12V signal on pin 3 (using
pin 5 as the (negative) ground) for at least 3.8 seconds.
You may connect your UPS to an EPO switch and a computer at once
using a Tripp Lite EPO cable (not included; order accessory #73-0901
from Tripp Lite). Follow the connection procedures included with the
EPO Cable.
NEMA 5-15R
NEMA 5-15/20R
Other outlet types not shown
Communications
9
Basic Operation
(continued)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 9
The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is
having operational difficulties.
Lights (On/Flashing) and Condition Solution
On: REPLACE BATT Let the UPS system charge for at least
Condition: Replace Battery 12 hours and perform a self test using
the "ON/Test Switch" as described on
page 6. If the light continues to stay on,
contact Tripp Lite for service.
On: BATT LOW, ON BATT Prepare for imminent UPS shutdown.
Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports.
Condition: On Bypass due to Overload
On: FAULT Remove the cause of the short circuit
Condition: Short Circuit from the UPS output.
Flashing: FAULT Check the utility line for wiring problems
Condition: Wiring Fault such as reversed line and neutral or a
missing ground.
On: FAULT, REPLACE BATT Restart the UPS. If the problem persists,
Condition: Battery Voltage too High contact Tripp Lite for repairs.
On: FAULT, REPLACE BATT, OVERLOAD Restart the UPS. If the problem persists,
Condition: EEPROM Error contact Tripp Lite for repairs.
On: FAULT, BYPASS, LINE, 100% Restart the UPS. If the problem persists,
Condition: On Bypass due to contact Tripp Lite for repairs.
High Output Voltage
On: FAULT, BYPASS, LINE, 75% Restart the UPS. If the problem persists,
Condition: On Bypass due to contact Tripp Lite for repairs.
Low Output Voltage
On: FAULT, BYPASS, LINE, 50% Restart the UPS. If the problem persists,
Condition: On Bypass due to High contact Tripp Lite for repairs.
Bus Voltage
On: FAULT, BYPASS, LINE, 25% Restart the UPS. If the problem persists,
Condition: On Bypass due to Low contact Tripp Lite for repairs.
Bus Voltage
Troubleshooting
10
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 10
Troubleshooting
(continued)
Lights (On/Flashing) and Condition Solution
On: FAULT, BYPASS, LINE, 100%, 75% Check the UPS to be sure that there is
Condition: On Bypass due to High adequate space for air to circulate near
Internal Temperature the vents and that the fan is working
properly. Restart the UPS.
Flashing: LINE This indicates that utility power is too high
Condition: Input Abnormal or low for the UPS to operate in BYPASS
mode, so if an inverter failure occurs,
the UPS will deliver no output.
On: FAULT, 100% Restart the UPS. If the problem persists,
Flashing: LINE, BYPASS contact Tripp Lite for repairs.
Condition: No Output due to High
Output Voltage and Abnormal Input
Flashing: LINE, BYPASS
Restart the UPS. If the problem persists,
On: FAULT, 75% contact Tripp Lite for repairs.
Condition: No Output due to Low
Output Voltage and Abnormal Input
Flashing: LINE, BYPASS Restart the UPS. If the problem persists,
On: FAULT, 50% contact Tripp Lite for repairs.
Condition: No Output due to High
Bus Voltage and Abnormal Input
Flashing: LINE, BYPASS Restart the UPS. If the problem persists,
On: FAULT, 25% contact Tripp Lite for repairs.
Condition: No Output due to Low
Bus Voltage and Abnormal Input
Flashing: LINE, BYPASS Check the UPS to be sure that there is
On: FAULT, 100%, 75% adequate space for air to circulate near
Condition: No Output due to High the vents and that the fan is working
Internal Temperature and Abnormal properly. Restart the UPS. If the problem
Input persists, contact Tripp Lite for repairs.
11
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 11
Under normal conditions, the original battery in your UPS will last several years. Contact Tripp Lite
for information about replacement batteries.
Battery replacement should be performed only by qualified service personnel. The batteries are
hot-swappable: it is not necessary to turn off or disconnect the UPS and its connected load to
replace the UPS’s batteries. However, when it is convenient to do so, service personnel may
simplify the replacement procedure by turning power off at the UPS outlets by pressing the
OFF switch to and disconnecting the UPS’s power cord from the wall outlet.
When replacing the batteries on a SU1000RTXL2U, SU1000RTXL2UHV or
SUINT1000RTXL2U, qualified service personnel should refer to “Battery Warnings” in the
Safety section and follow this procedure:
1) Place the UPS horizontal with the Control Panel on the right side.
2) Remove both snap-on cover panels (A).
3) Unscrew and remove rack handle plates (B) on either side of the UPS.
4) Disconnect the microprocessor circuit board plug (C) located on the right side of the UPS.
5) Disconnect battery connectors (D). Note: while batteries are disconnected, the UPS will
not provide battery backup in the event of a power outage.
6) Unscrew and remove the battery retaining bracket (E).
7) Grasp pull-tab and pull out sliding battery tray (F).
8) Make a detailed sketch of the batteries and the polarity, color and connection of all cables.
Disconnect used batteries and dispose of them properly. Connect replacement batteries in
exactly the way the original batteries were connected. Note: Small sparks arcing between
battery connectors during battery replacement are normal. Reassemble the UPS by reversing
steps 1-7. Note: you may not receive full runtime until your new batteries have fully charged.
SU1000RTXL2U shown
B
C
F
EA
D
12
Battery Replacement
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 12
Battery Replacement
(continued)
A
D
C
F
When replacing the batteries on a SU1500RTXL2U, SU1500RTXL2UHV, SUINT1500RTXL2U,
SU2200RTXL2U, SU2200RTXL2UHV, SUINT2200RTXL2U, SU3000RTXL2U,
SU3000RTXL2UHV or SUINT3000RTXL2U, qualified service personnel should refer to
“Battery Warnings” in the Safety section and follow this procedure:
1) Place the UPS horizontal with its control panel on the right side.
2) Remove the left snap-on cover panel (A).
3) Unscrew and remove the battery connector cover (B).
4) Disconnect battery connectors (C). Note: while batteries are disconnected, the UPS will
not provide battery backup in the event of a power outage.
5) Unscrew and remove the battery cover plate (D).
6) Unscrew and remove the battery retaining bracket (E).
7) Grasp pull-tab and pull out sliding battery tray (F).
8) Make a detailed sketch of the batteries and the polarity, color and connection of all cables.
Disconnect used batteries and dispose of them properly. Connect replacement batteries in
exactly the way the original batteries were connected. Note: Small sparks arcing between
battery connectors during battery replacement are normal. Reassemble the UPS by reversing
steps 1-7. Note: you may not receive full runtime until your new batteries have fully charged.
SU2200RTXL2U shown
E
B
13
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 13
Storage and Service
First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS outlets, then
disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery
drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS
batteries once every three months by plugging the UPS into a live AC outlet and letting the
UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period
of time, they may suffer permanent loss of capacity.
If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL
PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the
problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.
Storage
Service
Specifications
All Models: Input Frequency (50/60 Hz Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave);
Transfer Time: (0 ns.); Maximum Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with
Nonlinear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours).
Model SU1000RTXL2U SU1000RTXL2UHV SUINT1000RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 15A 8A 8A
Input Plug Type: 5-15P 6-15P IEC 320-C14
Recommended Utility Amps: 15A 15A 10A
Output Capacity (VA/Watts): 1000/800 1000/800 1000/800
Battery Runtime (Half Load/Full Load) Min.: 18/6 18/6 18/6
System Battery Voltage: 36 VDC 36 VDC 36 VDC
Approvals: UL, cUL, FCC, NOM UL, cUL, FCC, NOM CE
Model: SU1500RTXL2U SU1500RTXL2UHV SUINT1500RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 20A 10A 10A
Input Plug Type: 5-15P 6-20P IEC 320-C14
Recommended Utility Amps: 20 A 15 A 15 A
Output Capacity (VA/Watts): 1500/1200 1500/1200 1500/1200
Battery Runtime (Half Load/Full Load) Min.: 17/5 17/5 17/5
System Battery Voltage: 48 VDC 48 VDC 48 VDC
Approvals: UL, cUL, FCC, NOM UL,cUL, FCC, NOM CE
Model SU2200RTXL2U SU2200RTXL2UHV SUINT2200RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 30A 15A 15A
Input Plug Type: 5-20P 6-20P IEC 320-C20
Recommended Utility Amps: 20A 20A 20A
Output Capacity (VA/Watts): 2200/1600 2200/1600 2200/1600
Battery Runtime (Half Load/Full Load) Min.: 18/6 18/6 18/6
System Battery Voltage: 48 VDC 48 VDC 48 VDC
Approvals: UL, cUL, FCC, NOM UL, cUL, FCC, NOM CE
14
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 14
Specifications
(continued)
Model SU3000RTXL3U SU3000RTXL3UHV SUINT3000RTXL3U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 40A 25A 25A
Input Plug Type: L5-30P L6-20P IEC 320-C20
Recommended Utility Amps: 30A 20A 20A
Output Capacity (VA/Watts): 3000/2400 3000/2400 3000/2400
Battery Runtime (Half Load/Full Load) Min.: 14/6 14/6 14/6
System Battery Voltage: 72 VDC 72 VDC 72 VDC
Approvals: UL, cUL, FCC, NOM UL, cUL, FCC, NOM CE
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
FCC Specifications for Models with FCC Approval: This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules.These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense. The
user must use shielded cables and connectors with this product. Any changes or modifications to this product
not expressly approved by the party responsible for compliance could void the user’s authority to operate the
equipment.
15
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 15
Manual del usuario
1111 W. 35th Street Chicago, IL 60609 EE.UU.
Atención al cliente: (773) 869-1234 • www.tripplite.com
Importantes instrucciones de seguridad 17
Instalación 18
Operación básica 21
Reemplazo de la batería 27
Almacenamiento y servicio 29
SmartOnline
Sistemas UPS en línea con montaje en bastidor/torre
Especificaciones 29
English
Français 31
1
© 2002 Tripp Lite. Todos los derechos reservados. SmartOnline es una marca registrada de Tripp Lite.
Localización de fallas 25
PyccŞèé 46
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 16
17
Advertencias sobre la colocación del UPS
Instale el sistema UPS bajo techo, alejado del calor o la humedad excesivos, de los
contaminantes conductivos, del polvo o de la luz solar directa.
Para lograr el mejor rendimiento, mantenga la temperatura interior entre 0º C y 40º C
(32º F y 104º F).
Mantenga suficiente espacio alrededor del sistema UPS para permitir una ventilación
adecuada.
Advertencias sobre la conexión del UPS
Conecte su sistema UPS directamente a una toma de corriente de CA con una conexión a
tierra adecuada. No conecte el sistema UPS a sí mismo, ya que esto lo dañará.
No modifique los conectores del UPS y no utilice un adaptador que pueda eliminar la
conexión a tierra del sistema.
No utilice cables de extensión para conectar el UPS en la toma de corriente de CA. Si se
utiliza otro tipo de supresor de sobretensión que no sea Tripp Lite para conectar el UPS a
la toma de corriente, se anulará la garantía del sistema.
Si el sistema UPS recibe energía eléctrica por medio de un generador de CA accionado
por motor, éste deberá proporcionar una salida de corriente limpia y filtrada del tipo
utilizado para computadoras.
Advertencias sobre la conexión de equipos
No utilice los sistemas UPS de Tripp Lite en equipo para el soporte de la vida humana,
donde un fallo o mal funcionamiento podría causar anomalías o alterar
significativamente el rendimiento del dispositivo para el soporte de la vida humana.
No conecte supresores de sobretensión o cables de extensión a la salida del sistema UPS.
Esto podría dañar el UPS y anularía la garantía del supresor de sobretensiones y del UPS.
Advertencias sobre las baterías
El sistema UPS no requiere ningún mantenimiento rutinario. No abra el UPS por ningún
motivo, excepto para el reemplazo de las baterías. Esta unidad no contiene partes
internas que puedan ser reparadas por el usuario.
Sólo personal técnico debidamente capacitado puede realizar el reemplazo de las
baterías. Debido a los riesgos que presentan las baterías en relación con los choques
eléctricos y las quemaduras causadas por corriente elevada de corto circuito, el personal
técnico capacitado debe observar todas las precauciones pertinentes. Apague y
desenchufe el sistema UPS antes de reemplazar las baterías. Utilice herramientas con
asas aisladas y reemplace las baterías con el mismo número y tipo de baterías nuevas (de
plomo-ácido selladas). No abra las baterías. No permita que ningún objeto entre en
contacto con los terminales de las baterías.
Las baterías del sistema UPS son reciclables. Consulte el reglamento local para conocer
los requerimientos de desecho aplicables o en los EE.UU. solamente, llame al 1-800-SAV-LEAD
(1-800-728-5323) para recibir información sobre el reciclaje. No utilice fuego para
desechar las baterías.
Conecte únicamente paquetes de baterías Tripp Lite del tipo apropiado y del voltaje
correcto en el conector de baterías externas.
No conecte ni desconecte las baterías externas cuando el sistema UPS está operando con
baterías.
No haga funcionar su UPS sin baterías.
GUARDE ESTAS INSTRUCCIONES
Este manual contiene advertencias e instrucciones importantes que deben seguirse
durante la instalación, operación y almacenamiento de todos los sistemas UPS de Tripp Lite.
De no cumplirse estas advertencias, la garantía será anulada.
Importantes instrucciones de seguridad
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 17
Montaje en bastidor
1) Afloje las tuercas de mariposa en cada uno de
los dos soportes laterales del UPS; ajuste la
longitud de los soportes para que concuerden con
la profundidad del bastidor; apriete las tuercas de
mariposa.
2) Realice el montaje de ambos soportes laterales
del UPS en su bastidor en las superficies de los
rieles del bastidor.
Nota: Ambas salientes del soporte deberán dirigirse hacia
adentro. Los orificios frontal y posterior de los soportes
laterales tienen rosca y no requieren tuercas para asegurar
los pernos del bastidor.
3) Una las lengüetas de montaje al extremo
delantero de los lados del UPS con los tornillos
proporcionados.
4) Levante el UPS y deslícelo dentro del bastidor
sobre los soportes laterales del UPS. Monte el
sistema UPS atornillando los pernos del bastidor
a través de las lengüetas de montaje del UPS, a
través de los rieles y de los soportes laterales del UPS.
Nota: Los orificios frontales de los soportes laterales tienen rosca
y no requieren tuercas para asegurar los pernos del bastidor.
Montaje de torre vertical
1) Cubra los orificios para tornillos del montaje
en bastidor ubicados a los lados del UPS con las
tapas de inserción suministradas.
2) Coloque el UPS en posición vertical en un
lugar plano y firme con el panel de control de la
esquina superior colocado hacia adelante. La
posición de la zapata de equilibrio debe estar a
10.16 cm (4 pulg.) desde cada extremo del UPS.
Montaje
Se muestra SU2200RTXL2U
Se muestra SU2200RTXL2U
Instalación
18
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 18
19
Conexión y encendido
Conecte el cable del sistema UPS
a una toma de corriente eléctrica.
Si su modelo tiene un cable de sistema
desmontable, conecte primero el extremo hembra
en el receptáculo de entrada de CA del UPS.
Su UPS debe estar conectado a un circuito
dedicado con un amperaje suficiente—
compruebe la gama de “Amperios de servicio
recomendados” de su modelo en las
especificaciones. Sin embargo, observe que los
modelos seleccionados pueden equiparse con
diferentes tipos de enchufe. Consulte la tabla
“Operación nominal/Conexión nominal”
impresa en la parte superior de su UPS.
Una vez que su UPS está enchufado, se
encenderá la luz del ventilador y todas las
luces indicadoras. Los LED “LINE” (Línea) y
“LOAD ACTIVE METER” (Medidor activo de
carga) se encenderán y el UPS emitirá un sonido
que indica funcionamiento normal. Sin embargo,
no se suministra energía a las tomas de corriente
de CA de su UPS hasta que se éste encienda.
Enchufe su equipo al sistema UPS.
Su sistema UPS está diseñado para soportar
únicamente equipo informático. Usted lo
sobrecargará si conecta electrodomésticos o
impresoras láser a las tomas de corriente del UPS.
Encienda su sistema UPS (ON):
Presione el interruptor “ON/TEST”
(Encendido/Prueba).
Manténgalo presionado por varios segundos
hasta que escuche un sonido.
Suelte el interruptor.
Su sistema UPS empezará a suministrar energía CA a sus tomas
de corriente. Se iluminará el LED “ON LINE” (En línea).
Se muestra el enchufe
SU2200RTXL2U (NEMA 5-20)
1
1
2
3
2
3
Se muestra
SU2200RTXL2U
Instalación
(continuación)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 19
20
Conexiones opcionales
Este sistema UPS funcionará correctamente sin estas conexiones.
Conexión de puerto serial
Utilice el cable serial incluido, conecte un
puerto serial de su computadora al puerto serial
de su UPS. Vea la sección Comunicaciones en
operación básica de esta manual para
determinar cómo monitorear y administrar el
sistema UPS a través de este puerto.
Conexión del paquete de baterías
externas
Verifique que las baterías externas que desea
conectar tengan el mismo voltaje de la lista
que aparece en el conector para baterías del
UPS. Conecte cualquier extremo del cable de
conexión de batería (proporcionado con el
paquete de baterías) en el conector para
baterías externas del UPS y el otro extremo en
el conector de salida de la batería que se
encuentra en el panel posterior del paquete de
baterías externas.
Debido a que su UPS ya posee baterías
internas, las baterías externas son necesarias
sólo para prolongar el tiempo de
funcionamiento. Si agrega baterías externas
incrementará el tiempo de recarga así como el
tiempo de respaldo. Asegúrese de que cada
extremo del cable esté completamente
insertado en su conector. Es normal que se
produzcan pequeñas chispas durante la
conexión de las baterías.
1
2
48V/26A
1
2
Se muestra SU2200RTXL2U
Se muestra SU2200RTXL2U
Instalación
(continuación)
200608121 93-2609 SU Owner’s Manual.qxd 10/3/2006 3:32 PM Page 20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Tripp Lite SmartOnline SU1000RTXL2U Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur