Mitsubishi Electric GT23 Le manuel du propriétaire

Taper
Le manuel du propriétaire
GT23 General Description
Thank you for purchasing the GOT2000 Series.
© 2013 MITSUBISHI ELECTRIC CORPORATION
GT2310-VTBA
GT2308-VTBA
GT2310-VTBD
GT2308-VTBD
Prior to use, please read both this manual and the
detailed manual thoroughly to fully understand the
product.
MODEL GT23-U-GD-E
Model
code
1D7MI4
IB(NA)-0800503ENG-I(2102)MEE
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
SAFETY PRECAUTIONS
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant
manuals introduced in this manual carefully and pay full attention to
safety to handle the product correctly.
The precautions given in this manual are concerned with this prod-
uct.
In this manual, the safety precautions are ranked as "WARNING"
and "CAUTION".
Note that the CAUTION level may lead to a serious accident
according to the circumstances.
Always follow the instructions of both levels because they are import-
ant to personal safety.
Please save this manual to make it accessible when required and
always forward it to the end user.
[DESIGN PRECAUTIONS]
Indicates that incorrect handling may cause
hazardous conditions, resulting in death or
severe injury.
Indicates that incorrect handling may cause
hazardous conditions, resulting in medium or
slight personal injury or physical damage.
Some failures of the GOT, communication unit or cable may keep the outputs
on or off.
Some failures of a touch panel may cause malfunction of the input objects
such as a touch switch.
An external monitoring circuit should be provided to check for output signals
which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
Do not use the GOT as the warning device that may cause a serious
accident.
An independent and redundant hardware or mechanical interlock is required
to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect
output or malfunction.
The GOT backlight failure disables the operation on the touch switch(s).
When the GOT backlight has a failure, the POWER LED blinks (orange/blue)
and the display section dims. In such a case, the input by the touch switch(s)
is disabled.
The display section of the GOT is an analog-resistive type touch panel.
Do not touch two points or more simultaneously on the display section.
Doing so may cause a touch switch near the touched points to operate
unexpectedly, or may cause an accident due to an incorrect output or
malfunction.
When programs or parameters of the controller (such as a PLC) that is
monitored by the GOT are changed, be sure to reset the GOT, or turn on the
unit again after shutting off the power as soon as possible.
Not doing so can cause an accident due to false output or malfunction.
If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is
suspended and the GOT becomes inoperative.
A system where the GOT is used should be configured to perform any
significant operation to the system by using the switches of a device other
than the GOT on the assumption that a GOT communication fault will occur.
Not doing so can cause an accident due to false output or malfunction.
WARNING
CAUTION
WARNING
[DESIGN PRECAUTIONS]
[MOUNTING PRECAUTIONS]
[WIRING PRECAUTIONS]
To maintain the security (confidentiality, integrity, and availability) of the GOT
and the system against unauthorized access, DoS
*1
attacks, computer
viruses, and other cyberattacks from unreliable networks and devices via
network, take appropriate measures such as firewalls, virtual private
networks (VPNs), and antivirus solutions.
Mitsubishi Electric shall have no responsibility or liability for any problems
involving GOT trouble and system trouble by unauthorized access, DoS
attacks, computer viruses, and other cyberattacks.
*1 DoS: A denial-of-service (DoS) attack disrupts services by overloading
systems or exploiting vulnerabilities, resulting in a denial-of-service (DoS)
state.
Do not bundle the control and communication cables with main-circuit, power
or other wiring.
Run the above cables separately from such wiring and keep them a minimum
of 100mm apart.
Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or
driver.
Doing so can result in a damage or failure of the display section.
When the GOT is connected to the Ethernet network, the available IP
address is restricted according to the system configuration.
When a GOT2000 series model and a GOT1000 series model are on an
Ethernet network, do not set the IP address 192.168.0.18 for the GOTs and
the controllers on this network.
Doing so can cause IP address duplication at the GOT startup, adversely
affecting the communication of the device with the IP address 192.168.0.18.
The operation at the IP address duplication depends on the devices and the
system.
Turn on the controllers and the network devices to be ready for
communication before they communicate with the GOT.
Failure to do so can cause a communication error on the GOT.
When the GOT is subject to shock or vibration, or some colors appear on the
screen of the GOT, the screen of the GOT might flicker.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the GOT main unit to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Use the GOT in the environment that satisfies the general specifications
described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product
damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in
the specified torque range (0.36 N•m to 0.48 N•m) with a Phillips-head
screwdriver No.2.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the
damage of the screws or the GOT.
Remove the protective film of the GOT.
When the user continues using the GOT with the protective film, the film may
not be removed.
Operate and store the GOT in environments without direct sunlight, high
temperature, dust, humidity, and vibrations.
When using the GOT in the environment of oil or chemicals, use the
protective cover for oil.Failure to do so may cause failure or malfunction due
to the oil or chemical entering into the GOT.
Be sure to shut off all phases of the external power supply used by the
system before wiring.
Failure to do so may result in an electric shock, product damage or
malfunctions.
Make sure to ground the FG terminal and LG terminal of the GOT power
supply section to the protective ground conductors dedicated to the GOT with
a ground resistance of 100 Ω or less.
When tightening the terminal screws, use a Phillips-head screwdriver No.2.
Terminal screws which are not to be used must be tightened always at torque
0.5 N•m to 0.8 N•m.
Otherwise there will be a danger of short circuit against the solderless
terminals.
Use applicable solderless terminals and tighten them with the specified
torque.
If any solderless spade terminal is used, it may be disconnected
when the terminal screw comes loose, resulting in failure.
WARNING
CAUTION
WARNING
CAUTION
WARNING
CAUTION
[WIRING PRECAUTIONS]
[TEST OPERATION PRECAUTIONS]
[STARTUP/MAINTENANCE PRECAUTIONS]
Correctly wire the GOT power supply section after confirming the rated
voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
Tighten the terminal screws of the GOT power supply section in the specified
torque range (0.5 N•m to 0.8 N•m). Undertightening can cause a short circuit
or malfunction.Overtightening can cause a short circuit or malfunction due to
the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering
the GOT. Not doing so can cause a fire, failure or malfunction.
Plug the communication cable into the GOT interface or the connector of the
connected unit, and tighten the mounting screws and the terminal screws in
the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of
the screws or unit.
Before performing the test operations of the user creation monitor screen
(such as turning ON or OFF bit device, changing the word device current
value, changing the settings or current values of the timer or counter, and
changing the buffer memory current value), read through the manual
carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to
perform significant operation for the system.
False output or malfunction can cause an accident.
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Correctly connect the battery connector.
Do not charge, disassemble, heat, short-circuit, solder, or throw the battery
into the fire.
Doing so will cause the battery to produce heat, explode, or ignite, resulting in
injury and fire.
Before starting cleaning or terminal screw retightening, always switch off the
power externally in all phases.
Not switching the power off in all phases can cause a unit failure or
malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of
the screws or unit.
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull from
the cable portion.
Doing so can cause the unit or cable to be damaged or can cause a
malfunction due to a cable connection fault.
Do not drop the module or subject it to strong shock. A module damage may
result.
Do not drop or give an impact to the battery mounted to the unit.
Doing so may damage the battery, causing the battery fluid to leak inside the
battery.
If the battery is dropped or given an impact, dispose of it without using.
Before touching the unit, always touch grounded metals, etc. to discharge
static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
Use the battery manufactured by Mitsubishi Electric Corporation.
Use of other batteries may cause a risk of fire or explosion.
Dispose of used battery promptly.
Keep away from children.Do not disassemble and do not dispose of in fire.
Be sure to shut off all phases of the external power supply before replacing
the battery or using the dip switch of the terminating resistor.
Not doing so can cause the unit to fail or malfunction by static electricity.
CAUTION
WARNING
WARNING
CAUTION
[TOUCH PANEL PRECAUTIONS]
[PRECAUTIONS WHEN THE DATA STORAGE IS IN
USE]
[DISPOSAL PRECAUTIONS]
[TRANSPORTATION PRECAUTIONS]
For the analog-resistive film type touch panels, normally the adjustment is not
required.
However, the difference between a touched position and the object position
may occur as the period of use elapses.
When any difference between a touched position and the object position
occurs, execute the touch panel calibration.
When any difference between a touched position and the object position
occurs, other object may be activated.
This may cause an unexpected operation due to incorrect output or
malfunction.
If the SD card mounted on drive A of the GOT is removed while the GOT is
accessed, processing for the GOT might be interrupted about for 20
seconds.The GOT cannot be operated during this period. The functions that
run in the background including a screen updating, alarm, logging, scripts,
and others are also interrupted.Since this interruption makes an impact to the
system operation, it might cause failure.After checking the light off of SD card
access LED, remove the SD card.
If the data storage mounted on the GOT is removed while the GOT is
accessed, the data storage and files are damaged.To remove the data
storage from the GOT, check that the access to the data storage in SD card
access LED, the system signal, and others is not performed.
Turning off the GOT while it accesses the SD card results in damage to the
SD card and files.
When inserting a SD card into the GOT, make sure to close the SD card
cover. Failure to do so causes the data not to be read or written.
When removing the SD card from the GOT, make sure to support the SD card
by hand as it may pop out.Failure to do so may cause the SD card to drop
from the GOT, resulting in a failure or break.
When inserting a USB device into a USB interface of the GOT, make sure to
insert the device into the interface firmly.Failure to do so may cause the USB
device to drop from the GOT, resulting in a failure or break
Before removing the USB device from the GOT, follow the procedure for
removal on the utility screen of the GOT. After the successful completion
dialog is displayed, remove the USB device by hand carefully.Failure to do so
may cause the USB device to drop from the GOT, resulting in a failure or
break.
When disposing of this product, treat it as industrial waste.
When disposing of batteries, separate them from other wastes according to
the local regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the
battery directive in the EU member states.)
When transporting lithium batteries, make sure to treat them based on the
transport regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the
regulated models.)
Make sure to transport the GOT main unit and/or relevant unit(s) in the
manner they will not be exposed to the impact exceeding the impact
resistance described in the general specifications of this manual, as they are
precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
When fumigants that contain halogen materials such as fluorine, chlorine,
bromine, and iodine are used for disinfecting and protecting wooden
packaging from insects, they cause malfunction when entering our products.
Please take necessary precautions to ensure that remaining materials from
fumigant do not enter our products, or treat packaging with methods other
than fumigation (heat method).
Additionally, disinfect and protect wood from insects before packing products.
CAUTION
WARNING
CAUTION
CAUTION
CAUTION
Manual
The following shows the manuals relevant to this product.
For detailed manuals and relevant manuals, refer to the e-Manual or PDF
manuals stored in the DVD-ROM for the screen design software used.
The latest manuals are also available from MITSUBISHI ELECTRIC FA Global
Website (www.MitsubishiElectric.com/fa).
Compliance with the new China RoHS directive
GOT 相关的基于 “ 电器电子产品有害物质限制使用管理办法 ” 要求的表示方法
Note: This symbol mark is for China only.
含有有害 6 物质的名称、含有量、含有部件
本产品中所含有的有害 6 物质的名称、含有量、含有部件如下表所示。
产品中有害物质的名称及含量
本表格依据 SJ/T11364 的规定编制。
○ : 表示该有害物质在该部件所有均质材料中的含量均在 GB/T26572 规定的限量
要求以下。
× : 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T26572 规定
的限量要求。
Referenced Standard: GB/T15969.2
(Requirement of Chinese standardized law)
Before using the GOT
Connect the connector of the GOT to the connector of the battery (GT11-50BAT,
sold separately).
Refer to the GOT2000 Series User’s Manual (Hardware) for the connection
instructions.
For details on the GOT specifications, installing instructions, wiring, maintenance
and inspection, or checking procedure for the version and the compatible standard,
refer to the GOT2000 Series User’s Manual (Hardware).
Packing List
The GOT product package includes the following:
1. FEATURES
(1) Abundant standard equipment
Variety of connection with FA devices
SD card interface compatible with the SDHC card having a
large capacity and allowing high-speed communication
Connection with various peripheral devices with the USB host
(2) Improved usability
Abundant troubleshooting
Easy and clear screen creation
PC-like operation screen
(3) Enhanced compatibility with Mitsubishi Electric FA devices
(4) Easy replacement
(5) LED backlight
Manual name
Manual number
(Model code)
GOT2000 Series User’s Manual
(Hardware)
SH-081194ENG(1D7MJ5)
GOT2000 Series User’s Manual
(Utility)
SH-081195ENG(1D7MJ6)
部件名称
有害物质
(Pb)
(Hg)
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
电路板组件 ×
树脂壳体、电缆、膜材
钣金部件、螺丝等金属部件 ×
Description Quantity
GT23 1
Installation fitting 4
GT23 General Description (This manual) 1
GT23 本体概要说明书
1
2. PART NAMES AND SETTINGS
The following shows the part names for GT2310 and GT2308.
No. Name Description
1) Display screen Displays the utility and the user-created screen.
2) Touch Pane
For operating the touch switches in the utility and the user-
created screen
3) POWER LED
Lit in blue : Power is properly supplied.
Lit in orange : Screen saving
Blinks in orange/blue : Backlight failure
Not lit : Power is not supplied
4) Unit installation fitting Mounting fixtures for fixing the GOT to the control panel
5) Installation switch Used for OS installations at the GOT startup
6) SD card access LED
Lit: SD card mounted
Blinking: SC card accessed
No lit: SD card not mounted or SD card mounted
(removable)
7) SD card interface For installing a SD card
8) SD card cover
With a switching function for accepting and stopping the
access to the SD card
When the cover is opened : Access is prohibited
When the cover is closed : Access is allowed
9) USB interface (Host)
For connecting a USB mouse, connecting a USB keyboard,
data transfer, and data storage
(connector type: TYPE-A)
10) USB interface (Device)
For connecting a personal computer (connector type: Mini-
B)
11)
Hole for attaching a
cable clamp
Hole for attaching a cable clamp for preventing USB cable
from being pulled out
(Recommended product: RSG-130-V0 made by
KITAGAWA INDUSTRIES CO.,LTD)
12)
Terminating resistor
setting switch
(Inside cover)
For switching on and off of the terminating resistor for the
RS-422 and RS-485 communication port (Default (Off))
13) Battery holder Houses the battery
14) Power terminal Power input terminal, LG terminal, FG terminal
15) Ethernet interface
For communicating with a controller or connecting a
personal computer (connector type: RJ-45 (modular jack))
16) RS-232 interface
For communicating with a controller (Connector type: D sub
9-pin (male))
17) RS-422/485 interface
For communicating with a controller (Connector type: D sub
9-pin (female))
Example:GT2310
1)2)
3)
5)
6)
7)
8)
10)
9)
17) 16)15) 14)
4) 13) 4)
4) 4)
12)
11)
3. SPECIFICATIONS
3.1 General Specifications
*1: The operating ambient temperature indicates the temperature inside the
enclosure of the control panel to which the GOT is installed.
La température ambiante de fonctionnement indique la température à l'intérieur
du boîtier du tableau de commande sur lequel le GOT est installé.
*2: If ambient temperature exceeds 40 , do not exceed absolute humidity
40 90%.
Si la température ambiante dépasse 40 , ne dépassez pas l'humidité absolue
de 40 90%.
*3: Do not use or store the GOT under pressure higher than the atmospheric
pressure of altitude 0m (0ft.).
Failure to observe this instruction may cause a malfunction.
When an air purge is made inside the control panel by adding pressure, there
may be a clearance between the surface sheet and the screen making it difficult
to use the touch panel, or the sheet may come off.
*4: This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from
fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*5: This index indicates the degree to which conductive material is generated in the
environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary
conductivity may be produced due to condensation.
*6: When a protective cover for oil is mounted on the GOT, the maximum operating
ambient temperature must be 5°C lower than the one described above.
Lors de l'installation du couvercle de protection contre l’huile, la température
ambiante de fonctionnement doit être réduite de 5°C par rapport aux valeurs
maximales dans les spécifications générales.
3.2 Power Supply Specifications
The following indicates the power supply specifications for GT23.
Item Specifications
Operating ambient
temperature
*1
Température
ambiante de
fonctionnement
*1
0 to 55
*2 *6
0 à 55
*2 *6
Storage ambient
temperature
-20 to 60
Operating ambient
humidity
10 to 90% RH, non-condensing
*2
Storage ambient
humidity
10 to 90% RH, non-condensing
*2
Vibration resistance
Compliant
with JIS B
3502 and
IEC
61131-2
Frequency Acceleration
Half-
amplitude
Sweep
count
Under
intermittent
vibration
5 to 8.4Hz
-
3.5mm
10 times
each in X,
Y and Z
directions
8.4
to150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 8.4Hz
-
1.75mm
-
8.4
to 150Hz
4.9m/s
2
-
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s
2
(15G), 3 times
each in X, Y and Z directions)
Operating
atmosphere
No greasy fumes, corrosive gas, flammable gas, excessive
conductive dust, and direct sunlight (Same as storage atmosphere)
Operating altitude
*3
2000 m (6562 ft) max.
Installation location Inside control panel
Overvoltage
category
*4
II or less
Pollution degree
*5
2 or less
Cooling method Self-cooling
Grounding
Grounding with a ground resistance of 100 Ω or less by using a ground
cable that has a cross-sectional area of 2 mm
2
or more.
If impossible, connect the ground cable to the control panel.
Point
Refer to the GOT2000 Series User’s Manual (Hardware) for details on the performance
specifications of each GOT.
Note
Operation at momentary failure
If an instantaneous power failure occurs in the power supply and continues for more
than the permissible period, the GOT will be reset.
Make sure to power on the unit more than 5 seconds after power-off.
3.2.1 For GOTs powered from the 100 to 240VAC
power supply
3.2.2 For GOTs powered from the 24VDC power
supply
3.3 External Dimensions
Item
Specifications
GT2310-VTBA GT2308-VTBA
Power supply voltage AC100 to 240VAC (+10%, -15%)
Power frequency 50,60Hz 5%
Input max. apparent power 44VA (maximum load) 30VA (maximum load)
Power
consum
ption
maximum load 18W or less 11W or less
Stand alone 15W 9W
Stand alone with backlight
off
8W 6W
Inrush current
40A or less (4ms, operating ambient temperature
25 , maximum load)
Allowable momentary power failure
time
20 ms or less (100VAC or more)
Noise immunity
1,500Vp-p noise voltage, 1 s noise width (when
measuring with a noise simulator under 25 to 60Hz
noise frequency)
Dielectric withstand voltage
1500VAC for 1 minute across power terminals and
earth
Insulation resistance
10M or more across power terminals and earth by a
500V DC insulation resistance tester
Applicable wire size 0.75[mm
2
] to 2[mm
2
]
Applicable solderless terminal
Solderless terminal for M3 screw RAV1.25-3, V2-
S3.3, V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5[N•m] to 0.8[N•m]
Item
Specifications
GT2310-VTBD GT2308-VTBD
Power supply voltage DC24V (+25%, -20%)
Power
consu
mption
Maximum load 16W or less 11W or less
Stand alone 13W 8W
Stand alone with backlight
off
7W 6W
Inrush current
40A or less (2ms, operating ambient temperature
25 , maximum load)
Allowable momentary power failure
time
10 ms or less
Noise immunity
500Vp-p noise voltage, 1 s noise width (when
measuring with a noise simulator under 25 to 60Hz
noise frequency)
Dielectric withstand voltage
350VAC for 1 minute across power terminals and
earth
Insulation resistance
10M or more across power terminals and earth by a
500V DC insulation resistance tester
Applicable wire size 0.75[mm
2
] to 2[mm
2
]
Applicable solderless terminal
Solderless terminal for M3 screw RAV1.25-3, V2-
S3.3, V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5[N•m] to 0.8[N•m]
199 (7.84)
10
(0.39)
10
(0.39)
303 (11.93)
208 (8.19)
228 (8.98)
288 (11.34)
218 (8.58)
56 (2.20)
6
(0.24)
GT2310 GT2308
175 (6.89)
194 (7.64)
10
(0.39)
10
(0.39)
241 (9.49)
166 (6.54)
166 (6.54)
226 (8.90)
56 (2.20)
6
(0.24)
Unit : mm (inch)
4. EMC AND LOW VOLTAGE DIRECTIVE
For the products sold in European countries, the conformance to the EMC
Directive, which is one of the European Directives, has been a legal
obligation since 1996. Also, conformance to the Low Voltage.
Directive, another European Directives, has been a legal obligation since
1997.
Manufacturers who recognize their products must conform to the EMC and
Low Voltage Directive are required to declare that their products conform to
these Directives and put a "CE mark" on their products.
Authorized representative in Europe
Authorized representative in Europe is shown below.
Name :Mitsubishi Electric Europe BV
Address :Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
4.1 Requirements to Meet EMC Directive
EMC Directives are those which require "any strong electromagnetic force
is not output to the external.:Emission (electromagnetic interference)" and
"It is not influenced by the electromagnetic wave from the external.:
Immunity (electromagnetic sensitivity)".
Items4.1.1 through4.1.3 summarize the precautions to use GOT and
configure the mechanical unit in order to match the EMC directives.
Though the data described herein are produced with our best on the basis
of the requirement items and standards of the restrictions gathered by
Mitsubishi Electric, they do not completely guaranteed that all mechanical
unit manufactured according to the data do not always match the above.
4.1.1 EMC directive
The standards of the EMC Directive are shown below.
*1: The GOT is an open type device (device installed to another device) and must
be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is installed
on the conductive control panel and combined with the Mitsubishi Electric PLC.
*2: QP (Quasi-Peak): Quasi-peak value, Mean: Average value
Applied
standard
Test standard Test details Standard value
EN61131-2
: 2007
CISPR16-2-3
Radiated noise
*1
Electromagnetic
emissions from the
product are
measured.
30M-230MHz QP:
30dB V/m (30m in
measurement range)
*2, *3
230M-1000MHz QP:
37dB V/m(30m in
measurement range)
*2, *3
CISPR16-2-1
Conducted noise
*1
Electromagnetic
emissions from the
product to the power
line is measured.
150k-500kHz QP:79dB,
Mean: 66dB
*2
500k-30MHz QP:73dB,
Mean: 60dB
*2
IEC61000-4-2
Electrostatic
immunity
*1
Immunity test in
which static
electricity is applied
to the cabinet of the
equipment.
4kV Contact discharge
8kV Aerial discharge
IEC61000-4-3
Radiated
electromagnetic
field AM modulation
Immunity test in
which field is
irradiated to the
product.
80-1000MHz:10V/m
1.4-2GHz:3V/m
2.0-2.7GHz:1V/m
80%AM modulation@1kHz
IEC61000-4-4
Fast transient burst
noise
*1
Immunity test in
which burst noise is
applied to the power
line and signal lines.
Power cable: 2kV
Digital I/O: 1kV
Analog I/O: 1kV
Signal cable: 1kV
IEC61000-4-5
Surge immunity
*1
Immunity test in
which lightening
surge is applied to
the product.
AC power type
Power line (between line and
ground): 2kV
Power line (between lines)
: 1kV
Data communication port
: 1kV
DC power type
Power line (between line and
ground) : 0.5kV
Power line (between lines)
: 0.5kV
Data communication port
: 1kV
IEC61000-4-6
Conducted RF
immunity
*1
Immunity test in
which a noise
inducted on the
power and signal
lines is applied.
Power line: 10V
Data communication port: 10V
IEC61000-4-8
Power supply
frequency magnetic
field immunity
Test for checking
normal operations
under the
circumstance
exposed to the
ferromagnetic field
noise of the power
supply frequency
(50/60Hz).
30 A/m
IEC61000-4-11
Instantaneous
power failure and
voltage dips
immunity
Test for checking
normal operations
at instantaneous
power failure.
AC power type
0.5 cycle 0% (interval 1 to 10s)
250/300 cycle 0%
10/12 cycle 40%
25/30 cycle 70%
*3: The above test items are conducted in the following conditions.
30M-230MHz QP : 40dB V/m (10m in measurement range)
230M-1000MHz QP : 47dB V/m (10m in measurement range)
4.1.2 Control panel
The GOT is an open type device (device installed to another device) and
must be installed in a conductive control panel.
It not only assure the safety but also has a large effect to shut down the
noise generated from GOT, on the control panel.
(1) Control Panel
(a) The control panel must be conductive.
(b) When fixing a top or bottom plate of the control panel with bolts,
do not coat the plate and bolt surfaces so that they will come into
contact.
And connect the door and box using a thick grounding cable in
order to ensure the low impedance under high frequency.
(c) When using an inner plate to ensure electric conductivity with the
control panel, do not coat the fixing bolt area of the inner plate
and control panel to ensure conductivity in the largest area as
possible.
(d) Ground the control panel using a thick grounding cable in order to
ensure the low impedance under high frequency.
(e) The diameter of cable holes in the control panel must be 10cm
(3.94in.). In order to reduce the chance of radio waves leaking
out, ensure that the space between the control panel and its door
is small as possible.
Paste the EMI gasket directly on the painted surface to seal the
space so that the leak of electric wave can be suppressed.
Our test has been carried out on a panel having the damping
characteristics of 37dB max. and 30dB mean (measured by 3m
method with 30 to 300MHz).
(2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as
described below.
(a) Provide a grounding point near the GOT. Short-circuit the LG and
FG terminals of the GOT (LG: line ground, FG: frame ground)
and ground them with the thickest and shortest wire possible
(The wire length must be 30cm (11.81in.) or shorter.)
The LG and FG terminals function is to pass the noise generated
in the PC system to the ground, so an impedance that is as low
as possible must be ensured. As the wires are used to relieve the
noise, the wire itself carries a large noise content and thus short
wiring means that the wire is prevented from acting as an
antenna.
Note) A long conductor will become a more efficient antenna at
high frequency.
(b) The earth wire led from the earthing point must be twisted with
the power supply wires.
By twisting with the earthing wire, noise flowing from the power
supply wires can be relieved to the earthing. However, if a filter is
installed on the power supply wires, the wires and the earthing
wire may not need to be twisted.
4.1.3 Noise filter (power supply line filter)
The noise filter (power supply line filter) is a device effective to reduce
conducted noise. Except some models, installation of a noise filter onto
the power supply lines is not necessary. However conducted noise can
be reduced if it is installed. (The noise filter is generally effective for
reducing conducted noise in the band of 10MHz or less.) Usage of the
following filters is recommended.
The precautions required when installing a noise filter are described
below.
(1) Do not install the input and output cables of the noise filter together
to prevent the output side noise will be inducted into the input side
cable where noise has been eliminated by the noise filer.
(2) Connect the noise filter's ground terminal to the control panel with
the shortest cable as possible (approx. 10cm (3.94 in.) or less).
Model name FN343-3/05 FN660-6/06 RSHN-2003
Manufacturer SCHAFFNER SCHAFFNER TDK
Rated current 3A 6A 3A
Rated voltage 250V
Installing the input and output cables
together will cause noise induction.
Separate the input cable from the output
cable.
Filter
Induction
Output side
(device side)
Input side
(power supply side)
Filter
Output side
(device side)
Input side
(power supply side)
4.2 Requirements for Compliance with the Low
Voltage Directive
The Low Voltage Directive requires each device which operates with
power supply ranging from 50VAC to 1000V and 75VDC to 1500V to
satisfy necessary safety items.
In the Sections from
4.2.1 to 4.2.5, cautions on installation and wiring of
the GOT to conform to the Low Voltage Directive requires are described.
We have put the maximum effort to develop this material based on the
requirements and standards of the Directive that we have collected.
However, compatibility of the devices which are fabricated according to
the contents of this manual to the above Directive is not guaranteed.
Each manufacturer who fabricates such device should make the final
judgement about the application method of the Low Voltage Directive
and the product compatibility.
4.2.1 Standard subject to GOT
4.2.2 Power supply
The insulation specification of the GOT was designed assuming
installation category II. Be sure to use the installation category II power
supply to the GOT.
The installation category indicates the durability level against surge
voltage generated by lightning strike.
Category I has the lowest durability; category IV has the highest
durability.
Installation category
Category II indicates a power supply whose voltage has been reduced
by two or more levels of isolating transformers from the public power
distribution.
4.2.3 Control panel
Because the GOT is open type equipment (device designed to be stored
within another device), be sure to use it only when installed in a control
panel.
(1) Shock Protection
In order to prevent those who are unfamiliar with power facility,
e.g., an operator, from getting a shock, make sure to take the
following measures on the control panel.
(a) Store the GOT within the control panel locked, and allow only
those who are familiar with power facility to unlock the panel.
(b)Build the structure in order that the power supply will be shut off
when the control panel is opened.
(2) Dustproof and waterproof features
The control panel also provides protection from dust, water and
other substances. Insufficient ingression protection may lower the
insulation withstand voltage, resulting in insulation destruction.
The insulation in the GOT is designed to cope with the pollution
level 2, so use in an environment with pollustion level 2 or better.
4.2.4 Grounding
The following are applicable ground terminals. Use them in the grounded
state.
Be sure to ground the GOT for ensuring the safety and complying with
the EMC Directive.
Standard applied to GOT : EN61131-2 Programmable controllers - Equipment
requirements and tests
Pollution level 1: An environment where the air is dry and conductive
dust does not exist.
Pollution level 2: An environment where conductive dust does not
usually exist, but occasional temporary conductivity
occurs due to the accumulated dust.
Generally, this is the level for inside the control panel
equivalent a control room or on the floor of a typical
factory.
Pollution level 3: An environment where conductive dust exits and
conductivity may be generated due to the accumulated
dust.
An environment for a typical factory floor.
Pollution level 4: Continuous conductivity may occur due to rain, snow,
etc. An outdoor environment.
Functional grounding : Improves the noise resistance.
Category ICategory IICategory IIICategory IV
4.2.5 External wiring
(1) External devices
When a device with a hazardous voltage circuit is externally
connected to the GOT, select a model which complies with the
Low Voltage Directive's requirements for isolation between the
primary and secondary circuits.(2)Insulation requirements
Dielectric withstand voltages are shown in the following table.
Reinforced Insulation Withstand Voltage
(Installation Category II, source : IEC664)
5. INSTALLATION
5.1 Control Panel Inside Dimensions for
Mounting GOT
Install the GOT on the control panel out of the way for the equipment
inside the control panel. Do not install the GOT and the unit in
prohibited areas for the installation.
5.2 Panel Cutting Dimensions
5.3 Mounting Position
When mounting the GOT, the following clearances must be maintained
from other structures and devices.
Some cables may need to be longer than the specified dimensions when
connecting to the GOT.
Therefore, consider the connector dimensions and bending radius of the
cable as well for installation.
For the lead-in allowance for cables at the bottom of the GOT, refer to
the GOT2000 Series User’s Manual (Hardware).
According to the dimensions in the following table, leave clearances
between the GOT and the other devices. The values enclosed in square
brackets apply to the case where no other equipment generating
radiated noise (such as a contactor) or heat is installed near the GOT.
However, keep the ambient temperature of the GOT to 55°C or lower.
Rated voltage of hazardous
voltage area
Surge withstand voltage (1.2/50 s)
150 VAC or below 2500V
300 VAC or below 4000V
Point
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the
GOT. Therefore, consider the connector dimensions and bending radius of the cable as
well for installation.
A
B
Unit: mm (inch)
*Panel thickness : 1.6 to 4 mm
(0.06 to 0.16 inch)
GOT A B
GT2310
GT2308
289 (11.38)
227 (8.94)
+2 (0.08)
0 (0)
+2 (0.08)
0 (0)
200 (7.87)
176 (6.93)
+2 (0.08)
0 (0)
+2 (0.08)
0 (0)
B
DE
A
C
Panel thickness: 1.6 to 4mm
(0.06 to 0.16 inch)
Unit : mm(inch)
*1: When opening or closing the battery cover: 72(2.83) or more
5.4 Control Panel Inside Temperature and
Installation Angle
When installing the GOT to a panel, set the display section as shown
below.
Using the GOT with the installation angle other than the following
deteriorates the GOT earlier.
When installing the GOT with the installation angle between 60 to 105 °,
the temperature inside the control panel must be within 55 °C.
When installing the GOT with the installation angle other than between
60 to 105 °, the temperature inside the control panel must be within 40
°C.
Item GT2310 GT2308
A
48(1.89) or more
[18(0.71) or more]
B
78(3.07) or more
[18(0.71) or more]
C
When the SD card is used
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
When the SD card is not
used
50(1.97) or more
[20(0.79) or more]
D
50(1.97) or more
[20(0.79) or more]
E
*1
100(3.94) or more
[20(0.79) or more]
GOT
Display section
Panel or others
105°
60°
5. INSTALLATION
5.1 Dimensions intérieures du tableau de
commande pour le montage du GOT
Installez le GOT sur le tableau de commande en laissant de l'espace
pour le dispositif à l'intérieur du tableau de commande. N'installez
pas le GOT et le module dans des zones où l'installation est interdite.
5.2 Cotes de découpe du panneau
5.3 Position de montage
Lors du montage du GOT, laissez les espaces suivants pour les autres
structures et dispositifs.
Certains câbles peuvent être plus longs que les dimensions spécifiées
lors de la connexion au GOT.
Par conséquent, prenez également en compte les dimensions du
connecteur et le rayon de courbure du câble pour l'installation.
Pour connaître l'espace à laisser pour les câbles sous le GOT, référez-
vous au manuel GOT2000 Series User’s Manual (Hardware).
Laissez les espaces entre le GOT et les autres dispositifs en fonction
des dimensions contenues dans le tableau suivant. Les valeurs entre
parenthèses s'appliquent au cas où aucun dispositif générant des
émissions sonores (comme un contacteur) ou de la chaleur n'est installé
près du GOT. Toutefois, maintenez la température ambiante du GOT à
55°C ou moins.
Unité : mm (pouce)
*1: Pour ouvrir ou fermer le couvercle de la batterie : 72 (2,83) ou plus
Point
Câble applicable
Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la
connexion au GOT. Par conséquent, prenez également en compte les dimensions du
connecteur et le rayon de courbure du câble pour l'installation.
Article GT2310 GT2308
A
48 (1,89) ou plus
[18 (0,71) ou plus]
B
78 (3,07) ou plus
[18 (0,71) ou plus]
C
Quand la carte SD est
utilisée
50 (1,97) ou plus
[20 (0,79) ou plus]
50 (1,97) ou plus
Quand la carte SD n'est
pas utilisée
50 (1,97) ou plus
[20 (0,79) ou plus]
D
50 (1,97) ou plus
[20 (0,79) ou plus]
E
*1
100 (3,94) ou plus
[20 (0,79) ou plus]
A
B
Unité : mm (pouce)
*
É
paisseur du panneau : 1,6 à 4mm
(0,06 à 0,16 pouce)
GOT A B
GT2310
GT2308
289 (11,38)
227 (8,94)
+2 (0,08)
0 (0)
+2 (0,08)
0 (0)
200 (7,87)
176 (6,93)
+2 (0,08)
0 (0)
+2 (0,08)
0 (0)
B
DE
A
C
Épaisseur du panneau : 1,6 à 4mm
(0,06 à 0,16 pouce)
5.4 Température intérieure et angle
d'installation du tableau de commande
Lors de l'installation du GOT sur un panneau, réglez la zone d'affichage
comme indiqué ci-dessous.
Si l'angle d'installation est différent de celui indiqué, le GOT se détériore
plus tôt.
Lors de l'installation du GOT avec un angle d'installation compris entre
60 et 105°, la température à l'intérieur du tableau de commande doit être
d'environ 55°C.
Lors de l'installation du GOT avec un angle d'installation non compris
entre 60 et 105°, la température à l'intérieur du tableau de commande
doit être d'environ 40°C.
6. MAINTENANCE AND INSPECTION
Refer to the GOT2000 Series User’s Manual (Hardware) for
maintenance and inspection for the GOT.
GOT
Zone d'affichage
Tableau ou autres
105°
60°
Warranty
Mitsubishi Electric will not be held liable for damage caused by
factors found not to be the cause of Mitsubishi Electric; machine
damage or lost profits caused by faults in the Mitsubishi Electric
products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi Electric;
damages to products other than Mitsubishi Electric products; and to
other duties.
For safe use
This product has been manufactured as a general-purpose part for
general industries, and has not been designed or manufactured to
be incorporated in a device or system used in purposes related to
human life.
Before using the product for special purposes such as nuclear
power, electric power, aerospace, medicine or passenger
movement vehicles, consult with Mitsubishi Electric.
This product has been manufactured under strict quality control.
However, when installing the product where major accidents or
losses could occur if the product fails, install appropriate backup or
failsafe functions in the system.
Country/Region Sales office/Tel
USA Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway, Vernon Hills, IL 60061, U.S.A.
Tel: +1-847-478-2100
Brazil Mitsubishi Electric do Brasil Comercio e Servicos Ltda.
Avenida Adelino Cardana, 293, 21 andar, Bethaville, Barueri SP, Brazil
Tel: +55-11-4689-3000
Mexico Mitsubishi Electric Automation, Inc. Mexico Branch
Boulevard Miguel de Cervantes Saavedra 301, Torre Norte Piso 5, Ampliacion Granada,
Miguel Hidalgo, Ciudad de Mexico, Mexico, C.P.11520
Tel: +52-55-3067-7512
Germany Mitsubishi Electric Europe B.V. German Branch
Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
Tel: +49-2102-486-0
UK Mitsubishi Electric Europe B.V. UK Branch
Travellers Lane, UK-Hatfield, Hertfordshire, AL10 8XB, U.K.
Tel: +44-1707-28-8780
Italy Mitsubishi Electric Europe B.V. Italian Branch
Centro Direzionale Colleoni - Palazzo Sirio, Viale Colleoni 7,
20864 Agrate Brianza (MB), Italy
Tel: +39-039-60531
Spain Mitsubishi Electric Europe B.V. Spanish Branch
Carretera de Rubi, 76-80-Apdo. 420, E-08190 Sant Cugat del Valles (Barcelona), Spain
Tel: +34-935-65-3131
France Mitsubishi Electric Europe B.V. French Branch
25, Boulevard des Bouvets, 92741 Nanterre Cedex, France
Tel: +33-1-55-68-55-68
Czech Mitsubishi Electric Europe B.V. Czech Branch
Pekarska 621/7, 155 00 Praha 5, Czech Republic
Tel: +420-255 719 200
Turkey Mitsubishi Electric Turkey A.S. Umraniye Branch
Serifali Mahallesi Nutuk Sokak No:5, TR-34775 Umraniye / Istanbul, Turkey
Tel: +90-216-526-3990
Poland Mitsubishi Electric Europe B.V. Polish Branch
ul. Krakowska 48, 32-083 Balice, Poland
Tel: +48-12-347-65-00
Russia Mitsubishi Electric (Russia) LLC St. Petersburg Branch
Piskarevsky pr. 2, bld 2, lit "Sch", BC "Benua", office 720; 195027 St. Petersburg, Russia
Tel: +7-812-633-3497
South Africa Adroit Technologies
20 Waterford Office Park, 189 Witkoppen Road, Fourways, South Africa
Tel: +27-11-658-8100
China Mitsubishi Electric Automation (China) Ltd.
Mitsubishi Electric Automation Center, No.1386 Hongqiao Road, Shanghai, China
Tel: +86-21-2322-3030
Taiwan SETSUYO ENTERPRISE CO., LTD.
6F, No.105, Wugong 3rd Road, Wugu District, New Taipei City 24889, Taiwan
Tel: +886-2-2299-2499
Korea Mitsubishi Electric Automation Korea Co., Ltd.
7F to 9F, Gangseo Hangang Xi-tower A, 401, Yangcheon-ro, Gangseo-Gu,
Seoul 07528, Korea
Tel: +82-2-3660-9569
Singapore Mitsubishi Electric Asia Pte. Ltd.
307 Alexandra Road, Mitsubishi Electric Building, Singapore 159943
Tel: +65-6473-2308
Thailand Mitsubishi Electric Factory Automation (Thailand) Co., Ltd.
12th Floor, SV.City Building, Office Tower 1, No. 896/19 and 20 Rama 3 Road,
Kwaeng Bangpongpang, Khet Yannawa, Bangkok 10120, Thailand
Tel: +66-2682-6522 to 31
Indonesia PT. Mitsubishi Electric Indonesia
Gedung Jaya 8th Floor, JL. MH. Thamrin No.12, Jakarta Pusat 10340, Indonesia
Tel: +62-21 3192-6461
Vietnam Mitsubishi Electric Vietnam Company Limited
11th & 12th Floor, Viettel Tower B, 285 Cach Mang Thang 8 Street, Ward 12,
District 10, Ho Chi Minh City, Vietnam.
Tel: +84-28-3910-5945
India Mitsubishi Electric India Pvt. Ltd. Pune Branch
Emerald House, EL-3, J Block, M.I.D.C., Bhosari, Pune - 411026, Maharashtra, India
Tel: +91-20-2710-2000
Australia MITSUBISHI ELECTRIC AUSTRALIA PTY. LTD.
348 Victoria Road, P.O. Box 11, Rydalmere, N.S.W 2116, Australia
Tel: +61-2-9684-7777
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan, February 2021.