NAPOLEON WHD48 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire

Ce manuel convient également à

W415-1606 / C / 11.08.17
FRENCH
PG.49
ADD MANUAL TITLE
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone 1 (866) 820-8686 • www.napoleonfi replaces.com • hearth@napoleonproducts.com
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES
INSTALLER:
Leave this manual with the appliance
CONSUMER:
Retain this manual for future reference
ADD PRODUCT CODE HERE (TRADE GOTHIC LT STD FONT)
NATURAL GAS MODELS:
PROPANE GAS MODELS:
PRODUCT NAME™
ADD ____ ILLUSTRATED
ADD PRODUCT IMAGE
CSA /
INTERTEK
LOGO
SAFETY INFORMATION
- Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of
this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbour’s phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier, call
the fi re department.
- Installation and service must be
performed by a qualifi ed installer, service
agency, or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certifi ed kit is used.
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
WARNING
!
ENGLISH
$10.00
FOR INDOOR USE ONLY
SAFETY BARRIER
Plazmafire™ 48
(WHD48)
WHD48N
WHD48P
INSTALLATION AND
OPERATION MANUAL
The information throughout this manual is believed to be correct at the time of printing. Wolf Steel
Ltd. reserves the right to change or modify any information within this manual at any time without
notice. Changes, other than editorial are denoted by a vertical line in the margin.
note:
W415-1606 / C / 11.08.17
EN
2
table of contents
1.0 installation overview 3
2.0 safety information 4
3.0 general information 6
3.1 dimensions 6
3.2 hardware list 7
3.3 general instructions 8
3.4 rating plate information 9
4.0 venting 10
4.1 venting lengths and components 11
4.2 typical vent installation 12
4.3 special vent installations 12
4.3.1 periscope termination 12
4.4 vent terminal clearances 13
4.5 horizontal termination 14
4.6 vertical termination 15
5.0 installation 16
5.1 mounting plate installation (for typical
drywall construction) 17
5.2 mounting plate installation (for concrete) 18
5.3 using flexible vent components 18
5.3.1 appliance vent connection 19
5.3.2 vertical installation 19
5.3.3 horizontal air terminal installation 19
5.3.4 vertical air terminal installation (flexible) 20
5.4 mounting the appliance 21
5.5 gas installation 22
5.6 mobile home 22
5.7 minimum clearance to combustibles and
non-combustibles 23
5.8 receiver location / wiring 24
6.0 finishing 25
6.1 housing panel installation 25
6.2 door removal / installation 26
6.3 glass media 26
6.4 surround installation / removal 27
6.5 logo placement 27
7.0 electrical information 28
7.1 hard wiring connection 28
7.2 wiring diagram 28
7.3 receptacle wiring diagram 29
8.0 operation 30
8.1 operating instructions 30
8.2 lighting instructions 30
8.3 general transmitter layout 31
8.5 temperature display 32
8.6 flame height time 32
8.4 Initializing the transmitter/battery holder
for the first time 32
8.7 LED on/off light control 33
8.8 continuous pilot / intermittent pilot (CPI /
IPI) selection 33
8.9 child proof function 34
8.10 low battery / manual bypass 34
8.11 in the event of a power failure 34
8.12 manual operation 34
9.0 adjustments 35
9.1 pilot burner adjustment 35
9.2 venturi adjustment 35
9.3 flame characteristics 35
10.0 maintenance 36
10.1 annual maintenance 36
10.2 care of glass 37
10.3 care of plated parts 37
10.4 door glass replacement 37
11.0 replacements 38
11.1 overview 39
11.2 valve train assembly 40
12.0 accessories 41
13.0 troubleshooting 42
14.0 warranty 45
15.0 service history 46
16.0 notes 47
WALL INSTALL
This drawing is the property of Wolf Steel LTD. or NAC.
It is not to be reproduced nor used in any manner
without our consent. All rights are reserved.
2
08/27/14 AGR
UNLESS OTHERWISE NOTED OR DEPICTED
ALL DIMENSIONS ARE OUTSIDE IN INCHES
ALL SURFACES ARE CONSIDERED CLASS "D"
REFER TO ENG-009 AND ENG-010
FOR SURFACE FINISH CRITERIA
TOLERANCES:
A
B
C
D
B
A
C
D
1 2 3 4 5 7 8
8
754321
SAFETY BARRIER
Mantel, see
“minimum
clearance to
combustibles
and non-
combustibles ”
section.
Venting, see
“venting” and
“installation” sections.
Rating plate, see “rating plate
information”
section.
Side Wall, see
“minimum clearances to
combustibles and non-
combustibles”
section.
Surround, see
“finishing” section.
EN
W415-1606 / C / 11.08.17
3
installation overview
1.0 installation overview
W415-1606 / C / 11.08.17
EN
4
safety information
2.0 safety information
This appliance is hot when operated and can
cause severe burns if contacted.
Any changes to this appliance or its control
can be dangerous and are prohibited.
Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
Risk of fi re or asphyxiation do not operate
appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned
off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
Children and adults should be alerted to the hazards of high surface temperature and should stay away
to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children, and others may be susceptible to accidental contact burns. A physical barrier
is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove,
install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the
room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and
draperies.
Ensure you have incorporated adequate safety measures to protect infants/toddlers from touching hot
surfaces.
Even after the appliance is off, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to
operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other
ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
LA VITRE CHAUDE CAUSERA
DES BRÛLURES.
NE PAS TOUCHER LA VITRE
AVANT QU’ELLE AIT REFROIDI.
NE JAMAIS LAISSER LES
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
!
AVERTISSEMENT
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
Une barriére conçu à réduire le risque de brûlures
causées par le verre chaud est fourni avec l’appareil et
sera installé pour la protection des enfants et d’autres
personnes à risque.
3.1
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to
prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the
exhaust escaping through these openings can also cause the surrounding combustible materials to overheat
and catch fi re.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all
plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced
as well as having a carbon monoxide detector installed in the same area to defend you and your family
against carbon monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or
damage to decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and
shall be installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be kept clean.
!
WARNING
!
WARNING
EN
W415-1606 / C / 11.08.17
5
safety information
This appliance is hot when operated and can
cause severe burns if contacted.
Any changes to this appliance or its control
can be dangerous and are prohibited.
Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
Risk of fi re or asphyxiation do not operate
appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned
off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
Children and adults should be alerted to the hazards of high surface temperature and should stay away
to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children, and others may be susceptible to accidental contact burns. A physical barrier
is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove,
install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the
room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and
draperies.
Ensure you have incorporated adequate safety measures to protect infants/toddlers from touching hot
surfaces.
Even after the appliance is off, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to
operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other
ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
LA VITRE CHAUDE CAUSERA
DES BRÛLURES.
NE PAS TOUCHER LA VITRE
AVANT QU’ELLE AIT REFROIDI.
NE JAMAIS LAISSER LES
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
!
AVERTISSEMENT
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
Une barriére conçu à réduire le risque de brûlures
causées par le verre chaud est fourni avec l’appareil et
sera installé pour la protection des enfants et d’autres
personnes à risque.
3.1
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to
prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the
exhaust escaping through these openings can also cause the surrounding combustible materials to overheat
and catch fi re.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all
plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced
as well as having a carbon monoxide detector installed in the same area to defend you and your family
against carbon monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or
damage to decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and
shall be installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be kept clean.
!
WARNING
!
WARNING
3.1 dimensions
W415-1606 / C / 11.08.17
EN
6
general information
28"
711mm
8
7
16
"
214mm
27"
685mm
7
16
"
11mm
20"
508mm
5"
125mm
8"
202mm
60
3
16
"
1529mm
54
1
8
"
1375mm
3"
77mm
FRONT VIEW RIGHT SIDE VIEW TOP VIEW
SAFETY BARRIER
3.0 general information
3.2 hardware list
Only fasteners supplied with the appliance will be illustrated.
note:
EN
W415-1606 / C / 11.08.17
7
general information
Type Description Quantity
5/16” Long Thread Cutting Screw
1
8
2
3
4 5
1
20
4
4
1/2” Long Sheet Metal Screw
Lag Bolt
1/4” Flat Washer
1/4” Hex, 1/2” Long Sheet Metal Screw
39
2
3
4
5
6 1/4” Long Flat Head Screw
2
6
7
7 2 1/2” Long Sheet Metal Screw 4
3.3 general instructions
THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for
example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of
Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas
log.
The appliance off valve must be a “T” handle gas cock.
The fl exible connector must not be longer than 36 inches (0.9m).
A carbon monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of local
codes, the National Gas and Propane Installation Code CSA B149.1
in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54
in the United States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA Z240MH Series,
for gas equipped mobile homes, in Canada or ANSI Z223.1 and
NFPA 54 in the United States.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (35 mb).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the
absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National
Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a
properly grounded receptacle. The grounding prong must not be removed from the cord plug.
The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable
and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat
created. The location of windows, doors and, the traffi c fl ow in the room where the appliance is to be located should be
considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or
appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
Institute
®
(NFI) as NFI Gas
Specialists
www.ncertied.org
!
WARNING
Always light the pilot whether for the first time or if the gas supply has run out, with the glass door opened
or removed.
Provide adequate clearance for servicing and operating the appliance.
Provide adequate ventilation.
Never obstruct the front opening of the appliance.
Objects placed in front of the appliance must be kept a minimum of 48” (121.9cm) from the front face of
the appliance.
Surfaces around and especially above the appliance can become hot. Avoid contact when appliance is
operating.
Fire risk. Explosion hazard.
High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PSIG. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 PSIG (35mb).
Use only Wolf Steel approved optional accessories and replacement parts with this appliance using non-
listed accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result
in a safety hazard and will void the warranty and certification.
The appliance must not be operated at temperatures below freezing (32ºF / 0ºC). Allow the appliance to
warm, to above freezing prior to operation.
This appliance has been designed and certified for indoor use only.
W415-1606 / C / 11.08.17
EN
8
general information
* When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specific recommendations from the
local authority having jurisdiction, the certified altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft
(305m) above sea level.
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home
installation. The natural gas model can only be installed in a mobile home that is
permanently positioned on its site and fueled with natural gas. This appliance may
be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certified kit is used.
A barrier designed to reduce the risk of burns from the hot viewing glass is
provided with the appliance and must be installed.
Expansion / contraction noises during heating up and cooling down cycles are
normal and are to be expected.
This appliance is equipped with a three-prong (grounding) plug for protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from the plug.
70.8%
CWHD48
70.8%
WHD48
70.8%
WHD48
Cote énergétique des foyers à gaz
Basée sur la norme CSA P.4.1-02
Modèle No.
70.8%
CWHD48
Cote énergétique des foyers à gaz
Basée sur la norme CSA P.4.1-02
Modèle No.
FRENCH:
ENGLISH:
15
15
15
15
EN
W415-1606 / C / 11.08.17
9
general information
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
Rates and Efficiencies
NG P
Altitude (FT) 0-4,500* 0-4,500*
Max. Input (BTU/hr) 28,000 28,000
Min. Inlet Gas Supply Pres-
sure
4.5"
(11mb) w.c.
11"
(27mb) w.c.
Max. Inlet Gas Supply
Pressure
13"
(32mb) w.c.
13"
(32mb) w.c.
Manifold Pressure (Under
Flow Conditions)
3.5"
(9mb) w.c.
10"
(25mb) w.c.
TITLE: RATING PLATE WHD48
REVISION: B: UPDATED CSA / ANSI YEAR AND DESCRIPTION, ADDED PAGE NUMBER || 08.11.17_C.L.
DWG#: W385-2131
DATE: 06.22.16
MAX SIZE: 8.5" X 4.75"
HOLE TO BE 0.250"Ø
MATERIAL: CLASS III A-2, PERMANENT LABEL, WATERPROOF, .010MIL VELVET MATTE LEXAN AND/OR .050 HI-TEMP POLYESTER, CAPABLE OF WITHSTANDING A
MAXIMUM TEMPERATURE OF 175°F (79°C).
MIN. LETTERING FOR "NOT FOR USE WITH SOLID FUEL. ", "UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CELUI. " TO BE 10 POINT ARIAL, BOLD FACE,
UPPER CASE AND 2 POINT LEADING SPACING OR EQUIVALENT.
BLACK LETTERING ON WHITE BACKGROUND.
SERIAL NUMBERS TO BE ASCENDING FROM WHD48 015416
W385-2131 / B
DIRECT VENT, VENTED GAS FIREPLACES. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING
ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE
WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES,
IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME
INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. THIS APPLIANCE MUST BE
INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE CURRENT
ANSI Z223.1, OR CSA B149, INSTALLATION CODES.
FOR USE WITH BARRIER W565-0273.
FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
FOYER À GAZ VENTILÉ. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE
SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI
SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE
MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA
NORME DE SÉCURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24
CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE
APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ
CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES
SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A. CODES. INSTALLER L’APPAREIL SELON LES
CODES OU RÈGLEMENTS LOCAUX, OU EN L’ABSENCE DE TELS RÈGLEMENTS, SELON LES
CODES D’INSTALLATION ANSI Z223.1 OU CSA-B149 EN VIGUER.
POUR UNE UTILISER AVEC
BARRIÈRE
W565-0273
. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE
MANUEL D'INSTALLATION.
9700539 (WSL) 4001657 (NGZ)
4001658 (NAC) 4001659 (WUSA)
WHD48N CWHD48N MODEL CWHD48P WHD48P
0-4500FT (0-1370m) ALTITUDE / ÉLÉVATION 0-4500FT (0-1370m)
28,000 BTU/h INPUT / ALIMENTATION 28,000 BTU/h
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS
DOORS CERTIFIED WITH THIS APPLIANCE ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES,
OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES *:
MANTEL / CEILING 15" MANTEAU / PLAFOND 15"
SIDES 7" CÔTÉS 7"
VENT SIDES / BOTTOM 1" CÔTÉS DE L'ÉVENT / ÉVENT INFÉRIEUR 1"
FLOOR 6" PLANCHER 6"
VENT TOP 3" ÉVENT SUPÉRIEUR 3"
* SEE INSTALLATION MANUAL FOR FURTHER INFORMATION / VOIR MANUEL D'INSTALLATION POUR PLUS
D'INFORMATION.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR LES LONGUEURS D'ÉVACUATION MINIMALE
ET MAXIMALE.
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ
AVEC CET APPAREIL. UTILISER AVEC LES PORTES
VITRÉES HOMOLOGUÉES SEULEMENT AVEC CETTE
APPAREIL.
AVERTISSEMENT:
N’AJOUTEZ PAS À CET APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN CONTACT
AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE NAPOLEON VENT KITS. SEE OWNER'S INSTALLATION
MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE
VENT-AIR INTAKE SYSTEM. /
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE À NAPOLEON. RÉFÉRER AU
MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER
ET RESCELLER L'ÉVENT APRÉS AVOIR ASSURÉ LE MAINTIEN DU SYSTÉME DE PRISE D'AIR.
ELECTRICAL RATING: 115V, 60HZ. LESS THAN 12 AMPERES
SPÉCIFICATIONS ÉLECTRIQUES: 115V, 60HZ. MOINS DE 12 AMPÈRES
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPAREIL DE CHAUFFAGE
SERIAL NUMBER/NO. DE SÉRIE: WHD48
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CERTIFIED TO / CERTIFIÉ CSA 2.22-2016 AND / ET ANSI Z21.50-2016 VENTED DECORATIVE GAS APPLIANCES / FOYER À GAZ VENTILÉ.
REDUCED INPUT / ALIMENTATION RÉDUITE
P4
19,000 BTU/h
23,000 BTU/h
70.8%70.8%
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
PRESSION AU COLLECTEUR: 3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
COLONNE D'EAU (GN)
MAX. SUPPLY PRESSURE: 13" W.C. (NG)
PRESSION D'ALIMENTATION MAX: 13" D'UNE
COLONNE D'EAU (GN)
MANIFOLD PRESSURE: 10 INCHES W.C.(P)
PRESSION AU COLLECTEUR: 10" D'UNE
COLONNE D'EAU (P)
MIN SUPPLY PRESSURE: 11" W.C. (P)
PRESSION D'ALIMENTATION MIN: 11" D'UNE
COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE: 13" W.C. (P)
PRESSION D'ALIMENTATION MAX: 13" D'UNE
COLONNE D'EAU (P)
WOLF STEEL LTD.
B
PAGE 1 OF 2 B
SAMPLE
3.4 rating plate information
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
The rating plate must remain with the appliance at all times. It must not be removed.
note:
7.2
!
WARNING
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
If venting is included with spacers, the vent system must be supported every 3’(0.9m) for both vertical and
horizontal runs. Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain
the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the
inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required
for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is
maintained. These spaces must not be removed.
This appliance uses a 5” (127mm) exhaust / 8” (203.2mm) air intake vent pipe system. Refer to the
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is
recommended.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the
following termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410,
8/12 to 12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration
below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent
kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
to verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of
vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections)
when using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4” (21mm) rise per foot/meter using fl exible venting. For safe and
proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single
family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼”
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
Vent
Manufacturer
Starter Adapter Part
Number
Supplier Website
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DNA Metal-Fab www.mtlfab.com
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
following vent systems and may be purchased from the corresponding supplier:
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
alternate constructions, such as a chimney as part of the vent system, is not permitted.
note:
W415-1606 / C / 11.08.17
EN
10
venting requirements
4.0 venting requirements
4.1 venting lengths and components
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must
be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the
installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding
supplier:
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red
high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe
joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance flue collar which
must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following
termination kits: wall terminal kit GD422R-2, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof terminal
kit GD411, flat roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With flexible venting, in
conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Rigid and flexible venting systems must not be combined. Different venting manufacturer components must
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. When terminating horizontally, the maximum
allowable horizontal run is 20 feet (6.1m). When terminating vertically, the maximum allowable vertical vent length is 40 feet
(12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the
air terminal connections) when using flexible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended that
all horizontal runs have a minimum 1/4” rise per foot or 21mm per meter using flexible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm)
air gap all around between the inner liner and outer liner is required for safe operation.
Vent Manufacturer
Starter Adapter Part
Number
Supplier Website
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DDA Metal-Fab www.mtlfab.com
EN
W415-1606 / C / 11.08.17
11
venting requirements
4.2 typical vent installation
16" (40.6CM)
MINIMUM
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
19 1/2"
(49.5CM)
14" (35.5CM) MAXIMUM
19 1/2" (49.5CM)
MINIMUM PLUS
RISE*
* See "VENTING" section
Appliance shown without surround.
Use the periscope kit to locate the air termination above grade. The periscope must be
installed so that when fi nal grading is completed, the bottom air slot is located a minimum
12” (30.5cm) above grade. The maximum allowable vent length is 10’ (3.1m) for a
replace and 8’ (2.4m) for a stove.
4.3 special vent installations
4.3.1 periscope termination
12"
(30.5CM)
MINIMUM
TO GRADE
30" (76.2CM)
MINIMUM
19 1/2"
(49.5CM)
W415-1606 / C / 11.08.17
EN
12
venting requirements
4.4 vent terminal clearances
EN
W415-1606 / C / 11.08.17
13
venting requirements
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
COVERED BALCONY APPLICATIONS ††*
Q
MIN
R
MAX
MAX
R
= 3 feet
(0.9m)
= 2 x
≤ 15 feet
(4.6m)
Q
ACTUAL
R
Q
S
G
P
INSTALLATIONS
CANADA U.S.A.
A
12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony.
B
12” (30.5cm)
Δ
9” (229mm) Clearance to windows or doors that open.
C
12” (30.5cm)* 12” (30.5cm)* Clearance to permanently closed windows.
D
18”(45.7cm)** 18” (45.7cm)**
Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’ (0.6m)
from the center line of the terminal.
E
18” (45.7cm)** 18” (45.7cm)** Clearance to unventilated soffit.
F
0” (0mm) 0” (0mm) Clearance to an outside corner wall.
G
12” (30.5cm)*** 12” (30.5cm)***
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
12” (30.5cm)*** 12” (30.5cm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H
3’(0.9m) 3’(0.9m)****
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum
vertical distance of 15’ (4.6m).
I
3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J
12” (30.5cm) 9” (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K
6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
L
7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
N
16” (40.6cm) 16” (40.6cm) Clearance above the roof.
O
2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
P
8’ (2.4m) 8’ (2.4m)
Roof must be non-combustible without openings.
Q
3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R
6’ (1.8m) 6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening
between the terminal and the open side of the structure.
S
12” (30.5cm) 12” (30.5cm) Clearance under a covered balcony
Δ The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
4.5 horizontal termination
0’
0’
10’
10’
15’
15’
20’
25’
20’
30’
40’
5’
1 1/2’
(18”)
1 1/2’
(18”)
35 3/4’
(429”)
5’
1-2 elbow zone
1-3 elbow zone
1-4 elbow zone
H
V
(For vent runs that exceed the graph
parameters, a power vent is required).
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
4 3/4’
(57”)
17 1/4’
(207.6”)
1-5 elbow zone
W415-1606 / C / 11.08.17
EN
14
venting requirements
4.6 vertical termination
10’
10’
15’
15’
20’
25’
20’
30’
40’
5’
39’
(468”)
1 elbow zone
1-2 elbow zone
1-3 elbow zone
H
V
(For vent runs that exceed the graph
parameters, a power vent is required).
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
0’
0’
1’
(12”)
3
(36”)
5’
4 3/4’
(57”)
1-4 elbow zone
1-5 elbow zone
1-6 elbow zone
EN
W415-1606 / C / 11.08.17
15
venting requirements
W415-1606 / C / 11.08.17
EN
16
installation
5.0 installation
42.1
!
WARNING
Ensure to unpack all loose materials from inside the fi rebox prior to connecting the gas and electrical supply
If your appliance is supplied with a remote, ensure the remote receiver is in the “OFF” position prior
to connecting the gas and electrical supply to the appliance.
For safe and proper operation of the appliance, follow the venting instructions exactly.
The appliance exhaust fl ue collar must be sealed using Mill Pac. All exhaust and intake vent pipe joints
must be sealed using red RTV high temp silicone sealant (W573-0002) (not supplied) or black high temp Mill
Pac (W573-0007) (not supplied).
If using pipe clamps to connect rigid vent components, a minimum of 3 screws must also be used to ensure
the connection cannot slip off.
Do not clamp the fl exible vent pipe.
Risk of fi re, explosion, or asphyxiation. Improper support of the entire venting system may allow vent to sag
and separate. Use vent run supports and connect vent sections per installation instructions.
Risk of fi re, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to allow for the
installation of the attic shield and to maintain clearances to combustibles.
Do not fi ll the space between the vent pipe and enclosure with any type of material. Do not pack insulation
or combustibles between ceiling fi restops. Always maintain specifi ed clearances around venting and fi restop
systems. Install wall shields and fi restops as specifi ed. Failure to keep insulation or other materials away from
vent pipe may cause fi re.
!
WARNING
Risk of fi re!
In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the appliance
body, it is recommended that the walls of the appliance enclosure be “fi nished” (i.e. drywall / sheetrock),
as you would fi nish any other outside wall of a home. This will ensure that clearance to combustibles is
maintained within the cavity.
Do not notch the framing around the appliance stand offs. Failure to maintain air space clearance may cause
over heating and fi re. Prevent contact with sagging or loose insulation or framing and other combustible
materials. Block opening into the chase to prevent entry of blown-in insulation. Make sure insulation and
other materials are secured.
When constructing the enclosure allow for fi nishing material closer than the minimums listed must be
constructed entirely of non-combustible materials. Materials consisting entirely of steel, iron, brick, tile,
concrete, slate, glass or plasters, or any combination thereof are suitable. Materials that are reported as
passing ASTM E136, standard test method for behaviour of materials in a vertical tube furnace at 1382ºF
(750ºC) and UL763 shall be considered non-combustible materials.
Minimum clearance to combusibles must be maintained or a serious fi re hazard could result.
The appliance requires a minimum enclosure height. Measure from the appliance base.
If steel stud framing kits with cement board are provided, or specifi ed in the installation instructions, they
must be installed.
If specifi ed in the installation instruction, fi nishing must be done using a non-combustible board, ceramic tile,
marble, etc. Do NOT use wood or drywall. Any fi re rated drywall is not acceptable.
When using optional fi nishing accessories, the framing dimensions and fi nishing materials may differ from
what is outlined in the section below; refer to the leafl et instructions supplied in the accessory kit for specifi c
framing and fi nishing specifi cations.
44.1
note:
EN
W415-1606 / C / 11.08.17
17
installation
A. Level and affix the mounting ‘template’ to the wall at the desired location and height. The centre of the
vent pipe must be centered between wall studs.
B. Using the ‘template’, mark the holes for the vent, gas and electrical inlets, and mounting screw locations
(must be into studs). See “MINIMUM CLEARANCES TO COMBUSTIBLES” section.
NOTE : Use the appropriate cutout on the mounting ‘template’ for combustible material.
C. Remove the mounting ‘template’ from the wall and cut/drill the required holes as marked.
D. Form the vent shield until the four screw holes overlap then secure from the inside out. (FIG. 1)
NOTE : Securing from the outside in will puncture venting.
E. Bend the four tabs on the firestop spacer outwards. Slide the vent shield into the firestop spacer aligning
the holes within the tabs and secure. (FIG. 2)
F. The vent shield and firestop spacer have been designed to accommodate a maximum wall depth of 14"
(35.6cm). The vent shield must extend the full depth of the combustible wall. Trim the vent shield to suit
as necessary.
G. Apply a bead of caulking (not supplied) to the flange perimeter and wings of the firestop plate. Install the
wall mounting plate assembly with the vent shield into the wall. (FIG. 3)
NOTE : Ensure the assembly is levelled.
H. Look through slotted holes on the wall mounting plate for pre-marked stud locations and secure wall
mounting plate assembly using a minimum of four screws (minimum one screw per corner must be
mounted to a wall stud). (FIG. 4)
NOTE : For typical stud wall with drywall installation, fasteners are provided and must engage
into frame/studs.
I. See the following sections up to the “FINISHING” section for venting and mounting instructions.
REAR VIEW
CAULKING
5.1 mounting plate installation (for typical drywall construction)
FIG.1 FIG.2
FIG.3 FIG.4
TYPE 1 (X4) TYPE 1 (X4)
TYPE 4 (X4)TYPE 3 (X4)
Bottom of appliance must maintain 6” clearance
to combustible. See “MINIMUM CLEARANCE TO
COMBUSTIBLES” section.
NOTE : For ease of installation, we recommend
installing fasteners into the 4 outer slots.
Fasteners must be secured to a stud.
W415-1606 / C / 11.08.17
EN
18
installation
5.2 mounting plate installation (for concrete)
A. Level and affix the mounting ‘template’ to the wall at the desired location and height.
B. Using the ‘template’, mark the holes for the vent, gas and electrical inlets, and wall anchor locations. See
“MINIMUM CLEARANCES TO COMBUSTIBLES” section.
NOTE : Use the appropriate cutout on the mounting ‘template’ for non-combustible material.
C. Remove the mounting ‘template’ from the wall and cut/drill the required holes as marked.
D. Remove the four fasteners that secure the firestop spacer assembly (complete with the wall plate) from
the wall mounting plate. (FIG. 1)
E. Place the wall mounting plate against the non-combustible wall and align the wall mounting plate hole
with the vent hole. Level the wall mounting plate. Once leveled, secure the wall mounting plate to the wall
through the dimpled holes using four fasteners (not supplied).
NOTE : For non-combustible installation, wall anchors (not supplied) will be required.
F. Look through slotted holes on the wall mounting plate for pre-marked mounting locations and secure wall
mounting plate using a minimum of one fastener per corner (not supplied). (FIG. 2)
G. See the following sections up to the “FINISHING” section for venting and mounting instructions.
FIG.2
5.3 using flexible vent components
FIG.1
17.1
For safe and proper operation of the appliance, follow the venting instructions
exactly.
The vent system must be supported approximately every 3 feet (0.9m) for
both vertical and horizontal runs. Use Wolf Steel Ltd. support ring assembly
or equivalent noncombustible strapping to maintain the minimum clearance to
combustibles for both vertical and horizontal runs.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high temperature
red RTV silicone W573-0002 (not supplied) or the high temperature sealant W573-
0007 Mill Pac (not supplied). However, the high temperature sealant W573-0007
Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe and
the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
“Wolf Steel Approved Venting” or “E2” as identifi ed by the stamp only on the fl ex pipes.
Elbow
Spacers
Do not allow the inner fl ex pipe to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight.
Spacers are attached to the inner fl ex pipe at predetermined intervals to maintain an even air gap to the outer
ex pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each
elbow to ensure this gap is maintained. These spacers must not be removed.
!
WARNING
EN
W415-1606 / C / 11.08.17
19
installation
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor.
See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm)
clearance between the vent pipe and any combustible material. Try to
center the vent pipe location midway between two joists to prevent
having to cut them. Use a plumb bob to line up the center of the
openings. A vent pipe shield will prevent any materials such as
insulation, from fi lling up the 1" (25mm) air space around the pipe.
Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished
ceiling), and secure over the opening in the ceiling. A fi restop must be placed
on the bottom of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around and place a
restop spacer over the vent shield to restrict cold air from being drawn into the
room or around the fi replace. Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply
Mill Pac sealant (W573-0007) (not supplied) or red RTV silicone (W573-0002) (not
supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm)
air space around the pipe.
21.1B
CAULKING
VENT PIPE
SHIELD
FIRESTOP
UNDERSIDE OF
JOIST
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
8”
8”
the additional length needed for the fi nished wall surface. Apply
a heavy bead of the Mill Pac sealant (W573-0007) (not
supplied) to the inner sleeve of the air terminal. Slip the
vent pipe a minimum of 2” (50.8mm) over the inner
sleeve of the air terminal and secure with a minimum
of 3 screws.
Using the outer fl ex pipe, slide over the outer
combustion air sleeve of the air terminal and secure with
a minimum of 3 screws. Seal using red RTV silicone
(W573-0002) (not supplied).
SCREWS
2" (50.8mm) OVERLAP
OUTER FLEX PIPE
INNER FLEX
PIPE
HIGH TEMPERATURE
SEALANT
CAULKING
(SUPPLIED)
Hi-Temp Sealant
Screws
Inner Coupler
Outer Coupler
Outer Flex
Pipe
Inner Flex
Pipe
Outer Flex
Pipe
HI-TEMP
SEALANT
ADD FASTENER TYPE
Install the inner fl ex pipe to the fi replace. Secure with
a minimum 3 screws. Seal the joint and screw holes
using Mill Pac sealant (W573-0007) (not supplied).
Install the outer fl ex pipe to the fi replace. Secure with
a minimum of 3 screws. Seal the joints using red RTV
silicone (W573-0002) (not supplied).
HIGH
TEMPERATURE
SEALANT
SCREWS
1
1
/2” OVERLAP
(38.1mm)
ADD FASTENER TYPE
TYPE 7 (X4)
TYPE 5 (X6)
TYPE 5 (X6)
5.3.1 appliance vent connection
5.3.2 vertical installation
5.3.3 horizontal air terminal installation
W415-1606 / C / 11.08.17
EN
20
installation
5.3.4 vertical air terminal installation (flexible)
SCREWS
2" (50.8mm) OVERLAP
OUTER FLEX PIPE
INNER FLEX
PIPE
HIGH TEMPERATURE
SEALANT
CAULKING
(SUPPLIED)
Hi-Temp Sealant
Screws
Inner Coupler
Outer Coupler
Outer Flex
Pipe
Inner Flex
Pipe
Outer Flex
Pipe
HI-TEMP
SEALANT
ADD FASTENER TYPE
A. Fasten the roof support to the roof using 6 screws. The roof support is
optional. In this case, the venting is to be adequately supported using
either an alternate method suitable to the authority having jurisdiction or
the optional roof support.
B. Stretch the inner fl ex pipe to the required length. Slip the inner fl ex
pipe a minimum of 2” (51mm) over the inner pipe of the air terminal
connector and secure with a minimum of three screws, when 4/7, 5/8
and 3/5 venting is used and a minimum of six screws when using 8/10
or 8/11 venting. Seal using a heavy bead of red RTV silicone (W573-
0002) (not supplied).
C. Repeat using the outer fl ex pipe, using a heavy bead of red RTV
silicone (W573-0002) (not supplied) and a minimum of three screws,
when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws
when using 8/10 or 8/11 venting.
D. Thread the air terminal connector / vent pipe assembly down through
the roof. The air terminal must be positioned vertically and plumb.
Attach the air terminal connector to the roof support, ensuring that the
top of the air terminal is 16” (40.6cm) above the highest point that it
penetrates the roof.
E. Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing above
the top of the fl ashing. Slide the fl ashing underneath the sides and
upper edge of the shingles. Ensure that the air terminal connector is
properly centered within the fl ashing, giving a 3/4” (19mm) margin all
around. Fasten to the roof. Do not nail through the lower portion of the
ashing. Make weather-tight by sealing with caulking. Where possible,
cover the sides and top edges of the fl ashing with roofi ng material.
F. Aligning the seams of the terminal and air terminal connector, place the
terminal over the air terminal connector making sure the vent pipe goes
into the hole in the terminal. Secure with a minimum of three screws,
when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws
when using 8/10 or 8/11 venting.
G. Apply a heavy bead of weatherproof caulking 2” (51mm) above the
ashing. Install the storm collar around the air terminal and slide down
to the caulking. Tighten to ensure that a weather-tight seal between the
air terminal and the collar is achieved.
H. If more vent pipe needs to be used to reach the appliance, see “horizontal
air terminal installation” section.
18.5
Roof Support
Inner Flex Pipe
Inner Pipe
Red RTV
Silicone
(W572-0002)
Air
Terminal
Connector
Outer Flex Pipe
Storm Collar
Flashing
Caulking
Weather
Sealant
2” (51mm)
Air Inlet
Base
!
WARNING
Maintain a minimum 2” (51mm) space between the air inlet base and the storm collar.
NOTE: Fastening hardware provided with appropriate roof terminal and liner kits.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

NAPOLEON WHD48 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire
Ce manuel convient également à

dans d''autres langues